Free English TCL TCD140D1HWH-DV (02) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD TCL TCD140D1HWH-DV (02) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
Can the TCL TCD140D1HWH-DV air conditioner be installed underfloor?
No, the TCD Series, including the TCL TCD140D1HWH-DV, cannot be installed underfloor. It is designed for ceiling concealed duct type installation.
What are the key safety warnings for installing the TCL TCD140D1HWH-DV?
Failure to observe the following warnings may result in death, injury, or damage to the equipment:
• Installation work must be carried out by a dealer or qualified personnel. Do not attempt to install the machine yourself.
• Perform installation according to this installation manual. Improper installation can cause water leakage, electrical shock, or fire.
• Use only the specified accessories and parts. Using non-specified parts can cause water leakage, electric shock, fire, or unit failure.
• Install the conditioner on a structure strong enough to withstand its weight.
• Carry out installation work considering strong winds, typhoons, or earthquakes.
• Ensure a separate power supply circuit is provided, and all electrical work is done by qualified personnel according to local laws and regulations.
• Secure all wiring, use specified wires, and ensure no external forces act on terminal connections.
• Position wires so that the switch box cover can be securely fastened.
• If refrigerant gas leaks during installation, ventilate the area immediately.
• After installation, check that refrigerant gas does not leak. Fire may occur if leaked refrigerant contacts an ignition source.
• Before accessing terminals and electrical parts, all supply circuits must be disconnected.
• Do not install the indoor unit or remote controller where they may be exposed to rain or moisture.
• Grounding is necessary. Do not connect the earth wire to gas/water pipes, a lightning conductor, or a telephone ground wire.
• An earth leakage breaker must be installed.
What are the main safety cautions for the installation of the TCL TCD140D1HWH-DV?
Observe the following cautions to prevent injury or damage to the equipment:
• Do not install the indoor unit or wired controller where flammable gases may leak, where carbon fiber or ignitable dust is present, or where volatile flammables like thinner or gasoline are handled.
• Do not install where the area is filled with steam or the ground is always wet, as this can damage electrical component insulation.
• Only use refrigerant piping approved for use with R32 refrigerant. Unapproved piping may result in rupture.
• When making piping connections, do not let air or substances other than the specified refrigerant enter the refrigeration cycle.
• The appliance must be installed in accordance with national wiring regulations.
• This appliance can be used by children aged 8 years and above and persons with reduced capabilities only if they have been given supervision or instruction. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
What are the specific instructions for servicing the TCL TCD140D1HWH-DV, which uses R32 refrigerant?
1. The appliance must be installed, operated, and stored in a room with a floor area larger than 4m2.
2. The installation of pipe-work shall be kept to a minimum.
3. Pipe-work shall be protected from physical damage and not installed in an unventilated space if the space is smaller than 4m2.
4. Comply with national gas regulations.
5. Mechanical connections must be accessible for maintenance.
6. Ensure ventilation openings are clear of obstruction.
7. Servicing shall be performed only as recommended by the manufacturer.
8. The appliance must be stored in a well-ventilated area where the room size corresponds to the room area specified for operation.
9. The appliance must be stored in a room without continuously operating open flames (e.g., an operating gas appliance) or ignition sources (e.g., an operating electric heater).
10. Store the appliance to prevent mechanical damage.
11. Do not use means to accelerate the defrosting process or to clean, other than those recommended.
12. Do not pierce or burn the appliance.
13. Be aware that refrigerants may not contain an odor.
What checks are required before beginning work on the TCL TCD140D1HWH-DV system with R32 refrigerant?
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. The following precautions must be followed:
Work Procedure: Work shall be undertaken under a controlled procedure to minimize the risk of a flammable gas or vapor being present while the work is being performed.
General Work Area: All maintenance staff and others working in the local area shall be instructed on the nature of the work. Avoid working in confined spaces. The area around the workspace shall be sectioned off and made safe by controlling flammable material.
Checking for Refrigerant: Check the area with an appropriate refrigerant detector before and during work. Ensure the leak detection equipment is suitable for flammable refrigerants (non-sparking, adequately sealed, or intrinsically safe).
