What are the features and benefits of the DURASTAR DRF2TA3624ASTNJB5F air handler?

The DURASTAR DRF2TA3624ASTNJB5F air handler includes the following features and benefits:

• Front or Bottom Return with aluminum tube and fin coil

• TXV for cooling or heat pump operation

• Wall-hanging brackets

• Built in Filter Rack

• Molex Plug Connections for field installed heater kits

• Dual Voltage Direct Drive Blower with multi-speed motor

• Thermoplastic Drain Pan with bottom primary and secondary connections

• Optional Decorative Grill for front return applications

• Optional Factory Installed Condensate Float Switch which shuts off the outdoor unit in the event the condensate pan becomes clogged

• Cabinet air leakage less than 2% at 1 inch H2O when tested in accordance with ASHRAE Standard 193

• Can be field wired for single or two stage applications


How is the model number for the DURASTAR DRF2TA3624ASTNJB5F series identified?

The model number for the DURASTAR DRF2TA3624ASTNJB5F series provides specific details about the unit’s configuration. The breakdown is as follows:

Code Position Description
DR Brand DR – Durastar
F Product Category F – Front Return
2 Stages Of Airflow 2 – 2-Stage
T Motor Type T – Constant Torque
A Refrigerant A – R-410A
24 / 36 Capacity 24 – 24,000 [7.03 kW] / 36 – 36,000 [10.55 kW]
21 / 24 Width 21 – 21″ / 24 – 24.5″
A Major Series A – 1st Design
S Efficiency S – Standard
T Metering T – TXV
N Coil Series N – N Coil
J Voltage J – 208-240/1/60
B / N Disconnect B – Breaker / N – None
0, 3, 5, 8, 1 Factory Heat 0 – No Heat, 3 – 3 kW, 5 – 5 kW, 8 – 8 kW, 1 – 10 kW
F Option Code F – Float Switch

What is the standard equipment included with the DURASTAR DRF2TA3624ASTNJB5F?

The standard equipment for the DURASTAR DRF2TA3624ASTNJB5F includes:

• Exclusive Incoloy sheath type electric heating elements

• Field convertible air supply

• Durable framed cleanable air filter

• Indoor coil design provides low air side pressure drop, high performance and compact size

• PVC condensate elbow is standard on all coils

• All indoor coils have aluminum tubing and aluminum fins

• Molded polymer corrosion resistant condensate drain pan

• Supply and return duct flanges

• High and low voltage connection points inside cabinet

• Concentric knockouts provided for power connection with hole size up to 2 inches [51 mm] for 1 1/2 inch [38mm] conduit

• Internal checked TX valves for quiet refrigerant metering

• Front refrigerant and drain connection


What are the unit dimensions, weights, and filter sizes for the DURASTAR DRF2TA3624ASTNJB5F series?

The dimensions, weights, and other specifications for the DURASTAR DRF2TA3624ASTNJB5F series are detailed in the table below.

Model (A) Unit Width In. [mm] (B) Unit Height In. [mm] (C) Unit Depth In. [mm] (D) Return Air Opening Width In. [mm] (E) Return Air Opening Height In. [mm] Filter Size in. x in. x in. [mm x mm x mm] Air Flow CFM (Nom.) [L/s] (Low/High) Unit Weight/Shipping Weight (Lbs.) [kg]
DRF2TA2421 21 1/2 [546.1] 36 [914.4] 17 [431.8] 20 [508.0] 17 7/16 [442.9] 20 X 20 X 1 [508 X 508 X 25.4] 600 [283] / 800 [378] 95 [43] / 105 [48]
DRF2TA3624 24 [609.6] 36 [914.4] 21 [533.4] 23 [584.2] 21 3/8 [542.9] 20 X 25 X 1 [508 X 635 X 25.4] 1000 [472] / 1200 [566] 95 [43] / 105 [48]

What are the airflow operating limits for the DURASTAR DRF2TA3624ASTNJB5F series?

