What are the features and benefits of the DURASTAR DRF2TA3624ASTNJB8F air handler?

The DURASTAR DRF2TA3624ASTNJB8F air handler includes the following features and benefits:

General Features:

• Front or Bottom Return with aluminum tube and fin coil

• TXV for cooling or heat pump operation

• Wall-hanging brackets

• Built in Filter Rack

• Molex Plug Connections for field installed heater kits

• Dual Voltage Direct Drive Blower with multi-speed motor

• Thermoplastic Drain Pan with bottom primary and secondary connections

• Optional Decorative Grill for front return applications

• Optional Factory Installed Condensate Float Switch which shuts off the outdoor unit in the event the condensate pan becomes clogged

• Cabinet air leakage less than 2% at 1 inch H2O when tested in accordance with ASHRAE Standard 193

• Can be field wired for single or two stage applications

Standard Equipment:

• Exclusive Incoloy sheath type electric heating elements

• Field convertible air supply

• Durable framed cleanable air filter

• Indoor coil design provides low air side pressure drop, high performance and compact size

• PVC condensate elbow is standard on all coils

• All indoor coils have aluminum tubing and aluminum fins

• Molded polymer corrosion resistant condensate drain pan

• Supply and return duct flanges

• High and low voltage connection points inside cabinet

• Concentric knockouts provided for power connection with hole size up to 2 inches [51 mm] for 1 1/2 inch [38mm] conduit

• Internal checked TX valves for quiet refrigerant metering

• Front refrigerant and drain connection


How is the model number for the DURASTAR DRF2TA3624ASTNJB8F air handler identified?

The model number nomenclature for the DURASTAR DRF2TA3624ASTNJB8F air handler series is broken down as follows:

DR F 2 T A 36 24 A S T N J B 8 F
Brand Product Category Stages Of Airflow Motor Type Refrigerant Capacity Width Major Series Efficiency Metering Coil Series Voltage Disconnect Factory Heat Option Code
DR – Durastar F – Front Return 2 – 2-Stage T – Constant Torque A – R-410A 24 – 24,000 [7.03 kW]
36 – 36,000 [10.55 kW]
21 – 21″
24 – 24.5″
A – 1st Design S – Standard T – TXV N – N Coil J – 208-240/1/60 B – Breaker
N – None
0 – No Heat
3 – 3 kW
5 – 5 kW
8 – 8 kW
1 – 10 kW
F – Float Switch

What are the return air opening dimensions for the DURASTAR DRF2TA3624ASTNJB8F series?

Return Air Opening Dimensions
Model Cabinet Size Return Air Opening Width (Inches) Return Air Opening Depth/Length (Inches)
17 15 7/8 19 3/4
21 19 3/8 19 3/4
24 22 7/8 19 3/4

What are the unit dimensions and weights for the DURASTAR DRF2TA3624ASTNJB8F series models?

Unit Dimensions & Weights
Model (A) Unit Width In. [mm] (B) Unit Height In. [mm] (C) Unit Depth In. [mm] (D) Return Air Opening Width In. [mm] (E) Return Air Opening Height In. [mm] Filter Size in. x in. x in. [mm x mm x mm] Air Flow CFM (Nom.) [L/s] Unit Weight/Shipping Weight (Lbs.) [kg]
Low High
DRF2TA2421 21 1/2 [546.1] 36 [914.4] 17 [431.8] 20 [508.0] 17 7/16 [442.9] 20 X 20 X 1 [508 X 508 X 25.4] 600 [283] 800 [378] 95 [43] x 105 [48]
DRF2TA3624 24 [609.6] 36 [914.4] 21 [533.4] 23 [584.2] 21 3/8 [542.9] 20 X 25 X 1 [508 X 635 X 25.4] 1000 [472] 1200 [566] 95 [43] x 105 [48]

What are the airflow operating limits for the DURASTAR DRF2TA3624ASTNJB8F series?