Fire Extinguisher: Have a dry powder or CO2 fire extinguisher available. If any hot work is to be conducted, appropriate fire extinguishing equipment must be on hand.
No Ignition Sources: No person carrying out work on the refrigeration system shall use any ignition sources in a manner that may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site.
Ventilated Area: Ensure the area is in the open or adequately ventilated before breaking into the system. Ventilation should continue during the work period.
How do I determine the minimum room area for installing the TCL TCD140D1HWH-DV?
The construction area for installation, operation, and storage of the TCL TCD140D1HWH-DV must be larger than the minimum construction area. This is determined by the total refrigerant charging quantity for the entire system (ex-factory quantity + additional charging quantity). Refer to the following table for the minimum required area based on the total R32 refrigerant weight.
For Ceiling Type Units (like the TCL TCD140D1HWH-DV):
| R32 refrigerant Weight (kg) | Area (m²) |
|---|---|
| <1.224 | — |
| 1.224 | 0.956 |
| 1.4 | 1.25 |
| 1.6 | 1.63 |
| 1.8 | 2.07 |
| 2.0 | 2.55 |
| 2.2 | 3.09 |
| 2.4 | 3.68 |
| 2.6 | 4.31 |
| 2.8 | 5.00 |
| 3.0 | 5.74 |
| 3.2 | 6.54 |
| 3.4 | 7.38 |
| 3.6 | 8.27 |
| 3.8 | 9.22 |
| 4.0 | 10.2 |
| 4.2 | 11.3 |
| 4.4 | 12.4 |
| 4.6 | 13.5 |
| 4.8 | 14.7 |
| 5.0 | 16.0 |
| 5.2 | 17.3 |
| 5.4 | 18.6 |
| 5.6 | 20.0 |
| 5.8 | 21.5 |
| 6.0 | 23.0 |
| 6.2 | 24.5 |
| 6.4 | 26.1 |
| 6.6 | 27.8 |
| 6.8 | 29.5 |
| 7.0 | 31.3 |
| 7.2 | 33.1 |
| 7.4 | 34.9 |
| 7.6 | 36.9 |
| 7.8 | 38.8 |
| 8.0 | 40.8 |
What are the ideal locations for installing the indoor and outdoor units of the TCL TCD140D1HWH-DV?
INDOOR UNIT Location:
1. A place with sufficient space for repair in a hung ceiling that can bear the weight of the machine.
2. A place where the air inlet and outlet are not hindered and are without influence from outdoor air.
3. A place without heat sources like smoke, fire, or toxic pollution.
4. A place where airflow can be transmitted everywhere in the room.
5. A place convenient for installation.
OUTDOOR UNIT Location:
1. A place with sufficient space for installation and repair.
2. A place where the air inlet and outlet are not hindered, without strong air flowing.
3. A dry and ventilated place.
4. A place where the overhanging structure is level and can bear the weight of the outdoor unit, without much noise.
5. A place where neighbors are not annoyed by noise and exhausted air.
6. A place without leakage of flammable gas.
7. A place convenient for installation.
Caution: Avoid locations with flammable gas leakage, salty air (near the coast), caustic gas, locations that cannot bear the unit’s weight, kitchens full of oil gas, strong electromagnetic waves, or places with acid/alkaline liquid evaporating.
What accessories are included with the TCL TCD140D1HWH-DV?
Check that the following accessories are included with your unit. Note that accessories may vary slightly by specific model within the series.
| Model | Name | Quantity |
|---|---|---|
| TCD100 / TCD125 / TCD140 / TCD160 | Hose Clamp | 1 |
| Drain Hose | 1 | |
| Installation Manual | 1 | |
| Operation Manual | 1 | |
| Hanger Bracket Accessories Pack | 1 (4 screws) | |
| Pipe Insulation | 2 | |
| Wired Controller & connection cable | 1 each |
What checks should be performed after the installation of the TCL TCD140D1HWH-DV is complete?
