Free English TCL TCD100D1HWH-DV (02) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.


CLICK HERE TO DOWNLOAD TCL TCD100D1HWH-DV (02) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

What are the primary safety warnings I should be aware of when installing the TCL TCD100D1HWH-DV?

Failure to observe these warnings may result in death, injury, or damage to the equipment.

• Only a qualified dealer or personnel should carry out installation work. Do not attempt to install the machine yourself, as improper installation can lead to water leakage, electric shock, or fire.

• Perform installation work strictly in accordance with this installation manual to avoid water leakage, electrical shock, or fire.

• Use only the specified accessories and parts for installation. Using non-specified parts can cause water leakage, electric shock, fire, or unit failure.

• Install the air conditioner on a structure strong enough to support its weight. An insufficiently strong structure may result in the equipment falling and causing injuries.

• Carry out installation considering strong winds, typhoons, or earthquakes to prevent the equipment from falling and causing accidents.

• Ensure a separate power supply circuit is provided for this unit. All electrical work must be performed by qualified personnel according to local laws and regulations.

• Secure all wiring, use the specified wires, and ensure no external forces act on the terminal connections. Improper connections can result in fire.

• Position wires so that the switch box cover can be securely fastened to prevent electric shock, fire, or overheating terminals.

• If refrigerant gas leaks during installation, ventilate the area immediately.

• After completing installation, check for refrigerant gas leaks. A fire may occur if leaked refrigerant contacts an ignition source.

• Disconnect all supply circuits before accessing terminals and electrical parts.

• Grounding is necessary. Do not connect the earth wire to gas pipes, water pipes, a lightning conductor, or a telephone ground wire.

• An earth leakage breaker must be installed to prevent electric shock.


What safety cautions should be followed during the installation of the TCL TCD100D1HWH-DV?

Failure to observe these cautions may result in injury or damage to the equipment.

• Do not install the indoor unit or wired controller in areas where flammable gases may leak, where carbon fiber or ignitable dust is present, or where volatile flammables like thinner or gasoline are handled.

• Do not install the indoor unit or controller in areas filled with steam or where the ground is always wet to prevent damage to electrical components and potential electric shock.

• Use only refrigerant piping approved for R32 refrigerant to prevent explosive rupture.

• When connecting piping, prevent air or other substances from entering the refrigeration cycle to avoid lower capacity, abnormally high pressure, explosion, and injury.

• The appliance should be installed in accordance with national wiring regulations.

• Children should not play with the appliance. Cleaning and user maintenance should not be performed by children without supervision.


What are the specific servicing instructions for the R32 refrigerant in the TCL TCD100D1HWH-DV?

1. The appliance must be installed, operated, and stored in a room with a floor area larger than 4m².

2. The installation of pipe-work should be kept to a minimum and protected from physical damage.

3. Pipe-work shall not be installed in an unventilated space smaller than 4m².

4. Compliance with national gas regulations must be observed.

5. Mechanical connections must be accessible for maintenance.

6. Ensure ventilation openings are clear of obstruction.

7. Servicing should only be performed as recommended by the manufacturer.

8. The appliance must be stored in a well-ventilated area where the room size corresponds to the area specified for operation.

9. The appliance must be stored in a room without continuously operating open flames (e.g., a gas appliance) or ignition sources (e.g., an electric heater).

10. Store the appliance to prevent mechanical damage.

11. Do not use means to accelerate defrosting or to clean, other than those recommended.

12. Do not pierce or burn the appliance.

13. Be aware that refrigerants may not contain an odor.

14. Any person working on a refrigerant circuit must hold a valid certificate from an accredited assessment authority.


What safety checks are required before working on a TCL TCD100D1HWH-DV system with flammable R32 refrigerant?

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to minimize the risk of ignition. The following precautions must be complied with:

1. **Work Procedure:** Work must be undertaken under a controlled procedure to minimize the risk of flammable gas or vapor being present.

2. **General Work Area:** All maintenance staff and others in the area must be instructed on the nature of the work. Avoid working in confined spaces. The area around the workspace should be sectioned off and made safe by controlling flammable materials.

3. **Checking for Refrigerant:** The area must be checked with an appropriate refrigerant detector before and during work to ensure the technician is aware of potentially flammable atmospheres. The leak detection equipment must be suitable for flammable refrigerants (i.e., non-sparking, adequately sealed, or intrinsically safe).

