FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF DOCUMENT.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF USER GUIDE.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF USER MANUAL.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF OWNER GUIDE.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF OWNER MANUAL.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF REFERENCE GUIDE.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF REFERENCE MANUAL.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH SOLARX POWER BMS PARALLEL BOX-II (01) PDF OPERATING INSTRUCTIONS.
CLICK HERE TO DOWNLOAD SOLARX POWER BMS PARALLEL BOX-II (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What are the meanings of the safety symbols used in the SOLARX POWER BMS PARALLEL BOX-II user manual?
The following safety symbols are used in the manual to indicate hazardous situations:
DANGER!: Indicates a hazardous situation which, if not avoided, will result in serious injury or death.
WARNING!: Indicates a hazardous situation which, if not avoided, could result in serious injury or death.
CAUTION!: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTE!: Provides tips that are valuable for the optimal operation of your product.
What are the important safety instructions for the SOLARX POWER BMS PARALLEL BOX-II?
Please adhere to the following safety instructions when handling the SOLARX POWER BMS PARALLEL BOX-II:
DANGER!
Danger to life due to high voltages in the inverter!
• All work must be carried out by a qualified electrician.
• The appliance is not to be used by children or persons with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
• Children should be supervised to ensure that they do not play with the appliance.
CAUTION!
Danger of burn injuries due to hot enclosure parts!
• During operation, the upper lid of the enclosure and the enclosure body may become hot.
• Only touch the lower enclosure lid during operation.
CAUTION!
Possible damage to health as a result of the effects of radiation!
• Do not stay closer than 0.66 ft/20 cm to the inverter for any length of time.
WARNING!
• Do not operate the inverter when the device is running.
• Risk of electric shock!
• Authorized service personnel must disconnect the cables before attempting any maintenance or cleaning or working on any circuits connected to the box.
What do the symbols on the warning label of the SOLARX POWER BMS PARALLEL BOX-II mean?
The symbols on the warning label provide the following information:
• The system must be disposed of at a proper facility for environmentally-safe recycling.
• The system should not be disposed of together with household waste.
• Wear protective glasses.
• Observe enclosed documentation.
• Keep the battery system away from open flames or ignition sources.
• Keep the battery system away from children.
• Danger of high voltages.
• Danger. Risk of electric shock.
What are the terminals on the SOLARX POWER BMS PARALLEL BOX-II and what are their functions?
| Object | Mark | Description |
|---|---|---|
| I | RS485-1 | Battery module communication of group 1 |
| II | B1+ | Connector B1+ of Box to + of battery module of group 1 |
| III | B1- | Connector B1- of Box to – of battery module of group 1 |
| IV | RS485-2 | Battery module communication of group 2 |
| V | B2+ | Connector B2+ of Box to + of battery module of group 2 |
| VI | B2- | Connector B2- of Box to – of battery module of group 2 |
| VII | BAT+ | Connector BAT+ of Box to BAT+ of inverter |
| VIII | BAT- | Connector BAT- of Box to BAT- of inverter |
| IX | BMS | Connector BMS of Box to BMS of inverter |
| X | / | Air Valve |
| XI | (Ground Symbol) | GND |
| XII | ON/OFF | Circuit Breaker |
| XIII | POWER | Power Button |
| XIV | DIP | DIP Switch |
Note: The serial number of B1 and B2 slave batteries must be equal.
What are the features of the SOLARX POWER BMS PARALLEL BOX-II?
The SOLARX POWER BMS PARALLEL BOX-II has the following features:
• Interacts with the inverter.
• Judges and controls the running state of the battery system based on interactive information.
• Performs BMS related control processing.
• Realizes corresponding fault identification and processing.
• Ensures the safe operation of the battery system.
• Secondary Protection by Hardware.
• IP55 Protection Level.
• Safety & Reliability.
• Small Occupied Area.
• Wall Mounting capability.
