FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF USER GUIDE
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF USER MANUAL
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF OWNER GUIDE
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF OWNER MANUAL
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF REFERENCE GUIDE
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF REFERENCE MANUAL
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH PHOTON PI-PLUS 3.6K (01) PDF OPERATING INSTRUCTIONS
CLICK HERE TO DOWNLOAD PHOTON PI-PLUS 3.6K (01) PDF MANUAL
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the safety instructions for using the solar inverter?
Read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual before using the unit.
To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
Only qualified personnel can install this device with battery.
Never charge a frozen battery.
For optimum operation of this inverter/charger, follow required specifications to select appropriate cable size. It is very important to correctly operate this inverter/charger.
Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
Strictly follow installation procedure when disconnecting AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
One piece of 150A fuse is provided as over-current protection for the battery supply.
GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounder wiring system. Comply with local requirements and regulations to install this inverter.
Never cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, send this inverter/charger back to local dealer or service center for maintenance.
How do I unpack and inspect the solar inverter?
Before installation, inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of the package:
The unit x 1
User manual 1
How do I prepare for mounting the unit?
Before connecting all wires, take off the bottom cover by removing two screws as shown.
What considerations should be made when mounting the solar inverter?
Do not mount the inverter on flammable construction materials.
Mount on a solid surface.
Install this inverter at eye level in order to allow the LCD display to be read at all times.
For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
The ambient temperature should be between and to ensure optimal operation.
The recommended installation position is to be adhered to the wall vertically.
Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
The inverter is suitable for mounting on concrete or other non-combustible surface only.
To install the unit, screw three screws:
1,2 Use the M6*80mm expansion bolts.
3 Use M4 or M5.
How do I connect the battery to the inverter?
For safety operation and regulation compliance, it is requested to install a separate DC over-current protector or disconnect device between the battery and inverter. While a disconnect device may not be required in some applications, over-current protection is still required. Refer to the typical amperage in the table below for required fuse or breaker size.
All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, use the proper recommended cable and terminal size as below:
| Rated Capacity | Typical Amperage | Battery capacity | Wire Size | Cable(mm²) | Ring Terminal Dimensions D(mm) | Ring Terminal Dimensions L(mm) | Torque value | |
|---|---|---|---|---|---|---|---|---|
| 2KVA | 88A | 100AH | 1*6AWG | 14 | 6.4 | 33.2 | 2~3 Nm | |
| 2*10AWG | 6 | 6.4 | 23.8 | |||||
| 3KVA | 132A | 100AH | 1*4AWG | 22 | 6.4 | 33.2 | 2~3 Nm | |
| 200AH | 2*8AWG | 9 | 6.4 | 29.2 | ||||
| 3.6KVA | 165A | 200AH | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm | |
| 5KVA | 109A | 200AH | 1*2AWG | 38 | 6.4 | 39.2 | 2~3 Nm | |
| 2*6AWG | 28 | 6.4 | 33.2 | |||||
| 5.5KVA | 121A | 200AH | 1*2AWG | 34 | 6.4 | 39.2 | 2~3 Nm | |
| 2*6AWG | 14 | 6.4 | 33.2 | |||||
| 6.2KVA | 124A | 200AH | 1*2AWG | 38 | 8.4 | 39.2 | 5Nm | |
| 2*4AWG | 25 | 8.4 | 33.2 | |||||
| 8KVA | 183.2A | 250AH | 1*2/0AWG | 67.4 | 8.4 | 51 | 5Nm | |
| 11KVA | 228A | 250AH | 1*3/0AWG | 85 | 8.4 | 54 | 5Nm |
Follow these steps to implement battery connection:
Assemble battery ring terminal based on recommended battery cable and terminal size.
Insert the battery wires flatly into battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in the clockwise direction. Ensure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
Shock Hazard: Installation must be performed with care due to high battery voltage in series.
Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).
How do I connect the AC input/output?