4. **Presence of Fire Extinguisher:** If any hot work is conducted, appropriate fire extinguishing equipment (dry powder or CO2) must be available.

5. **No Ignition Sources:** Do not use any ignition sources, including cigarette smoking, that could lead to fire or explosion. Keep all possible ignition sources away from the site of installation, repair, removal, and disposal.

6. **Ventilated Area:** Ensure the area is in the open or adequately ventilated before breaking into the system or conducting hot work. Ventilation should continue during the work period.


What are the minimum room area requirements for installing the TCL TCD100D1HWH-DV?

The TCL TCD100D1HWH-DV air conditioner uses R32 refrigerant. The installation area must be larger than the minimum construction area, which is determined by the total refrigerant charging quantity (factory charge + additional charge). The minimum area for a ceiling concealed duct type unit is as follows:

R32 refrigerant Weight (kg) Area (m²)
<1.224
1.224 0.956
1.4 1.25
1.6 1.63
1.8 2.07
2.0 2.55
2.2 3.09
2.4 3.68
2.6 4.31
2.8 5.00
3.0 5.74
3.2 6.54
3.4 7.38
3.6 8.27
3.8 9.22
4.0 10.2
4.2 11.3
4.4 12.4
4.6 13.5
4.8 14.7
5.0 16.0
5.2 17.3
5.4 18.6
5.6 20.0
5.8 21.5
6.0 23.0
6.2 24.5
6.4 26.1
6.6 27.8
6.8 29.5
7.0 31.3
7.2 33.1
7.4 34.9
7.6 36.9
7.8 38.8
8.0 40.8

Where should I install the indoor and outdoor units of the TCL TCD100D1HWH-DV?

INDOOR UNIT Installation Location:

1. A place with sufficient space for repair, in a hung ceiling that can bear the weight of the machine.

2. A place where the air inlet and outlet are not hindered and are without influence from outdoor air.

3. A place without heat sources like smoke, fire, or toxic pollution.

4. A place where airflow can be transmitted everywhere in the room.

5. A place convenient for installation.

OUTDOOR UNIT Installation Location:

1. A place with sufficient space for installation and repair.

2. A place where the air inlet and outlet are not hindered and without strong air flowing.

3. A dry and ventilated place.

4. A place where the overhang is level and can bear the weight of the outdoor unit, without much noise.

5. A place where neighbors are not annoyed by noise and exhausted air.

6. A place without leakage of flammable gas.

7. A place convenient for installation.

Caution: Avoid the following locations as they may cause malfunction:

• A place with flammable gas leakage.

• A place with salty air surrounding (near the coast).

• A place with caustic gas (like sulfide) existing in the air.

• In a kitchen where it is full of oil gas.

• A place with strong electromagnetic wave existing.

• A place with acid or alkaline liquid evaporating.


What accessories are included with the TCL TCD100D1HWH-DV?

The following accessories are included with your unit:

Name Quantity
Hose Clamp 1
Drain Hose 1
Installation Manual 1
Operation Manual 1
Hanger Bracket Accessories Pack 1
Pipe Insulation 2
Wired Controller 1
Wired controller connection cable 1

What should be checked after the installation of my TCL TCD100D1HWH-DV is complete?

The following items should be checked after completing the installation work to ensure proper operation and safety.

Items to be checked If not properly done, what is likely to occur
Is the gas leak test finished? It may result in insufficient cooling or heating.
Does the unit require external insulation? Condensate water may drip.
Does drainage flow smoothly? Condensate water may drip.
Does the power supply voltage correspond to that shown on the name plate? The unit may malfunction or the components burn out.
Is the wiring and piping correct? The unit may malfunction or the components burn out.
Is the unit safely grounded? Dangerous during electric leakage.
Is the wiring size according to specification? The unit may malfunction or the components burn out.
Is something blocking the air outlet or inlet of either the indoor or outdoor units? It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge noted down? The refrigerant charge in the system is not clear.
Is the indoor unit positioned so that it is not in contact with parts of the ceiling? Vibration and noise can be transmitted into building.
Is the airflow within specification? Poor performance or malfunction.
Is an air filter installed in the return air? Blocked heat exchanger causing malfunction or compressor failure.
Is an external drain tray installed? Condensate water may drip.
Check and confirm that there are no R32 leak after the installation.