After completing the installation, perform the following checks to ensure proper and safe operation.
| Items to be checked | If not properly done, what is likely to occur |
|---|---|
| Is the gas leak test finished? | It may result in insufficient cooling or heating. |
| Does the unit require external insulation? | Condensate water may drip. |
| Does drainage flow smoothly? | Condensate water may drip. |
| Does the power supply voltage correspond to that shown on the name plate? | The unit may malfunction or the components burn out. |
| Is the wiring and piping correct? | The unit may malfunction or the components burn out. |
| Is the unit safely grounded? | Dangerous during electric leakage. |
| Is the wiring size according to specification? | The unit may malfunction or the components burn out. |
| Is something blocking the air outlet or inlet of either the indoor or outdoor units? | It may result in insufficient cooling or heating. |
| Are refrigerant piping length and additional refrigerant charge noted down? | The refrigerant charge in the system is not clear. |
| Is the indoor unit positioned so that it is not in contact with parts of the ceiling? | Vibration and noise can be transmitted into building. |
| Is the airflow within specification? | Poor performance or malfunction. |
| Is an air filter installed in the return air? | Blocked heat exchanger causing malfunction or compressor failure. |
| Is an external drain tray installed? | Condensate water may drip. |
| Check and confirm that there are no R32 leaks after the installation. | (Potential for fire or performance issues) |
Also, at completion, you should show the customer how to operate the system, explain safety considerations, and hand over the operation manual.
How do I perform refrigerant piping work for the TCL TCD140D1HWH-DV?
Refrigerant piping must be done by a qualified person. Where additional refrigerant is required, use only R32.
1. Fully insulate the liquid and gas piping separately to prevent water leaks. In heating mode, the gas piping can reach 120°C, so use insulation with a suitable temperature rating.
2. Use a spanner and a torque wrench together when connecting or disconnecting pipes.
3. Use a flaring block suitable for R32 tube.
4. When connecting the flare nut, coat only the flare’s inner surface with ether or ester oil. Initially tighten by hand for 3 to 4 turns before tightening firmly with the torque wrench.
5. Use the flare nuts included with the indoor unit.
6. Refer to the table for proper tightening torque and flare dimensions. Over-tightening can cause leaks.
| Pipe size | Tightening torque | Flare dimensions A (mm) |
|---|---|---|
| 6.4 (1/4″) | 14.2-17.2 N·m (144-175 kgf·cm) | 8.6-9.0 |
| 9.5 (3/8″) | 32.7 -39.9 N·m (333-407 kgf·cm) | 12.6-13.0 |
| 12.7 (1/2″) | 49.5-60.3 N·m (504-614 kgf·cm) | 15.8-16.2 |
| 15.9 (5/8″) | 61.8-75.4 N·m (630-770 kgf-cm) | 19.3-19.7 |
In an emergency without a torque wrench: Tighten with a spanner until the torque suddenly increases. From that point, further tighten the nut using the angle shown in the table below. After the work is finished, check for gas leaks.
| Pipe size | Further tightening angle | Recommended arm length of tool |
|---|---|---|
| 6.4 (1/4″) | 60 to 90 degrees | Approx. 150mm |
| 9.5 (3/8″) | 60 to 90 degrees | Approx. 200mm |
| 12.7 (1/2″) | 30 to 60 degrees | Approx. 250mm |
| 15.9 (5/8″) | 30 to 60 degrees | Approx. 300mm |
How should I set up the drain piping for the TCL TCD140D1HWH-DV?
Improperly installed drain piping may result in water leaks and damage to property. After piping work, check that drainage flows smoothly by gradually pouring approximately 1 litre of water into the drain tray.
For units with water pumps (Standard for this series):
• Use the pump for drainage via the “Pump Drain Outlet”. The “Tray Drain Outlet” needs to be blocked with the “Drain Plug”.
• The drain pipe outlet can be raised up to 600mm above the ceiling.
• Keep the horizontal pipe length short (100mm or less) before the vertical rise to prevent backflow.
General Drain Piping Installation:
• Keep the drain pipe short and sloping downward at a gradient of at least 1/100 to prevent air pockets.
• Secure the pipe every 1 to 1.5m to prevent sagging.
• Use the provided drain hose and clamp, and tighten the clamp firmly.