Before connecting to AC input power source, install a separate AC breaker between the inverter and AC input power source. This ensures the inverter can be disconnected during maintenance and fully protected from over current of AC input. The recommended breaker specification is 32A for 24V system and 63A for 48V system.
There are two terminal blocks with ” IN ” and ” OUT” markings. Do NOT mis-connect input and output connectors.
All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, use the proper recommended cable size as below:
| Rated Capacity | Gauge | Torque value |
|---|---|---|
| 2KVA | 14AWG | 08~1.0Nm |
| 3KVA | 12AWG | 1.2~1.6Nm |
| 3.6KVA | 12AWG | 1.2~1.6Nm |
| 5KVA | 10AWG | 1.4~1.6Nm |
| 5.5KVA | 10AWG | 1.4~1.6Nm |
| 6.2KVA | 10AWG | 1.4~1.6Nm |
| 8KVA | 8AWG | 1.4~1.6Nm |
| 11KVA | 8AWG | 1.4~1.6Nm |
Follow these steps to implement AC input/output connection:
Before making AC input/output connection be sure to open DC protector or disconnector first.
Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N3 mm.
Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (ground) first.
Ground (yellow-green)
LINE (brown or black)
Neutral (blue)
Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
Make sure the wires are securely connected.
Appliances such as air conditioners require at least 2~3 minutes to restart because they need enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, check the manufacturer of the air conditioner if it is equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.
How do I connect the PV modules (solar charger models only)?
Before connecting to PV modules, install separately a DC circuit breaker between the inverter and PV modules.
All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, use the proper recommended cable size as below:
| Typical Amperage | Gauge | Torque Value |
|---|---|---|
| 30A | 12AWG | 1.4~1.6Nm |
When choosing the right PV module, first consider the following requirements:
The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter.
The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance.
If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.
Follow these steps to implement PV module connection:
Remove insulation sleeve 10 mm for positive and negative conductors.
Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
Fix wire cover to the inverter with supplied screws as shown in the chart.
Check the correct polarity of wire from PV modules and PV input connectors. Then, connect the positive pole(+) of the connection wire to the positive pole(+) of the PV input connector. Connect the negative pole (-)of the connection wire to the negative pole(-) of the PV input connector. Screw two wires tightly in the clockwise direction. Recommended tool: 4mm blade screwdriver.
How do I perform the final assembly after connecting all wirings?
After connecting all wirings, put the bottom cover back by screwing two screws as shown.
How do I power the unit ON/OFF?
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
What are the steps to start up the inverter?
Connect the battery that meets the requirements (battery voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.
For Mains power on:
Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode, which represents that the machine is successfully turned on, and then it will enter the AC mode.
For Battery boot:
Connect to the battery, press the power-on button to establish a working power source.
The system will automatically turn on. After waiting for a period of time, the panel will display battery mode, which represents that the machine is successfully turned on, and then it will enter the battery mode.
How do I shut down the inverter?
When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.
How do I interpret the LCD display icons?
Input Source Information:
| Icon | Function description |
|---|---|
| AC | Indicates the AC input. |
| PV | Indicates the PV input. |
| INPUTBATT 8.88 | Indicate input voltage, input frequency, PV voltage, charger current, charger power, battery voltage. |
Configuration Program and Fault Information:
| Icon | Function description |
|---|---|
| 88 | Indicates the setting programs. |
| 8.8 A ERROR | Indicates the warning and fault codes. Warning: flashing with warning code. |
| ERROR Fault: | lighting with fault code. |
Output Information:
| Icon | Function description |
|---|---|
| OUTPUTBATTLOAD 8.8.8 kW % Hz | Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. |
Battery Information:
| Icon | Function description |
|---|---|
| CHARGING | Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode. |
What are the recommended cable and breaker specifications for parallel operation?