For optimal blower performance, the DURASTAR DRF2TA3624ASTNJB5F series should be operated in the .3 [8 mm] to .7 inches [18 mm] W.C. external static range. Units with coils should be applied with a minimum of .1 inch [3 mm] W.C. external static range. The specific operating limits are as follows:

Model Cabinet Size 21 24
Cooling BTUH x 1,000 -24 -36
Cooling Tons Nominal 2 3
Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (450 CFM [212 L/s]/Ton Nominal) 900 [425] 1350 [637]
Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (400 CFM [189 L/s]/Ton Nominal) 800 [378] 1200 [566]
Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [14 L/s]/1,255 BTUH) (360 CFM [170 L/s]/Ton Nominal) 720 [340] 1080 [510]
Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s] 10
690 [326]
10
976 [461]
Maximum Electric Heat Rise °F [°C] 44 [7] 44 [7]

What is the airflow performance data for the DURASTAR DRF2TA3624ASTNJB5F series?

The airflow performance data for the DURASTAR DRF2TA3624ASTNJB5F series with a Constant Torque (ECM) Motor is based on cooling performance with a coil and no filter. The table below shows CFM dry delivery, RPM, and Watts at various external static pressures.

Model/Nominal Cooling Capacity Air-Flow Range (Max/Min) CFM Motor Speed External Static Pressure-Inches W.C.
0.1 0.2 0.3 0.4 0.5 0.6 0.7
DRF2TA24
1.5 Tons
825/510 2 CFM 537 495 451 404 343 286 252
RPM 608 656 702 752 826 879 935
Watts 51.2 54.5 57.6 60.9 65.9 69.5 73.2
3 CFM 735 702 666 634 600 565 528
RPM 757 794 836 872 905 942 981
Watts 99.1 103.2 107.7 112 115.6 119.6 124.1
DRF2TA24
2 Tons
973/733 4 CFM 654 616 581 542 503 463 399
RPM 694 736 777 818 858 899 971
Watts 76.4 80.1 83.7 87.6 91.3 95.1 101.6
5 CFM 887 858 830 802 771 743 717
RPM 876 914 945 976 1014 1044 1070
Watts 156 161.8 166.8 171.5 177.5 182.3 186.2
DRF2TA36
2.5 Tons
1145/894 2 CFM 772 698 635 569 497 438 366
RPM 595 639 698 771 821 866 933
Watts 82.9 84.9 91.6 100 105.8 110.7 118.3
3 CFM 1106 1053 1004 962 918 864 814
RPM 776 816 838 862 901 955 1007
Watts 183.3 191.4 195.7 200.5 208.4 219.3 230.2
DRF2TA36
3 Tons
1306/1040 4 CFM 808 750 698 633 568 504 448
RPM 615 665 713 780 842 884 929
Watts 91.4 97.7 103.9 112.4 120.2 125.5 131.2
5 CFM 1241 1201 1148 1109 1065 1028 983
RPM 847 880 905 916 955 991 1035
Watts 246.3 254.9 260.9 263.8 273.1 282.5 293.3

How are the speed taps configured on the DURASTAR DRF2TA3624ASTNJB5F?

The DURASTAR DRF2TA3624ASTNJB5F air handler has 5-speed constant torque motors. The speed taps are configured as follows:

Speed tap 1: For continuous fan operation.

Speed tap 2 (low static): For lower tonnage (1.5 or 2.5 tons) with external static pressures below 0.5″ WC.

Speed tap 3 (high static): For lower tonnage (1.5 or 2.5 tons) with external static pressures exceeding 0.5″ WC.

Speed tap 4 (low static): For higher tonnage (2.0 or 3.0 tons) with external static pressures below 0.5″ WC.

Speed tap 5 (high static): For higher tonnage (2.0 or 3.0 tons) with external static pressures exceeding 0.5″ WC.

The unit is always shipped from the factory set to speed tap 5. To adjust, move the blue wire to the appropriate speed tap on the motor terminal block as required by the application needs.

The airflow for the continuous fan (speed tap 1) is always set at 50% of the speed tap 4 airflow.


What are the electrical specifications for the blower motor only on the DURASTAR DRF2TA3624ASTNJB5F series?

