What are the key features of the DURASTAR DRF2TA3624ASTNJN0 air handler?

The DURASTAR DRF2TA3624ASTNJN0 air handler includes the following features:

• Constant Torque Motor (ECM)

• Two-Stage Airflow

• Thermal Expansion Valve (TXV) for cooling or heat pump operation

• Efficiencies from 13.4 to 14.3 SEER2

• Front or Bottom Return with aluminum tube and fin coil

• Wall-hanging brackets

• Built-in Filter Rack

• Molex Plug Connections for field installed heater kits

• Dual Voltage Direct Drive Blower with multi-speed motor

• Thermoplastic Drain Pan with bottom primary and secondary connections

• Cabinet air leakage is less than 2% at 1 inch H2O when tested in accordance with ASHRAE Standard 193

• Can be field wired for single or two-stage applications

• Optional Decorative Grill for front return applications

• Optional Factory Installed Condensate Float Switch which shuts off the outdoor unit if the condensate pan becomes clogged


What standard equipment is included with the DURASTAR DRF2TA3624ASTNJN0?

The standard equipment for the DURASTAR DRF2TA3624ASTNJN0 includes:

• Field convertible air supply

• Durable framed cleanable air filter

• Indoor coil design that provides low air side pressure drop, high performance, and compact size

• PVC condensate elbow is standard on all coils

• All indoor coils have aluminum tubing and aluminum fins

• Molded polymer corrosion-resistant condensate drain pan

• Supply and return duct flanges

• High and low voltage connection points inside the cabinet

• Concentric knockouts for power connection with a hole size up to 2 inches [51 mm] for a 1 1/2 inch [38mm] conduit

• Internal checked TX valves for quiet refrigerant metering

• Front refrigerant and drain connection


What is the airflow configuration for the DURASTAR DRF2TA3624ASTNJN0?

All DURASTAR DRF2TA3624ASTNJN0 units are configured for vertical upflow. The units cannot be installed in any other configuration.


What are the unit dimensions, weight, and filter size for the DURASTAR DRF2TA3624ASTNJN0?

Model Unit Width In. [mm] Unit Height In. [mm] Unit Depth In. [mm] Filter Size in. x in. x in. [mm x mm x mm] Air Flow CFM (Nom.) [L/s] Low/High Unit Weight/Shipping Weight (Lbs.) [kg]
DRF2TA3624 24 [609.6] 36 [914.4] 21 [533.4] 20 X 25 X 1 [508 X 635 X 25.4] 1000 [472] / 1200 [566] 95 [43] x 105 [48]

What are the airflow operating limits for the DURASTAR DRF2TA3624ASTNJN0?

The airflow operating limits for the DURASTAR DRF2TA3624ASTNJN0 (Model Cabinet Size 24) are as follows:

Parameter Value
Cooling BTUH x 1,000 -36
Cooling Tons Nominal 3
Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] 1350 [637]
Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] 1200 [566]
Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] 1080 [510]
Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s] 10 / 976 [461]
Maximum Electric Heat Rise °F [°C] 44 [7]

What is the optimal external static range for the DURASTAR DRF2TA3624ASTNJN0?

For optimum blower performance, operate the DURASTAR DRF2TA3624ASTNJN0 in the 0.3 to 0.7 inches W.C. external static range. Units with coils should be applied with a minimum of 0.1 inch W.C. external static range.


How do the motor speed taps on the DURASTAR DRF2TA3624ASTNJN0 work?

The DURASTAR DRF2TA3624ASTNJN0 air handler has a 5-speed constant torque motor. The speed taps are designated as follows:

Speed tap 1: For continuous fan operation.

Speed tap 2 (low static) and speed tap 3 (high static): For lower tonnage units (1.5 or 2.5 tons).

Speed tap 4 (low static) and speed tap 5 (high static): For higher tonnage units (2.0 or 3.0 tons). As a 3.0 ton unit, the DURASTAR DRF2TA3624ASTNJN0 uses taps 4 and 5 for cooling/heating operation.