For optimum blower performance, operate the DURASTAR DRF2TA3624ASTNJB8F unit in the .3 [8 mm] to .7 inches [18 mm] W.C. external static range. Units with coils should be applied with a minimum of .1 inch [3 mm] W.C. external static range. The airflow operating limits are as follows:

Airflow Operating Limits
Model Cabinet Size 21 24
Cooling BTUH x 1,000 -24 -36
Cooling Tons Nominal 2 3
Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (450 CFM [212 L/s]/Ton Nominal) 900 [425] 1350 [637]
Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (400 CFM [189 L/s]/Ton Nominal) 800 [378] 1200 [566]
Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [14 L/s]/1,255 BTUH) (360 CFM [170 L/s]/Ton Nominal) 720 [340] 1080 [510]
Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s] 10
690 [326]
10
976 [461]
Maximum Electric Heat Rise °F [°C] 44 [7] 44 [7]

What is the airflow performance data for the DURASTAR DRF2TA3624ASTNJB8F air handler with a Constant Torque (ECM) Motor?

115V/208V/240V Airflow Performance Data—DRF2TA (Constant Torque (ECM) Motor)
Model/ Nominal Cooling Capacity Air-Flow Range (Max/Min) CFM Manufacturer Recommended Blower Size/ Motor HP # of Speeds Motor Speed From Factory Motor Speed CFM Dry Delivery/filter/heaters/RPM/Watts External Static Pressure-Inches W.C.
0.1 0.2 0.3 0.4 0.5 0.6 0.7
DRF2TA24 1.5 Tons 825/510 10×6 1/3 Hp 2 speed dual voltage 5 2 CFM 537 495 451 404 343 286 252
RPM 608 656 702 752 826 879 935
Watts 51.2 54.5 57.6 60.9 65.9 69.5 73.2
3 CFM 735 702 666 634 600 565 528
RPM 757 794 836 872 905 942 981
Watts 99.1 103.2 107.7 112 115.6 119.6 124.1
DRF2TA24 2 Tons 973/733 10×6 1/3 Hp 2 speed dual voltage 5 4 CFM 654 616 581 542 503 463 399
RPM 694 736 777 818 858 899 971
Watts 76.4 80.1 83.7 87.6 91.3 95.1 101.6
5 CFM 887 858 830 802 771 743 717
RPM 876 914 945 976 1014 1044 1070
Watts 156 161.8 166.8 171.5 177.5 182.3 186.2
DRF2TA36 2.5 Tons 1145/894 10×8 1/2 Hp 2 speed dual voltage 5 2 CFM 772 698 635 569 497 438 366
RPM 595 639 698 771 821 866 933
Watts 82.9 84.9 91.6 100 105.8 110.7 118.3
3 CFM 1106 1053 1004 962 918 864 814
RPM 776 816 838 862 901 955 1007
Watts 183.3 191.4 195.7 200.5 208.4 219.3 230.2
DRF2TA36 3 Tons 1306/1040 10×8 1/2 Hp 2 speed dual voltage 5 4 CFM 808 750 698 633 568 504 448
RPM 615 665 713 780 842 884 929
Watts 91.4 97.7 103.9 112.4 120.2 125.5 131.2
5 CFM 1241 1201 1148 1109 1065 1028 983
RPM 847 880 905 916 955 991 1035
Watts 246.3 254.9 260.9 263.8 273.1 282.5 293.3

NOTE: All DRF2TA air-handlers have 5 speed constant torque motors.

• Speed tap 1 is for continuous fan.

• Speed tap 2 (low static) and speed tap 3 (high static) are for lower tonnage (1.5 or 2.5 tons).

• Speed tap 4 (low static) and speed tap 5 (high static) are for higher tonnage (2.0 or 3.0 tons).

• DRF2TA air handlers are always shipped from factory at speed tap 5.

• The low static speed tap 2 (lower tonnage) and 4 (higher tonnage) are for external static pressures below 0.5″ WC. The high static speed tap 3 (lower tonnage) and 5 (higher tonnage) are used for external static exceeding 0.5″ WC. Move the blue wire to the appropriate speed tap on the motor terminal block as required by the application needs.

• The airflow for continuous fan (speed tap 1) is always set at 50% of the speed tap 4.

• The above airflow table lists the airflow information for air handlers with maximum heater allowed for each model.


What are the electrical specifications for the blower motor only on the DURASTAR DRF2TA3624ASTNJB8F?

The following table details the electrical specifications for the blower motor without an electric heat kit. Blower motors are all single phase motors.