Recommended AC input and output cable size for each inverter:
| Rated Capacity | AWG no. | Torque |
|---|---|---|
| 3KW | 12AWG | 1.2~1.6Nm |
| 3.6KW | 12AWG | 1.2~1.6Nm |
| 5KW | 10AWG | 1.2~1.6Nm |
| 5.5KW | 10AWG | 1.2~1.6Nm |
| 6.2KW | 10AWG | 1.2~1.6Nm |
| 8KW | 8AWG | 1.4~1.6Nm |
| 11KW | 8AWG | 1.4~1.6Nm |
You need to connect the cables of each inverter together. For battery cables, use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery terminal. The cable size used from the joint to the battery should be X times the cable size in the tables above, where X indicates the number of inverters connected in parallel. For AC input and output, follow the same principle.
Make sure all output Neutral wires of each inverter are connected all the time. Otherwise, it will cause inverter fault in error code #72.
Install the breaker at the battery and AC input side. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of battery or AC input.
Recommended breaker specification of battery for each inverter:
| Rated Capacity | 1 unit* | Rated Capacity | 1 unit* |
|---|---|---|---|
| 3KW | 150A/70VDC | 6.2KW | 150A/70VDC |
| 3.6KW | 200A/70VDC | 8KW | 300A/70VDC |
| 5KW | 150A/70VDC | 11KW | 300A/70VDC |
| 5.5KW | 150A/70VDC |
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times the current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:
| Rated Capacity | 2 units | 3 units | 4 units | 5 units | 6 units | 7 units | 8 units | 9 units |
|---|---|---|---|---|---|---|---|---|
| 3KW | 80A/ 230VAC | 120A/ 230VAC | 160A/ 230VAC | 200A/ 230VAC | 240A/ 230VAC | 280A/ 230VAC | 320A/ 230VAC | 360A/ 230VAC |
| 3.6KW | 80A/ 230VAC | 120A/ 230VAC | 160A/ 230VAC | 200A/ 230VAC | 240A/ 230VAC | 280A/ 230VAC | 320A/ 230VAC | 360A/ 230VAC |
| 5KW | 80A/ 230VAC | 120A/ 230VAC | 160A/ 230VAC | 200A/ 230VAC | 240A/ 230VAC | 280A/ 230VAC | 320A/ 230VAC | 360A/ 230VAC |
| 5.5KW | 80A/ 230VAC | 120A/ 230VAC | 160A/ 230VAC | 200A/ 230VAC | 240A/ 230VAC | 280A/ 230VAC | 320A/ 230VAC | 360A/ 230VAC |
| 6.2KW | 80A/ 230VAC | 120A/ 230VAC | 160A/ 230VAC | 200A/ 230VAC | 240A/ 230VAC | 280A/ 230VAC | 320A/ 230VAC | 360A/ 230VAC |
| 8KW | 120A/ 230VAC | 180A/ 230VAC | 240A/ 230VAC | 300A/ 230VAC | 360A/ 230VAC | / | / | / |
| 11KW | 120A/ 230VAC | 180A/ 230VAC | 240A/ 230VAC | 300A/ 230VAC | 360A/ 230VAC | / | / | / |
A circuit breaker should be installed at the AC input of each inverter, and the selection of the circuit breaker should refer to the AC input current of the machine nameplate.
Regarding three-phase system, you can use a 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units.
How is battery charging status displayed in AC mode?
| Status | Battery voltage | LCD Display |
|---|---|---|
| Constant Current mode/ Constant Voltage mode | <2V/cell | 4 bars will flash in turns. |
| 2~2.083V/cell | Bottom bar will be on and the other three bars will flash in turns. | |
| 2.083~2.167V/cell | Bottom two bars will be on and the other two bars will flash in turns. | |
| > 2.167 V/cell | Bottom three bars will be on and the top bar will flash. | |
| Floating mode. Batteries are fully charged. | 4 bars will be on. |
How is battery capacity displayed in battery mode?
| Load Percentage | Battery Voltage | LCD Display |
|---|---|---|
| Load>50% | <1.85V/cell | |
| 1.85V/cell~1.933V/cell | ||
| 1.933V/cell~2.017V/cell | ||
| >2.017V/cell | ||
| Load<50% | <1.892V/cell | |
| 1.892V/cell~1.975V/cell | ||
| 1.975V/cell~2.058V/cell | ||
| >2.058V/cell |
How do I interpret the load information display?
| OVER LOAD | Indicates overload. |
| Indicates the load level by 0-24%, 25-49%, 50-74%, and 75-100%. | |
| 100% 25% | 0%~24% 25%~49% 50%~74% 75%~100% |
How do I navigate and interpret the display settings?