• Insulate the drain hose and any metal clamps inside the building to prevent condensation.
• As a safety measure, use a separate safety drain tray (field supplied).
• Do not connect the drain piping directly to sewage pipes to prevent odors and corrosion.
What are the electrical specifications for the TCL TCD140D1HWH-DV?
All wiring must be performed by an authorized electrician. Please refer to the specified parameters for the indoor and outdoor units.
Indoor Unit Electrical Parameters:
| Indoor Unit Model | Power Supply (V/Ph/Hz) | Fuse Capacity (A) | Circuit Breaker Capacity (A) | Min. Sectional Area of Power Cord (mm2) |
|---|---|---|---|---|
| TCD140/160 | 220-240V 1~50Hz | 8 | 10 | 1.5 |
Outdoor Unit Electrical Parameters:
| Outdoor Unit Model | Power Supply (V/Ph/Hz) | Fuse Capacity (A) | Circuit Breaker Capacity (A) | Min. Sectional Area of Power Cord (mm2) |
|---|---|---|---|---|
| TCD140/160 | 220-240V 1~50Hz | 30 | 40 | 4 |
How do I separate the indoor unit of the TCL TCD140D1HWH-DV for installation?
WARNING: Power should be disconnected and tagged off before performing this procedure if the unit is already installed. Separate the unit only when necessary and on a flat surface.
To Separate the Indoor Unit:
1. Carefully remove the Airbox compartment by removing the (4) M6 bolts.
2. Carefully remove the (1) thermistor cable (R1T) from its clamp.
3. Wrap the thermistor cable and place it neatly into the rubber bush next to the fan deck.
4. Carefully disconnect the fan motor wiring from the base panel located underneath the reactor box.
5. Remove the (5) tapping screws located above the fan deck flange.
6. Remove the (4) M6 bolts securing the fan deck to the base panel of the heat exchanger compartment.
7. Carefully separate the fan deck assembly from the base panel, taking care not to damage the fan motor wiring.
8. Carefully detach the fan deck.
To Reassemble the Indoor Unit:
9. Carefully place the fan deck back in position on the base panel.
10. Secure the fan deck onto the heat exchanger compartment with the (4) M6 bolts and (5) tapping screws for the top flange.
11. Place the thermistor cable (R1T) back to the side of the fan deck and secure it with the thermistor clamp. Ensure the tip of the thermistor is positioned horizontally opposite the fan casing.
12. Reconnect the fan motor connector back to the connector of the base panel.
13. Carefully place the fan deck compartment with (4) M6 bolts, taking care not to damage the fan motor wiring.
How do I use the buttons on the wired controller for the TCL TCD140D1HWH-DV?
• [ON/OFF] button: Press to turn the air conditioner on or off.
• [MODE] button: Press to cycle through the running modes: AUTO -> COOL -> DRY -> FAN -> HEAT.
• [∧ / ∨] button: Press to increase (∧) or decrease (∨) the set temperature or time value.
• [FAN SPEED] button: Press to cycle through fan speeds: Mute -> Low speed -> Medium-low speed -> Medium speed -> Medium-high speed -> High speed -> Turbo -> Auto speed.
• [UP-DOWN SWING]/[ENTER] button: Press to activate or inactivate the upward-downward swing. When setting functions, press this button to confirm a selection.
• [LEFT-RIGHT SWING]/[BACK]button: Press to activate or inactivate the left-right swing. When setting functions, press this button to return to the previous setting.
• [FUNCTION] button: Press to select a function. The selected function icon will blink. Use the ∧ / ∨ buttons to switch to the next function. A permanently lit icon means the function is activated.
How do I set the Night Quiet Mode on my TCL TCD140D1HWH-DV?
You can set the Night Quiet Mode using the wired controller.
1. In the power on or off state, press and hold the “FAN” key and the “∨” key for 5-7 seconds to enter the parameter setting screen.
2. Use the “∧” or “∨” keys until the time display area shows “bA” and it is blinking.
3. Press the [ENTER] button. “bA” will stop blinking and the temperature display zone will blink.
4. Use the “∧” or “∨” buttons to select “ON” or “OF”, then press the [ENTER] button to enable or disable Night Quiet Mode.