How do I adjust the motor speed taps on the DURASTAR DRF2TA3624ASTNJN0 based on external static pressure?

To adjust the motor speed for your application’s needs, follow these guidelines:

• Use the low static speed tap (tap 4) for external static pressures below 0.5″ WC.

• Use the high static speed tap (tap 5) for external static pressures exceeding 0.5″ WC.

To change the setting, move the blue wire to the appropriate speed tap on the motor terminal block.


What is the factory-shipped speed tap setting for the DURASTAR DRF2TA3624ASTNJN0?

The DURASTAR DRF2TA3624ASTNJN0 air handler is always shipped from the factory with the motor set to speed tap 5.


How is the airflow for the continuous fan (speed tap 1) determined on the DURASTAR DRF2TA3624ASTNJN0?

The airflow for the continuous fan, which uses speed tap 1, is always set at 50% of the airflow of speed tap 4.


What is the airflow performance data for the DURASTAR DRF2TA3624ASTNJN0 (3 Tons)?

The following table shows the CFM Dry Delivery, RPM, and Watts at various external static pressures for the 3-ton DURASTAR DRF2TA3624ASTNJN0.

Motor Speed Parameter External Static Pressure – Inches W.C.
0.1 0.2 0.3 0.4 0.5 0.6 0.7
4 (low static) CFM 808 750 698 633 568 504 448
RPM 615 665 713 780 842 884 929
Watts 91.4 97.7 103.9 112.4 120.2 125.5 131.2
5 (high static) CFM 1241 1201 1148 1109 1065 1028 983
RPM 847 880 905 916 955 991 1035
Watts 246.3 254.9 260.9 263.8 273.1 282.5 293.3

What are the blower motor electrical specifications for the DURASTAR DRF2TA3624ASTNJN0 without electric heat?

Model/Nominal Cooling Tons Voltage Phase Hertz HP [W] RPM Speeds Circuit Amps. Minimum Circuit Ampacity Maximum Circuit Protector
DRF2TA3624 208/230 1 60 1/2 [373] 300-1100 4 2.7 4 15

*Blower motors are all single-phase motors.


What is the electrical data for the DURASTAR DRF2TA3624ASTNJN0 when an electric heater kit is installed?

Model No. Heater kW PH/Hz No. Elements – kW Per (208/240V) Type Supply Circuit Circuit Amps. Motor Ampacity Minimum Circuit Ampacity Maximum Circuit Protection
RXHJ-24B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 2.7 17/19 20/20
RXHJ-24B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 2.7 25/29 25/30
RXHJ-24B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 2.7 36/41 40/45
RXHJ-24B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 2.7 47/54 50/60

What are the electrical power and grounding requirements for the DURASTAR DRF2TA3624ASTNJN0?

When installing the DURASTAR DRF2TA3624ASTNJN0, adhere to the following electrical requirements:

• Field wiring must comply with the National Electrical Code (C.E.C. in Canada) and any applicable local ordinances.

• The product must be sufficiently grounded.

• Supply wiring must be 75°C minimum copper conductors only.

• A grounding lug is provided.

• Refer to the electrical data tables for specific Ampacity ratings and circuit protector requirements.


What optional accessories and kits are available for the DURASTAR DRF2TA3624ASTNJN0?

Several kits and accessories are available for the DURASTAR DRF2TA3624ASTNJN0:

Drain Pan Over Flow Switch (RXHK-A01): This switch detects condensate drain blockage and shuts down the outdoor unit to prevent water damage.

Bottom Return Conversion Kit (RXHK-B02): This kit is used to divert the return air from the factory standard front return to a bottom return configuration.

Louvered Cabinet Grill (RXHK-C02): This is a decorative grill that covers the return air opening of the front return air handler.

Decorative Wall Grill (RXHK-D01 or RXHK-D02): This grill is used in applications where the air handler is installed in a closet or interior wall, allowing adequate return air back to the unit.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD DURASTAR DRF2TA3624ASTNJN0 (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.