Additionally, confirm the following at completion:

• Did you show the customer how to operate the system while referring to the operation manual? Provide a detailed explanation of operation.

• Review the safety considerations.

• Did you hand the operation manual over to the customer?


How do I perform a drain test on the TCL TCD100D1HWH-DV?

A drain test should be conducted after the electrical work is complete. For new buildings, conduct the test before the ceiling is furnished. This test should be performed even if the unit is installed during the heating season.

Test Method:

1. Remove the test cover.

2. Fill the water pan with 2 liters of water using a stow tube (prepare on site).

3. Turn on the unit in COOLING mode. You will hear the drain pump work.

4. Check that the water is discharged properly (a 1-minute lag is possible depending on the drain pipe length). Check for any water leaks from the joints.

5. Turn off the air conditioner and put the cap back on.


How do I separate the indoor unit of the TCL TCD100D1HWH-DV for installation?

WARNING: Power should be disconnected and tagged off when performing this procedure if the unit is already installed. Separate the unit only when necessary and on a flat surface.

To separate the indoor unit:

1. Carefully remove the Airbox compartment by removing the (4) M6 bolts.

2. Carefully remove the (1) thermistor cable (R1T) from its clamp.

3. Wrap the thermistor cable and place it neatly into the rubber bush next to the fan deck.

4. Carefully disconnect the fan motor wiring from the base panel located underneath the reactor box.

5. Remove the (5) tapping screws located above the fan deck flange.

6. Remove the (4) M6 bolts securing the fan deck to the base panel of the heat exchanger compartment.

7. Carefully separate the fan deck assembly from the base panel, taking care not to damage the fan motor wiring.

8. Carefully detach the fan deck.

To reassemble the fan deck and heat exchanger compartments:

9. Carefully place the fan deck back in position on the base panel.

10. Secure the fan deck onto the heat exchanger compartment with the (4) M6 bolts and (5) tapping screws for the top flange of the fan deck.

11. Place the thermistor cable (R1T) back to the side of the fan deck and secure it with the thermistor clamp. Ensure the tip of the thermistor is positioned horizontally opposite the fan casing.

12. Reconnect the fan motor connector back to the connector of the base panel.

13. Carefully place the fan deck compartment with (4) M6 bolts, taking care not to damage the fan motor wiring.


What are the functions of the buttons on the wired controller for the TCL TCD100D1HWH-DV?

1. **[ON/OFF] button:** Controls the power on and off of the air conditioner.

2. **[MODE] button:** Changes the running modes cyclically: AUTO → COOL → DRY → FAN → HEAT.

3. **[∧ / ∨] button:** Increases (∧) or decreases (∨) the set temperature or time value.

4. **[FAN SPEED] button:** Changes the fan speeds cyclically: Mute → Low speed → Medium-low speed → Medium speed → Medium-high speed → High speed → Turbo → Auto speed.

5. **[UP-DOWN SWING]/[ENTER] button:** Activates or inactivates the upward-downward swing function. When setting other functions, this button confirms the selection.

6. **[LEFT-RIGHT SWING]/[BACK] button:** Activates or inactivates the left-right swing function. When setting other functions, this button returns to the previous setting.

7. **[FUNCTION] button:** Used for function selection. The current function icon will blink. Use the ∧ / ∨ buttons to switch to the next function. A permanently lit icon means the function is activated.


How do I set the Night Quiet Mode on the TCL TCD100D1HWH-DV?

You can set the Night Quiet Mode using the wired controller.

1. In the power on or off state, press and hold the “FAN” key and the “∨” key for 5-7 seconds to enter the parameter setting screen.

2. The temperature display will show “01” and the time display will show a blinking “PO”.

3. Use the “∨” or “∧” keys to select the icon “bA”, which will then blink.

4. Press the [ENTER] button. “bA” will stop blinking, and the temperature display icon will blink.

5. Use the “∨” or “∧” buttons to select “ON” or “OF”, then press the [ENTER] button to enable or disable Night Quiet Mode.

6. Press the [ENTER] button again, “bA” will blink. Use “∨” or “∧” to navigate to the icon “bb”, which will blink.

7. Press the [ENTER] button. The digital code in the temperature display will blink. Select a start time between “0” and “23”.

8. Press the [ENTER] button to confirm. The “bb” icon will blink. Use “∨” or “∧” to navigate to the “bC” icon, which will blink.