What are the technical specifications of the SOLARX POWER BMS PARALLEL BOX-II?
| Model | BMS Parallel Box-II |
| Dimension (W/H/D)(in/mm) | 14.48*13.15*5.67/368*334*144 |
| Dimension of Packing (W/H/D)(in/mm) | 17.32*15.63*10.12/440*397*257 |
| Net Weight (lbs/kg) | 11.46/5.2 |
| Input/Output voltage Range (V) | 70-550 |
| Maximum Charge/Discharge Current (A) | 35 |
| Environment | Outdoor |
| Standard Power (kW) | 11.6 |
| Maximum Power (kW) | 14 |
| Altitude (ft/m) | ≤ 6561.68/2000 |
| Pollution Degree | PD 3 |
| Noise Level | <30dB |
| Overvoltage Category (OVC) | II |
| Protective Class | I |
| Operating Temperature | 32°F~131°F/0°C~55°C |
| Ingress Protection | IP55 |
What are the installation prerequisites for the SOLARX POWER BMS PARALLEL BOX-II?
Ensure the installation location meets the following conditions:
• The building is designed to withstand earthquakes.
• The location is far from the sea (over 0.62 miles/997.79 meters) to avoid salt water and humidity.
• The floor is flat and level.
• There are no flammable or explosive materials within a minimum of 3 ft/0.91 m.
• The ambiance is shady and cool, away from heat and direct sunlight.
• The temperature and humidity remain at a constant level.
• There is minimal dust and dirt in the area.
• There are no corrosive gases present, including ammonia and acid vapor.
Note: When installing the battery for the first time, the manufacturing date between battery modules should not exceed 3 months.
What tools are required to install the SOLARX POWER BMS PARALLEL BOX-II?
The following tools are required for installation:
• Torque Screw Driver
• Phillips-Screw Driver
• Hexagon Wrench
• Phillips-Head Screw Driver
• Flat-Head Screw Driver
• Torque Wrench
• Tape Measure
• Drill
• Pencil or Marker
It is also mandatory for personnel to wear appropriate safety gear, including Insulated Gloves, Safety Goggles, and Safety Shoes.
How do I wall-mount the SOLARX POWER BMS PARALLEL BOX-II?
Follow these steps to mount the SOLARX POWER BMS PARALLEL BOX-II on a wall:
Step 1: Fix the wall bracket on the wall
• Remove the bracket from the back of the box. Measure it and mark the position of the two holes on the wall.
• Drill holes at the marked positions to a depth of at least 3.15 inches/80.00 mm using a drill (ø 0.39 inch/10 mm).
• Insert the expansion screw sleeves into the holes, and then screw the wall bracket to the wall using a wrench (Torque: 1.2-1.5 N·m).
Step 2: Match the box with the wall bracket
• Hang the box over the wall bracket, move the box close to it and ensure it is securely matched on the wall bracket.
CAUTION! Ensure that the system is always exposed to ambient air as it is cooled by natural convection. If the system is entirely or partially covered or shielded, it may cause the system to stop operating.
How should I connect the cables from the SOLARX POWER BMS PARALLEL BOX-II to the inverter?
To connect the power cables from the box to the inverter (BAT+ to BAT+; BAT- to BAT-), follow these steps:
Step 1. Strip the cable to 0.59 in/15 mm.
Step 2. Insert the stripped cable up to the stop into the connector. The negative cable goes into the DC plug(-) and the positive cable goes into the DC socket(+). Hold the housing on the screw connection.
Step 3. Press down the spring clamp until it clicks audibly into place. You should be able to see the fine wire strands in the chamber.
Step 4. Tighten the screw connection with a tightening torque of 2.0±0.2 N·m.
To connect the BMS communication cable (Box to Inverter: BMS to BMS):
The BMS communication cable is required for the BMS to communicate with the inverter for proper operation. The wire order is as follows:
| Sequence | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|---|---|---|---|---|---|---|---|---|
| BMS | / | / | / | CAN_H | CAN_L | / | A1 | B1 |
The wire colors correspond to the sequence as follows: 1) Orange stripes on white, 2) Orange, 3) Green stripes on white, 4) Blue, 5) Blue stripes on white, 6) Green, 7) Brown stripes on white, 8) Brown.
