What items should be included in the X3-EPS BOX package?
Before installation, make sure that nothing inside the package is damaged. The following items should be inside the package:
| Self-tapping screws x4 | Cushion blocks x4 |
| Washers x4 | Flat head screws x4 |
| Expansion tubes x4 | Silicone sleeves x15 |
| 6 mm² tube-insulated terminals x15 | 16 mm² tube-insulated terminals x15 |
What tools are needed for installation?
Before you start, get the following tools ready:
- Diagonal plier
- Philips screwdriver
- Φ6 driller
- Crimping plier
- Marker pen
- Slotted screwdriver
- Manual wrench
- Rubber hammer
How do I mount the X3-EPS BOX?
Step 1: Make sure the installation site does not expose the device to direct sunlight. Then install the four cushion blocks on the X3-EPS BOX with flat head screws.
Step 2: Use the X3-EPS BOX with cushion blocks as a template to mark the four holes’ position on the wall with a marker pen.
Step 3: Drill holes with a Φ6 driller carefully. Make sure the holes are deep enough for installing (at least 50mm). Put the expansion tubes into the wall, then insert the self-tapping screws through the cushion blocks into the expansion tubes. Screw and tighten the screws.
Step 4: Install the expansion screws with a screwdriver to fix the X3-EPS BOX to the wall.
How do I prepare the wires for connection?
1. Prepare the necessary wires. You will need:
– L wire (6 AWG) x9 pcs
– N wire (6 AWG) x3 pcs
– GND wire for EU x1 pcs
– N wire for AU x1 pcs
2. Use a diagonal plier to strip 15mm of insulation from the side of each wire.
3. Insert the wire into the cable gland, then insert the end of the wire into a cold pressed terminal and tighten it.
Note: If AWG-10 wires are used, please pass the wires through the silicone sleeves to avoid leakage at the insertions.
How do I connect the Grid wires?
1. Use the manual wrench to screw off the cap on the cable nut for the MAIN GRID PORT.
2. Insert Grid-L wires and Grid-N wires into the ports (L1, L2, L3, L4) of contactor A.
3. Pass the wires through the cable nut and tighten them with a screwdriver.
Note: Please prevent other wires from getting loose during operation.
How do I connect the EPS wires?
1. Screw off the cap on the cable nut for the INVERTER EPS PORT.
2. Insert EPS-L wires and EPS-N wires into the ports (L1, L2, L3, L4) of contactor B.
3. Pass the wires through the cable nut and tighten them with a screwdriver.
How do I connect the Load wires?
1. Screw off the cap on the cable nut for the LOAD PORT.
2. Insert Load-L wires and Load-N wires into the ports (T1, T2, T3, T4) of contactor C.
3. Pass the wires through the cable nut and tighten them with a screwdriver.
How do I connect the Earth wire?
For EU users: please insert the GND wire into the port of contactor B (port L4) through the cable nut and tighten it with a screwdriver.
For AU users: please insert the N wire into the ports of contactor A (port L4) and contactor B (port L4).
What is the final check after wiring?
Please make sure all wires are tightened. Check the wire connection in the X3-EPS BOX.
What are the technical parameters of the X3-EPS BOX?
| Grid | Load | ||
|---|---|---|---|
| Max. AC input current (A) | 3×63 | Rated output current(A), on grid mode | 3×63* |
| Rated AC voltage (V) | 3/N/PE~400/230 | Rated output current(A), EPS mode | 3×63* |
| Rated AC frequency (Hz) | 50 / 60 | Rated Grid Voltage(V) | 3/N/PE~400/230 |
| Rated Grid Frequency(Hz) | 50/60 | ||
| EPS | General Data | ||
| Max. EPS input current (A) | 3×63 | Operating Temperature range (°C) | -20~+60 |
| Rated EPS voltage (V) | 3/N/PE~400/230 | Dimension (mm) | 300 x 220 x 170 |
| Rated EPS frequency (Hz) | 50 / 60 | Weight (kg) | 4.85 |
* The output current will be reduced when the operating temperature exceeds 40°C. At 50°C, the output current drops to 95%. At 60°C, it drops to 80%.
CLICK HERE TO DOWNLOAD SOLAX POWER X3-EPS BOX (01) PDF MANUAL