The electrical data for the blower motor without electric heat for the DURASTAR DRF2TA3624ASTNJB5F series is as follows. Note that all blower motors are single phase motors.

Model/Nominal Cooling Tons Voltage Phase Hertz HP [W] RPM Speeds Circuit Amps. Minimum Circuit Ampacity Maximum Circuit Protector
DRF2TA2421 208/230 1 60 1/3 [249] 300-1100 4 1.9 3 15
DRF2TA3624 208/230 1 60 1/2 [373] 300-1100 4 2.7 4 15

What are the electrical specifications when using an electric heat kit with the DURASTAR DRF2TA3624ASTNJB5F series?

When using an original equipment manufacturer provided heater kit with the DURASTAR DRF2TA3624ASTNJB5F, refer to the following electrical data. The table shows data for 208/240V.

Cooling Capacity Tons Model No. Heater kW PH/Hz No. Elements – kW Per Type Supply Circuit Circuit Amps. Motor Ampacity Minimum Circuit Ampacity Maximum Circuit Protection
DRF2TA3624 RXHJ-21B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 1.9 16/18 20/20
RXHJ-21B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 1.9 0.9 25/30
RXHJ-21B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 1.9 35/40 35/40
RXHJ-21B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 1.9 0.9 50/60
DRF2TA3636 RXHJ-24B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 2.7 17/19 20/20
RXHJ-24B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 2.7 25/29 25/30
RXHJ-24B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 2.7 36/41 40/45
RXHJ-24B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 2.7 47/54 50/60

Important Notes:

• Electric heater BTUH = (heater watts + motor watts) x 3.414.

• J voltage (230V) single phase air handler is designed to be used with single or three phase.

• Supply circuit protective devices may be fused or “HACR” type circuit breakers.

• If a non-standard fuse size is specified, use the next size larger standard fuse size. Without the heater, bring only two leads to the terminal block, cap, insulate, and fully secure the third lead.

• The largest motor load is included in a single circuit or circuit 1 of multiple circuits.

• Do not use 480 volts electrical heaters on 230 volts air handler.


What are the power wiring and grounding requirements for the DURASTAR DRF2TA3624ASTNJB5F?

For electrical wiring, power wiring, and grounding of the DURASTAR DRF2TA3624ASTNJB5F, follow these requirements:

• Field wiring must comply with the National Electrical Code and any applicable local ordinance.

• This product must be sufficiently grounded in accordance with the National Electrical Code and any applicable local ordinance.

• Supply wiring must be 75°C minimum copper conductors only, in compliance with local ordinances.

• Refer to the electrical data for the product Ampacity rating and Circuit information.

• A grounding lug is provided, as required for the protector.


What optional accessories and kits are available for the DURASTAR DRF2TA3624ASTNJB5F?

Several optional kits and accessories are available for the DURASTAR DRF2TA3624ASTNJB5F air handler:

Drain Pan Over Flow Switch RXHK-A01: This switch is used to detect condensate drain blockage. It will shut down the outdoor unit to prevent structural damage to the surrounding area if a blockage occurs.

Bottom Return Conversion Kit RXHK-B01 / RXHK-B02: This kit is used to divert the return air from the standard front return to a bottom return configuration.

Accessory NumberIndoor Unit
RXHK-B01DRF2TA-FR18
DRF2TA-FR24
RF1T-FR24
RXHK-B02DRF2TA-FR30
DRF2TA-FR36
RF1T-FR36

Louvered Cabinet Grill RXHK-C01 / RXHK-C02: This is a decorative grill that covers the return air opening of the front return air handler.

Accessory NumberIndoor Unit
RXHK-C01DRF2TA-FR18
DRF2TA-FR24
RF1T-FR24
RXHK-C02DRF2TA-FR30
DRF2TA-FR36
RF1T-FR36

Decorative Wall Grill RXHK-D01 / RXHK-D02: This grill is used in applications where the air handler is installed in a closet or interior wall. It allows adequate return air back to the unit.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD DURASTAR DRF2TA3624ASTNJB5F (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.