AUTOMATIONDIRECT C-MORE EA9-T7CL (01) Image

FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF DOCUMENT.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF USER GUIDE.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF USER MANUAL.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF OWNER GUIDE.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF OWNER MANUAL.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF REFERENCE GUIDE.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF REFERENCE MANUAL.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF OPERATING INSTRUCTIONS.


CLICK HERE TO DOWNLOAD AUTOMATIONDIRECT C-MORE EA9-T7CL (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What should I do after unpacking my AUTOMATIONDIRECT C-MORE EA9-T7CL?

Inspect all equipment for completeness. If anything is missing or damaged, immediately contact the AutomationDirect returns department.

The contents should include:

• Quick Start Guide

• Cutout Template*

• C-more Panel

• Gasket

• DC power connector

• Mounting Clips

• Logo Label*

*Not included with EA9-T7CL-R and EA9-T7CL.


How do I power the AUTOMATIONDIRECT C-MORE EA9-T7CL using a DC power source?

Wire a dedicated 12-24 VDC power source to the DC connector on the rear of the C-more touch panel, including wiring the ground terminal to a proper equipment ground. The recommended power supply is Automation Direct p/n: PSC24-060. Then turn on the power source and check the LED status indicators on the front and rear of the touch panel for proper indication. Use 60 / 75°C copper conductors only, 12 – 24 AWG.


How do I power the AUTOMATIONDIRECT C-MORE EA9-T7CL using an AC power source?

Install a C-more AC/DC Power Adapter, p/n EA-AC, to the rear of the touch panel and wire an AC voltage source of 100-240 VAC, 50/60 Hz, to its AC connector. The recommended AC supply fuse is a 3.0A time delay, ADC p/n: MDL3. Then turn on the power source and check the LED status indicators on the front and rear of the C-more touch panel for proper indication.


What are the recommended tightening torques for the AUTOMATIONDIRECT C-MORE EA9-T7CL?

For AC Wiring with the EA-AC Adapter:

Part Torque
Power supply cable torque 71-85 oz-in (0.5-0.6 Nm)
Power connector mounting torque 71-85 oz-in (0.5-0.6 Nm)
Mounting flange screw torque 57-71 oz-in (0.4-0.5 Nm)

For DC Wiring with the DC-CON connector:

Part Torque
Power connector screw torque 70.4 oz-in (0.5 Nm)
Power connector mounting torque 56 oz-in (0.4 Nm)

What are the recommended supply fuses for the AUTOMATIONDIRECT C-MORE EA9-T7CL?

For AC Power (100-240 VAC):

• Recommended Fuse: 3.0A time delay, ADC p/n: MDL3

For DC Power (12-24 VDC):

Panel Size Rating ADC p/n
6″-10″ 2.5 A MDL2-5
12″ & 15″ 4.0 A MDL4

What do the status LEDs on the AUTOMATIONDIRECT C-MORE EA9-T7CL indicate?

The CPU Status LED (Green, Orange & Red) on the rear of the panel indicates the following:

LED State Status
Off Power Off
Green Normal – CPU Run State
Red Memory Error
Blinking Red Watchdog Timer Error
Blinking Orange OS Error
Blinking Green Power Loss Detection

The Power LED on the front of the panel indicates the following:

Color On Off
Green Power On Power Error

What safety information should I be aware of when installing and operating the AUTOMATIONDIRECT C-MORE EA9-T7CL?

To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes.

Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation.

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.


What are the technical specifications for the AUTOMATIONDIRECT C-MORE EA9-T7CL and other EA9 series panels?

Specification EA9-T6CL-R / EA9-T6CL EA9-T7CL-R / EA9-T7CL EA9-T8CL EA9-T10WCL EA9-T10CL EA9-T12CL EA9-T15CL-R / EA9-T15CL
Power Consumption 16.0 W, 1.30A @ 12 VDC, 0.66A @ 24 VDC 18.0 W, 1.50A @ 12 VDC, 0.75A @ 24 VDC 17.0 W, 1.42A @ 12 VDC, 0.71A @ 24 VDC 18.0 W, 1.50A @ 12 VDC, 0.75A @ 24 VDC 21.0 W, 1.75A @ 12 VDC, 0.88A @ 24 VDC 29.0 W, 2.40A @ 12 VDC, 1.20A @ 24 VDC
Internal Fuse (non-replaceable) 4.0A 6.3A
Altitude Up to 2000m (6562 ft)
Operating Temperature 0 to 50 °C (32 to 122 °F)
Storage Temperature -20 to +60 °C (-4 to +140 °F)
Humidity 5-95% RH (non-condensing)
Environment For use in Pollution Degree 2 environment, no corrosive gases permitted
Withstand Voltage 1000 VAC, 1 min. (FG to Power supply)
Insulation Resistance > 10M ohm @ 500V DC (FG to Power supply)
Enclosure NEMA 250 type 4/4X indoor use only
UL50 type 4X indoor use only
IP65 indoor use only
(When mounted correctly)
NEMA 250 type 4/4X indoor use only
UL50 type 4X indoor use only
IP65 indoor use only (not tested by UL)
(When mounted correctly)
NEMA 250 type 4/4X indoor use only
UL50 type 4X indoor use only
IP65 indoor use only
(When mounted correctly)

What are the panel cutout dimensions for mounting the AUTOMATIONDIRECT C-MORE EA9-T7CL?