5. After enabling, “bA” will blink again. Use the “∧” or “∨” buttons to navigate to the icon “bb” (start time), which will blink.
6. Press the [ENTER] button. The digital code in the temperature display zone will blink. Select a start time between “0” and “23”.
7. Press the [ENTER] button to confirm. “bb” will blink again. Use “∧” or “∨” to navigate to “bC” (end time), which will blink.
8. Press the [ENTER] button. The digital code will blink. Select an end time between “0” and “23”.
9. Press the [ENTER] button to confirm. “bC” will blink.
10. Press the [BACK] or [MODE] button (or wait 5 seconds) to return to the normal display.
Notes: Night Quiet Mode is effective only in cooling or heating modes. Once enabled, it will activate and deactivate at the selected start and end times. The start and end times cannot be the same.
How do I adjust the static pressure settings on the TCL TCD140D1HWH-DV?
The default static pressure is 150 Pa. If this doesn’t meet the requirements of your duct installation, you can adjust it using the wired controller.
1. In the power on or off state, press and hold the “FAN” key and the “∨” key for 5-7 seconds to enter the parameter setting screen.
2. Use the “∧” or “∨” keys to select the icon “PL” in the time display area. “PL” will blink.
3. Press the [ENTER] button. “PL” will stop blinking, and a digital code will blink in the temperature display zone (default is “00”).
4. Use the “∧” or “∨” keys to select a number from “01” to “09” corresponding to the static pressure value you need.
5. Press the [ENTER] button to confirm. “PL” will blink again.
6. Press the [BACK] or [MODE] button (or wait 15 seconds) to return to the normal display.
The corresponding codes and static pressure values are:
| Display code | P1 | P2 | P3 | P4 | P5 | P6 | P7 | P8 | P9 |
|---|---|---|---|---|---|---|---|---|---|
| Value | (0Pa) | (25Pa) | (50Pa) | (75Pa) | (100Pa) | (125Pa) | (150Pa) | (175Pa) | (200Pa) |
When do I need to add or remove refrigerant for the TCL TCD140D1HWH-DV?
The TCL TCD140D1HWH-DV models are pre-charged with refrigerant for 20 meters of connecting piping.
• If pipeline length exceeds 20 meters: Additional refrigerant is required. The formula is:
Additional charge (kg) = {Main length (m) – 20(m)} × 0.03 (kg/m).
• If pipeline length is between 10m and 20m: Refrigerant must be reduced for optimal performance. The formula is:
Amount reduced (kg) = {20(m) – main length (m)} × 0.03 (kg/m).
• If pipeline length is between 5m and 10m: Refrigerant must be reduced for optimal performance. The formula is:
Amount reduced (kg) = {20(m) – main length (m)} × 0.03 (kg/m).
• If pipeline length is shorter than 5 meters: The refrigerant shall be at the rated charge indicated on the nameplate for 5 meters of refrigerant pipeline.
The additional charge per meter of pipe for the TCD140/160 model is 30g/m.
What are the piping length and height limits for the TCL TCD140D1HWH-DV?
The limits for the refrigerant connection pipe are as follows:
| Pipe Limit | TCD100/125/140/160 |
|---|---|
| Longest pipe (L) | 75m |
| Maximum height drop (H) between indoor and outdoor unit | 30m |
When the height drop between the indoor and outdoor units is longer than 10m, an oil return bend should be added every 6m.
What should I do if my TCL TCD140D1HWH-DV won’t run?
If your air conditioner can’t run, check the following items before calling for service:
| Problem | Cause | Corrective measure |
|---|---|---|
| The air conditioner can’t run. | If you turn off the unit and then immediately turn it on, the compressor will delay running for 3 minutes for protection. | Please wait for a while. |
| Wire connection is wrong. | Connect wires according to the wiring diagram. | |
| Fuse or circuit breaker is broken. | Replace the fuse or switch on the circuit breaker. | |
| Power failure. | Restart after power is resumed. | |
| Power plug is loose. | Reinsert the power plug. | |
| Wired controller has low battery. | Replace the batteries. |
Why is my TCL TCD140D1HWH-DV not cooling or heating effectively?