How are battery modules connected to the SOLARX POWER BMS PARALLEL BOX-II?
To connect the SOLARX POWER BMS PARALLEL BOX-II to 2, 4, 6, or 8 battery packs, make the following connections from the box to the first battery module in each group:
• B1+/B2+ on the box connects to “+” on the battery module.
• B1-/B2- on the box connects to “XPLUG” on the battery module.
• RS485-1/RS485-2 on the box connects to “RS485 I” on the battery module.
Subsequent batteries in the group are connected in series. To form a complete circuit for the group, connect “-” and “YPLUG” with a series-connected cable on the right side of the last battery module in the group.
Note: If any ports are not used after wiring is completed, please remember to install the waterproof caps on those ports.
How do I configure the DIP switch on the SOLARX POWER BMS PARALLEL BOX-II?
The DIP switch configures the communication between the battery module(s) and the inverter. A small flat-head screwdriver is needed for adjustment.
Configuration activated by inverter:
• 0: Matching a single battery group (group 1 or group 2).
• 1: Matching both battery groups (group 1 and group 2).
Caution: If the DIP switch is set to 1, the number of batteries in both groups must be the same.
Black-start Configuration (for off-grid applications with no other power supply):
• 4: Matching the Black Start mode for a single group (group 1 or group 2).
• 5: Matching the Black Start mode for both groups (group 1 and group 2).
Note: When powering on the box, it will start a self-test. If the buzzer beeps, it indicates a DIP configuration fault or communication failure. Check if the number of battery modules corresponds to the DIP configuration and if the RS485 communication cables are correctly connected. After checking, press the POWER button to power on, and press it again 10 seconds later.
What is the procedure for commissioning the SOLARX POWER BMS PARALLEL BOX-II?
After all battery modules are installed, follow these steps to start the SOLARX POWER BMS PARALLEL BOX-II:
1. Verify that the model number of each battery module is the same.
2. Configure the DIP switch to the corresponding number according to the number of battery module(s) installed.
3. Remove the cover board of the box.
4. Move the circuit breaker switch to the “ON” position.
5. Press the POWER button to start the box.
6. Reinstall the cover board on the box.
7. Turn on the inverter AC switch.
8. After starting the box, confirm that the waterproof cap is closed again.
NOTE: Frequently pressing the POWER button may cause a system error. Allow at least 10 seconds after pressing the POWER button before making another attempt.
How do I interpret the status indicators on the SOLARX POWER BMS PARALLEL BOX-II?
The LED indicators on the front panel show the operating status. The capacity indicators (S2) show the state of charge (SOC), while the status lights (S1) indicate the BMS status.
Status of BMS (S1):
| No. | Status of BMS | Mode |
|---|---|---|
| 1 | Green LED flashes on 1 sec and off for 4 sec | Inverter sends Idle command |
| 2 | In case two groups are in warning state, the status light flashes yellow light for 1 sec and turns off for 4 sec. | Warning |
| 3 | (1) In case two groups are in fault, the status light 1 & 2 flash red light for 0.5 sec and turn off for 0.5 sec, and at the same time, the status light comes on solid red light for 10 min, and then flashes red light for 1 sec and turns off for 4 sec until the fault is solved. (2) In case either of groups is in fault, the status light 1 (or 2) flashes red light for 0.5 sec and turns off for 0.5 sec, the status light 2 (or 1) does not light, and the status light comes on green light. |
Protection |
| 4 | If either of two groups is normal, status light of such group will not light. | Normal |
| 5 | Green LED flashes once every 0.3 sec | Upgrade for BMS |
| 6 | Light off | Power off |
Capacity Indicators (SOC):
• When the battery module is neither charging nor discharging, the indicator lights are off.
• When the battery module is charging, a part of the blue LED flashes once every 5 seconds, and a part of the blue LED is on. For example, at SOC 60% while charging:
– The last two blue LED indicators are on.
– The last three blue LED indicators flash once every 5 seconds.
• When the battery module is discharging, the blue LED indicators flash once every 5 seconds. For example, at SOC 60% while discharging:
– The last three blue LED indicators flash once every 5 seconds.