The LCD display information will be switched in turns by pressing the “UP” or “DOWN” key. The selectable information is switched in the order of input voltage, input frequency, PV voltage, charging current, charging power battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, and main CPU Version.
Examples of selectable information and LCD displays:
Input voltage /Output voltage (Default Display Screen):
Input Voltage=230V, output voltage=230V
Input frequency:
Input frequency=50Hz
PV voltage:
PV voltage=260V
PV current:
PV current = 2.5A
PV power:
PV power = 500W
AC and PV charging current:
AC and PV charging current=50A
PV charging current:
PV charging current=50A
AC charging current:
AC charging current=50A
AC and PV charging power:
AC and PV charging power=500W
PV charging power:
PV charging power=500W
AC charging power:
AC charging power=500W
Load in Watt:
When load is lower than 1kW, load in W will present xxxW.
When load is larger than 1kW (>=1KW), load in W will present x.xkW.
Battery voltage/DC discharging current:
Battery voltage=25.5V, discharging current=1A
Main CPU version checking:
Main CPU version 00014.04
Setting BMS communication success display:
The left side shows the lithium battery temperature and the right side shows the lithium battery capacity.
The input current of the lithium battery is displayed on the left side, and the output current of the lithium battery is displayed on the right side.
What are the different operating modes and their descriptions?
Standby mode:
Description: No output is supplied by the unit but it still can charge batteries.
LCD display: Charging by utility and PV energy; Charging by utility; Charging by PV energy; No charging.
Fault mode:
Description: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on. PV energy and utility can charge batteries.
LCD display: Charging by utility and PV energy; Charging by utility; Charging by PV energy; No charging.
Line Mode:
Description: The unit will provide output power from the mains. It will also charge the battery at line mode.
LCD display: Charging by utility and PV energy; Charging by utility.
Battery Mode:
Description: The unit will provide output power from the battery and PV power.
If “solar first” is selected priority and solar energy is not sufficient to provide the load, solar energy and the utility will provide the loads and charge the battery at the same time.
If “solar first” is selected as output source priority and battery is not connected, solar energy and the utility will provide the loads.
Power from utility.
Power from battery and PV energy.
PV energy will supply power to the loads and charge battery at the same time.
Power from battery only.
Battery free mode:
Description: The device will provide output power from the PV power supply.
How do I access and change settings in the LCD setting program?
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press the “UP” or “DOWN” button to select setting programs. Then, press the “ENTER” button to confirm the selection or the ESC button to exit.