If you are experiencing bad cooling or heating effect, check these possible causes:
| Cause | Corrective measure |
|---|---|
| Air inlet and outlet of indoor or outdoor units have been blocked. | Clear the obstacles and keep the area for indoor and outdoor units well ventilated. |
| Improper temperature setting. | Reset to a proper temperature. |
| Fan speed is too low. | Reset to a proper fan speed. |
| Air flow direction is not right. | Change the direction of air louvers. |
| Doors or windows are open. | Close them. |
| Exposed under direct sunshine. | Put on curtains or louvers in front of the windows. |
| Too many heat sources in the room. | Remove unnecessary heat sources. |
| Filter is blocked or dirty. | Send for a professional to clean the filter. |
What does an error code on my TCL TCD140D1HWH-DV display mean?
If the display panel or wired controller shows an error code, refer to the following table for its meaning.
| Error Code | Error Content | Error Code | Error Content |
|---|---|---|---|
| E0 | Indoor and outdoor communication failure | F1 | Battery module failure |
| E1 | Indoor ambient temperature sensor failure | F2 | Exhaust temperature sensor failure protection |
| E2 | Indoor fancoil temperature sensor failure | F3 | Failure protection of outer tube temperature sensor |
| E3 | Outdoor fancoil temperature sensor failure | F4 | Abnormal protection of refrigerant circulation |
| E4 | Abnormal system malfunction (lack of fluorine) | F5 | PFC protection |
| E5 | Model configuration error | F6 | Compressor missing/ reverse phase protection |
| E6 | Indoor PG/DC fan failure | F7 | Module temperature protection |
| E7 | Outdoor ambient temperature sensor failure | F8 | Abnormal commutation of four-way valve |
| E8 | Outdoor exhaust temperature sensor failure | F9 | Module temperature sensor circuit malfunction |
| E9 | Outdoor IPM module failure/compressor drive failure | FA | Compressor phase current detection fault |
| EA | Outdoor current sensor failure | Fb | Cooling and heating overload protection limit / reduce frequency |
| Eb | PCB and display screen communication Failure | FC | High power protection limit / reduce frequency |
| EC | Outdoor modules Communication failure | FE | Module current protection limit / reduce frequency |
| EE | Outdoor EEPROM fault | FF | Module temperature protection limit / reduce frequency |
| EF | Outdoor DC fan failure | FH | Drive protection limit / reduce frequency |
| EH | Outdoor suction sensor failure | FP | Anti condensation protection limit / reduce frequency |
| EP | Outdoor compressor casing top failure | FU | Anti freezing protection limit / reduce frequency |
| EU | Outdoor voltage sensor failure | Fj | Exhaust protection limit / reduce frequency |
| Ej | Outdoor central coil temperature sensor failure | Fn | External AC current protection limit / reduce frequency |
| En | Outdoor air pipe temperature sensor failure | Fy | Fluorine deficiency protection |
| Ey | Outdoor liquid pipe temperature sensor failure | H1 | High pressure switch malfunction |
| P0 | IPM module protection | H2 | Low pressure switch malfunction |
| P1 | Overvoltage and undervoltage protection | bf | TVOC sensor failure |
| P2 | Overcurrent protection | be | PM2.5 sensor failure |
| P3 | Other protections | bj | Humidity sensor failure |
| P4 | Protection against excessive outdoor exhaust temperature | bE | CO2 sensor malfunction |
| P5 | Cooling protection against overcooling | bd | Fresh air fan failure |
| P6 | Cooling and anti overheating protection | d4 | Water full protection failure |
| P7 | Heating and anti overheating protection | d5 | Access control protection |
| P8 | Protection against high or low outdoor temperature | b5 | Main fan drive communication fault |
| P9 | Compressor drive protection (abnormal load) | Fd | Refrigerant sensor fault |
| PA | Communication failure/mode conflict | Hd | Refrigerant leakage protection |
| F0 | Infrared human sensing sensor failure |
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD TCL TCD140D1HWH-DV (02) PDF DOCUMENT