9. Press the [ENTER] button. The digital code will blink. Select an end time between “0” and “23”.

10. Press the [ENTER] button to confirm. The “bC” icon will blink.

11. Press the [BACK] or “MODE” icon (or wait 5 seconds) to return to the normal display.

Notes:

• Night Quiet Mode is effective only in cooling or heating modes.

• The mode will activate and deactivate at the selected start and end times.

• The start and end times cannot be the same.

• Activating this mode may result in a slight reduction in capacity.


How do I adjust the static pressure and manual constant air volume settings on my TCL TCD100D1HWH-DV?

The default static pressure is 150 Pa. If this doesn’t meet your ductwork requirements, you can adjust it using the wired controller.

1. With the unit on or off, press and hold the “FAN” key and the “∨” key for 5-7 seconds.

2. The parameter setting screen will appear. The temperature display shows “01”, and the time display shows a blinking “PO”.

3. Use the “∨” or “∧” keys to select the “PL” icon, which will blink.

4. Press the [ENTER] button. “PL” will stop blinking, and the digital code in the temperature zone will blink (default is “00”).

5. Use the “∨” or “∧” keys to select a number from “01” to “09” corresponding to the desired static pressure value.

6. Press the [ENTER] button to confirm. The “PL” icon will blink again.

7. Press the [BACK] or “MODE” icon (or wait 15 seconds) to return to the normal display.

The code corresponds to the static pressure value as follows:

Display code Set definition (Static Pressure Value)
00 current operating static pressure value is displayed
01 P1 (0Pa)
02 P2 (25Pa)
03 P3 (50Pa)
04 P4 (75Pa)
05 P5 (100Pa)
06 P6 (125Pa)
07 P7 (150Pa)
08 P8 (175Pa)
09 P9 (200Pa)
10 current indoor unit free static function
11 pressure setting

How much additional refrigerant charge is needed for the TCL TCD100D1HWH-DV based on pipe length?

The TCL TCD100D1HWH-DV is pre-charged for 20 meters of connecting piping. The refrigerant amount needs adjustment if the pipe length is different.

• **If pipeline exceeds 20 meters:** Add refrigerant.
Additional charge (kg) = {Main length (m) – 20(m)} × 0.03 (kg/m)

• **If pipeline is 10m to 20m:** Reduce refrigerant.
Amount of refrigerant reduced (kg) = {20(m) – main length (m)} x 0.03 (kg/m)

• **If pipeline is 5m to 10m:** Reduce refrigerant.
Amount of refrigerant reduced (kg) = {20(m) – main length (m)} × 0.03 (kg/m)

• **If pipeline is shorter than 5 meters:** The refrigerant shall be at the rated charge indicated on the nameplate for 5 meters of piping.

The additional charge per meter of pipe for R32 is 30g.

The maximum pipe length and height drop are as follows:

TCD100/125/140/160
Longest pipe (L) 75m
Maximum height drop (H) 30m

When the drop between indoor and outdoor units is longer than 10m, an oil return bend should be added every 6m.


What do the error codes on my TCL TCD100D1HWH-DV mean?

If the display panel or wired control shows an error code, refer to the following table for its meaning.