What is the correct procedure for shutting down the SOLARX POWER BMS PARALLEL BOX-II?
To shut down the system, follow these steps:
1. Turn off the breaker between the inverter and the box.
2. Power off the BMS.
3. Turn off the system by moving the circuit breaker switch on the box to the OFF position.
4. Ensure that every indicator on the box is off.
5. Disconnect the cables.
How can I troubleshoot the SOLARX POWER BMS PARALLEL BOX-II based on warning messages?
Use the following table to troubleshoot warning messages reported by the SOLARX POWER BMS PARALLEL BOX-II.
| Warning Messages | Description | Troubleshooting |
|---|---|---|
| BMS_Internal_Err | 1) DIP switch on the wrong position 2) The communication between battery modules is interrupted. |
1) Move the DIP switch to the correct position 2) Check if the communication cable between the battery modules is correctly and properly connected. |
| BMS_OverVoltage | Battery over voltage | Contact your distributor or SolaX directly for servicing. |
| BMS_LowerVoltage | Battery under voltage | Contact your distributor or SolaX directly for servicing. |
| BMS_ChargeOCP | Battery charge over current protection | Contact your distributor or SolaX directly for servicing. |
| BMS_DishargeOCP | Battery discharge over current protection | Contact your distributor or SolaX directly for servicing. |
| BMS_TemHigh | Battery over temperature | Wait until the temperature of the cells returns to the normal state. |
| BMS_TemLow | Battery under temperature | Wait until the temperature of the cells returns to the normal state. |
| BMS_Celllmblance | The capacities of cells are different | Contact your distributor or SolaX directly for servicing. |
| BMS_Hardware_Protect | Battery hardware under protection | Contact your distributor or SolaX directly for servicing. |
| BMS_Insulation_Fault | Battery insulation fault | Contact your distributor or SolaX directly for servicing. |
| BMS_VoltSensor_Fault | Battery voltage sensor fault | Contact your distributor or SolaX directly for servicing. |
| BMS_TempSensor_Fault | Battery temperature sensor fault | Contact your distributor or SolaX directly for servicing. |
| BMS_CurrSensor_Fault | Battery current sensor fault | Contact your distributor or SolaX directly for servicing. |
| BMS_Relay_Fault | Battery relay fault | 1) Ensure the power cable is correctly and properly connected to the power connector (XPLUG) of the BMS 2) If the first step still does not work, contact your distributor or SolaX directly. |
| BMS_Type_Unmatch | The type of BMS is unmatched | Contact your distributor or SolaX directly for servicing. |
| BMS_Ver_Unmatch | The version of BMS is unmatched | Contact your distributor or SolaX directly for servicing. |
What are the maintenance guidelines for the SOLARX POWER BMS PARALLEL BOX-II?
Only a qualified person may perform maintenance. Follow these guidelines:
Storage and Recharging:
• If ambient temperature for storage is -4°F to 113°F (-20°C to 45°C), recharge batteries at least once every 3 months.
• If ambient temperature for storage is -4°F to 68°F (-20°C to 20°C), recharge batteries at least once every 6 months.
• If batteries have not been used for more than 9 months, they must be charged to at least 50% SOC each time.
Battery Installation and Replacement:
• For the first installation, the interval among manufacture dates of battery modules shall not exceed 3 months.
• If a battery is replaced, the SOC of the new battery must be consistent with the others, with a maximum difference between -5% and 5%.
• To increase battery system capacity, ensure the existing system’s SOC is about 40%. The new battery’s manufacture date shall not exceed 6 months; if it does, charge the new battery to around 40% before adding.
Periodic Maintenance Checklist:
1. Periodically check if the cooling fins on the rear are covered by dirt and clean them if necessary.
2. Every 6 months, check that the indicators and keys on the box are in a normal state and that the system display is normal.
3. Every 6 months, check that the input and output wires are not damaged or aged.
4. Every 12 months, check that the ground terminal and cable are securely connected and all terminals and ports are properly sealed.
5. Every 6 months, clean the box panels and check their security.