The cutout dimensions are provided in inches [mm]:

Model Number A B D E J
EA9-T6CL-R / EA9-T6CL 8.08 [205.2] 6.13 [155.8] 7.46 [189.5] 5.51 [140.0] 0.31 [7.9]
EA9-T8CL 9.87 [250.7] 7.69 [195.4] 9.25 [235.0] 7.07 [179.6] 0.31 [7.9]
EA9-T10WCL 11.18 [284.0] 7.69 [195.4] 9.25 [235.0] 7.07 [179.6] 0.96 [24.5]
EA9-T10CL 12.52 [318.0] 9.53 [242.1] 11.90 [302.3] 8.91 [226.3] 0.31 [7.9]
EA9-T12CL 13.37 [339.6] 11.02 [280.0] 12.57 [319.3] 10.22 [259.6] 0.40 [10.2]
EA9-T15CL-R / EA9-T15CL 15.75 [400.0] 12.09 [307.2] 14.93 [379.2] 11.27 [286.3] 0.41 [10.4]

Note: Cutout dimensions for the EA9-T7CL and EA9-T7CL-R models are not specified in the provided table.


What are the installation clearance and mounting angle requirements for the AUTOMATIONDIRECT C-MORE EA9-T7CL?

Clearance: The mounting clearances when installing the touch panel in an enclosure or cabinet shall be a minimum of 4 inches from the top, bottom and sides and 1.72 inches from the rear.

Derating: If EA9-T15CL is mounted off the vertical plane facing upward, the temperature shall be derated. Other panels, such as the EA9-T7CL, may be mounted at any angle without derating consideration.


What is the recommended screw torque for the mounting clips on the AUTOMATIONDIRECT C-MORE EA9-T7CL?

Touch Panel Size Enclosure Thickness Range Mounting Clip Screw Torque Material
6″, 7″, 8″, 10″ and 12″ 0.039 – 0.20 inch [1-5 mm] 63 – 77 oz-in [0.45 – 0.55 Nm] Metal
10″W, 15″ 92 – 106 oz-in [0.65 – 0.75 Nm]

How should I clean the display screen and operate the touchscreen of the AUTOMATIONDIRECT C-MORE EA9-T7CL?

Cleaning: The display screen should be cleaned periodically by wiping it with a lint free damp cloth using a mild soap solution. Use a dry or slightly dampened cloth to wipe any dirt from the labels on the back of the panel. Dry all surfaces with a lint free cloth. Do not clean with ammonia based products which are solvents and will damage the face of the panel and the labels.

Touchscreen Operation: The touchscreen is designed to respond to a single touch. If it is touched at multiple points at the same time, an unexpected object may be activated.


What are the UL satisfaction ratings and other connection requirements for the AUTOMATIONDIRECT C-MORE EA9-T7CL?

Model Number Input Ratings
EA9-T6CL-R / EA9-T6CL 12 – 24 VDC, Class 2, SELV or LEC, Maximum 16.0W
EA9-T7CL-R / EA9-T7CL 12 – 24 VDC, Class 2, SELV or LEC, Maximum 18.0W
EA9-T8CL 12 – 24 VDC, Class 2, SELV or LEC, Maximum 17.0W
EA9-T10WCL 12 – 24 VDC, Class 2, SELV or LEC, Maximum 18.0W
EA9-T10CL 12 – 24 VDC, Class 2, SELV or LEC, Maximum 21.0W
EA9-T12CL / EA9-T15CL-R / EA9-T15CL 12 – 24 VDC, Class 2, SELV or LEC, Maximum 29.0W

Additional Requirements:

• Terminal connecting wire size: 12-24 AWG

• Connecting torque: 71 – 85 oz-in (0.5-0.6 Nm)

• Surrounding Air Temperature rating: 0 to 50°C (32 to 122°F)

• For use in Pollution Degree 2 environment

• All interface ports are intended to be directly connected to an isolated secondary circuit

• For use on a flat surface of a type 4X Indoor Use Only enclosure


Are there special installation requirements for using the AUTOMATIONDIRECT C-MORE EA9-T7CL in hazardous locations?

For models EA9-T6CL-R and EA9-T6CL, the following requirements apply for Class 1, Div 2, Groups A, B, C hazardous locations:

• SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.

• WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

• WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.

• DEVICES SHALL BE INSTALLED INTO AN ENCLOSURE THAT UTILIZES A TOOL REMOVABLE DOOR/COVER.