Error Code Error Content Error Code Error Content
E0 Indoor and outdoor communication failure F1 Battery module failure
E1 Indoor ambient temperature sensor failure F2 Exhaust temperature sensor failure protection
E2 Indoor fancoil temperature sensor failure F3 Failure protection of outer tube temperature sensor
E3 Outdoor fancoil temperature sensor failure F4 Abnormal protection of refrigerant circulation
E4 Abnormal system malfunction (lack of fluorine) F5 PFC protection
E5 Model configuration error F6 Compressor missing/ reverse phase protection
E6 Indoor PG/DC fan failure F7 Module temperature protection
E7 Outdoor ambient temperature sensor failure F8 Abnormal commutation of four-way valve
E8 Outdoor exhaust temperature sensor failure F9 Module temperature sensor circuit malfunction
E9 Outdoor IPM module failure/compressor drive failure FA Compressor phase current detection fault
EA Outdoor current sensor failure Fb Cooling and heating overload protection limit / reduce frequency
Eb PCB and display screen communication Failure FC High power protection limit / reduce frequency
EC Outdoor modules Communication failure FE Module current (compressor phase current) protection limit / reduce frequency
EE Outdoor EEPROM fault FF Module temperature protection limit / reduce frequency
EF Outdoor DC fan failure FH Drive protection limit / reduce frequency
EH Outdoor suction sensor failure FP Anti condensation protection limit / reduce frequency
EP Outdoor compressor casing top failure FU Anti freezing protection limit / reduce frequency
EU Outdoor voltage sensor failure Fj Exhaust protection limit / reduce frequency
Ej Outdoor central coil temperature sensor failure Fn External AC current protection limit / reduce frequency
En Outdoor air pipe temperature sensor failure Fy Fluorine deficiency protection
Ey Outdoor liquid pipe temperature sensor failure H1 High pressure switch malfunction
PO IPM module protection H2 Low pressure switch malfunction
P1 Overvoltage and undervoltage protection bf TVOC sensor failure
P2 Overcurrent protection be PM2.5 sensor failure
P3 Other protections bj Humidity sensor failure
P4 Protection against excessive outdoor exhaust temperature bE CO2 sensor malfunction
P5 Cooling protection against overcooling bd Fresh air fan failure
P6 Cooling and anti overheating protection d4 Water full protection failure
P7 Heating and anti overheating protection d5 Access control protection
P8 Protection against high or low outdoor temperature b5 Main fan drive communication fault
P9 Compressor drive protection (abnormal load) Fd Refrigerant sensor fault
PA Communication failure/mode conflict Hd Refrigerant leakage protection
FO Infrared human sensing sensor failure

What should I do if my TCL TCD100D1HWH-DV air conditioner won’t run?

If your air conditioner fails to function, please check the following items before calling for maintenance:

Problem Cause Corrective measure
The air conditioner can’t run. If you turn off the unit and then immediately turn it on, the compressor will delay running for 3 minutes to protect it. Please wait for a while.
Wire connection is wrong. Connect wires according to the wiring diagram.
Fuse or circuit breaker is broken. Replace the fuse or switch on the circuit breaker.
Power failure. Restart after power is resumed.
Power plug is loose. Reinsert the power plug.
Wired controller has low battery. Replace the batteries.

Why is the cooling or heating effect of my TCL TCD100D1HWH-DV poor?

If you are experiencing bad cooling or heating effects, check the following possible causes and solutions:

Cause Corrective measure
Air inlet and outlet of indoor or outdoor units have been blocked. Clear the obstacles and keep the room for indoor and outdoor units well ventilated.
Improper temperature setting. Reset a proper temperature.
Fan speed is too low. Reset a proper fan speed.
Air flow direction is not right. Change the direction of air louvers.
Doors or windows are open. Close them.
Exposed under direct sunshine. Put on curtains or louvers in front of the windows.
Too many heat sources in the room. Remove unnecessary heat sources.
Filter is blocked or dirty. Send for a professional to clean the filter.

Are these situations with my TCL TCD100D1HWH-DV considered operation failures?

The following situations are not operation failures:

Phenomenon Time of occurrence Cause
Mist comes from the air conditioner. During operation. If the unit is running under high humidity, the wet air in the room will be quickly cooled down.
System switches to heating mode after defrosting. During operation. Defrosting process will generate some water, which will turn to water vapor.
The air conditioner is buzzing at the beginning of operation. Beginning of operation. The temperature controller will be buzzing when it starts. The noise will become weak after 1 minute.
When the unit is turned on, it purrs. When turned on. When the system is just started, the refrigerant is not stable. After about 30s, the purr becomes low.
Refrigerant brushing sound when defrosting under heating. During heating/defrost. This is the sound of the 4-way valve switching direction. The sound will disappear after the valve changes direction.
There is a hissing sound when the unit is started or stopped. During and after operation. This is the sound of gaseous refrigerant that stops flowing and the sound of the drainage system.
There is a sound of crunching during and after operation. During and after operation. Due to temperature change, the front panel and other components may swell up and cause an abrasion sound.
There is a hissing sound when the unit is turned on or suddenly stopped. During operation or after defrosting. This is because the refrigerant suddenly stops flowing or changes its flow direction.
Dust comes from the air conditioner when starting after a long time. After being unused for a long time. Dust inside the indoor unit comes out together with the air.
The air conditioner generates some smell. During operation. The room smell or the smell of cigarettes comes out through the indoor unit.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD TCL TCD100D1HWH-DV (02) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.