Electrical Data—Blower Motor Only—No Electric Heat
Model/Nominal Cooling Tons Voltage Phase Hertz HP [W] RPM Speeds Circuit Amps. Minimum Circuit Ampacity Maximum Circuit Protector
DRF2TA2421 208/230 1 60 1/3 [249] 300-1100 4 1.9 3 15
DRF2TA3624 208/230 1 60 1/2 [373] 300-1100 4 2.7 4 15

What are the electrical specifications for the DURASTAR DRF2TA3624ASTNJB8F when using an electric heat kit?

Installation of a U.L. Listed original equipment manufacturer provided heater kit is recommended for all auxiliary heating requirements. The electrical data for units with electric heat is as follows:

Electrical Data—with Electric Heat
Cooling Capacity Tons Model No. Heater kW PH/Hz No. Elements – kW Per (208/240V) Type Supply Circuit Circuit Amps. Motor Ampacity Minimum Circuit Ampacity Maximum Circuit Protection
DRF2TA3624 RXHJ-21B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 1.9 16/18 20/20
RXHJ-21B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 1.9 0.9 25/30
RXHJ-21B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 1.9 35/40 35/40
RXHJ-21B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 1.9 0.9 50/60
DRF2TA3636 RXHJ-24B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 2.7 17/19 20/20
RXHJ-24B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 2.7 25/29 25/30
RXHJ-24B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 2.7 36/41 40/45
RXHJ-24B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 2.7 47/54 50/60

• Electric heater BTUH – (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)

• J voltage (230V) single phase air handler is designed to be used with single or three phase.

• Supply circuit protective devices may be fused or “HACR” type circuit breakers.

• If non-standard fuse size is specified, use next size larger standard fuse size. Without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead.

• Largest motor load is included in single circuit or circuit 1 of multiple circuits.

• Do not use 480 volts electrical heaters on 230 volts air handler.


What are the electrical power wiring and grounding requirements for the DURASTAR DRF2TA3624ASTNJB8F?

When wiring the DURASTAR DRF2TA3624ASTNJB8F, please adhere to the following requirements:

• Field wiring must comply with the National Electrical Code.

• This product must be sufficiently grounded in accordance with (C.E.C. in Canada) and any applicable local ordinance.

• Supply wiring must be 75°C minimum copper conductors only, in accordance with the National Electrical Code (C.E.C. in Canada) and any applicable local ordinance.

• See electrical data for product Ampacity rating and Circuit Protector requirement.

• A grounding lug is provided.


What is the purpose of the Drain Pan Over Flow Switch RXHK-A01 for the DURASTAR DRF2TA3624ASTNJB8F?

The Drain Pan Over Flow Switch RXHK-A01 is an accessory used to detect condensate drain blockage. If a blockage is detected, it will shut down the outdoor unit to prevent structural damage to the surrounding structures of the air handler.

What is the Bottom Return Conversion Kit RXHK for the DURASTAR DRF2TA3624ASTNJB8F?

The Bottom Return Conversion Kit is used to divert the return air from the factory standard front return to a bottom return configuration. The correct kit depends on your specific indoor unit model.

Accessory Number Indoor Unit
RXHK-B01 DRF2TA-FR18
DRF2TA-FR24
RF1T-FR24
RXHK-B02 DRF2TA-FR30
DRF2TA-FR36
RF1T-FR36

What is the Louvered Cabinet Grill RXHK for the DURASTAR DRF2TA3624ASTNJB8F?

The Louvered Cabinet Grill is a decorative grill accessory that covers the return air opening of the front return air handler. The correct grill depends on your specific indoor unit model.

Accessory Number Indoor Unit
RXHK-C01 DRF2TA-FR18
DRF2TA-FR24
RF1T-FR24
RXHK-C02 DRF2TA-FR30
DRF2TA-FR36
RF1T-FR36

When is the Decorative Wall Grill RXHK-D01 or RXHK-D02 used with the DURASTAR DRF2TA3624ASTNJB8F?

The Decorative Wall Grill accessory (RXHK-D01 or RXHK-D02) is used in applications where the air handler is installed in a closet or interior wall. It allows adequate return air back to the unit. Please refer to the installation instructions for the specific grill for complete dimensional information.

What should be done before proceeding with the installation of the DURASTAR DRF2TA3624ASTNJB8F?

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD DURASTAR DRF2TA3624ASTNJB8F (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.