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
Setting Programs:
| Program | Description | Selectable option |
|---|---|---|
| 00 | Exit setting mode | Escape: 00 ESC |
| 01 | Output source priority: To configure load power source priority | Utility first (default): 01 USG (Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.) Solar first: 01 SOE (Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time.) BU priority: 01 SBU (Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.) |
| 02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 60A (default): 02 60. Setting range is from 10A to maximum charging current. Increment of each click is 10A. |
| 03 | AC input voltage range | Appliances (default): 03 APL (If selected, acceptable AC input voltage range will be within 90-280VAC.) UPS: 03 UPS (If selected, acceptable AC input voltage range will be within 170-280VAC.) |
| 04 | AC output mode *This setting is only available when the inverter is in standby mode (Switch off). |
Single: 04 SNG (When the units are used in parallel with single phase, select “PAL” in program 4.) Parallel: 04 PAL (When the units are used in parallel with single phase, select “PAL” in program 4.) L1 phase: 04 3P1 (It is required to have at least 3 inverters or maximum 9 inverters to support three-phase equipment. It is required to have at least one inverter in each phase or up to four inverters in one phase. Select “3P1” in program 4 for inverters connected to L1 phase.) L2 phase: 04 3P2 (Select “3P2” in program 4 for inverters connected to L2 phase.) L3 phase: 04 3P3 (Select “3P3” in program 4 for inverters connected to L3 phase.) Be sure to connect share current cable to units which are on the same phase. Do NOT connect share current cable between units on different phases. Besides, power saving function will be automatically disabled. |
| 05 | Battery type | AGM (default): 05 AGN User-Defined: 05 USE (If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.) Flooded: 05 FLd |
| 06 | Auto restart when overload occurs | Restart disable (default): 06 LFD Restart enable: 06 LYF |
| 07 | Auto restart when over temperature occurs | Restart disable (default): 07 ETD Restart enable: 07 EYF |
| 08 | ECO function: System will temporarily stop when the load is low in battery mode. | disable (default): ECO 08 SBS enable: ECO 08 SEN |
| 09 | Output frequency | 50Hz (default): 09 50Hz 60Hz: 09 60Hz |
| 10 | Output voltage | 220V: 10 220 230V (default): 10 230 240V: 10 240 |
| 11 | Maximum utility charging current Note: If setting value in program 02 is smaller than that in program 11, the inverter will apply charging current from program 02 for utility charger. |
30A (default): 11 30A Setting range is 2A, then from 10A to max AC charging current. Increment of each click is 10A. |
| 12 | Setting voltage point back to utility source when selecting “SBU priority” in program 01. | Available options in 24 system model: 23.0V (default): 12 23.0 Setting range is from 22V to 25.5V. Increment of each click is 0.5V. Available options in 48 system model: 46V (default): 12 46 Setting range is from 44V to 51V. Increment of each click is 1V. |
| 13 | Setting voltage point back to battery mode when selecting “SBU priority” in program 01. | Available options in 24 system model: Battery fully charged 27V (default): 13 FUL Setting range is from 24V to 29V. Increment of each click is 0.5V. |
| 16 | Charger source priority: To configure charger source priority | Available options in 48 system model: Battery fully charged 54V (default): 13 FUL 13 54.0. Setting range is from 48V to 58V. Increment of each click is 1V. If this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below: Utility first: 16 CUE (Utility will charge battery as first priority. Solar energy will charge battery only when utility power is not available.) Solar first: 16 C SO (Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.) Solar and Utility (default): 16 SNU (Solar energy and utility will charge battery at the same time.) Only Solar: 16 O SO (Solar energy will be the only charger source no matter utility is available or not.) If this inverter/charger is working in Battery mode, only solar energy can charge battery. Solar energy will charge battery if it is available and sufficient. |
| 18 | Alarm control | Alarm on (default): 18 CON Alarm off: 18 COF |
| 19 | Auto return to default display screen | Return to default display screen (default): 19 ESP (If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute.) Stay at latest screen: 19 HEP (If selected, the display screen will stay at latest screen user finally switches.) |
| 20 | Backlight control | Backlight on (default): 20 LON Backlight off: 20 LOF |
| 22 | Beeps while primary source is interrupted | Alarm on (default): 22 AON Alarm off: 22 AOF |
| 23 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Bypass disable (default): 23 BYP Bypass enable: 23 BYP |
| 25 | Record Fault code | Record enable (default): 25 FEN Record disable: 25 FDS |
| 26 | Bulk charging voltage (C.V voltage) | 24V system default setting: 28.2V: 26 28.2 48V system default setting: 56.4V: 26 56.4 If self-defined is selected in program 5, this program can be set up. Setting range is from 25.0V to 31.5V for 24V system model and 48.0V to 61.0V for 48V system model. Increment of each click is 0.1V. |
| 27 | Floating charging voltage | 24V system default setting: 27.0V: 27 27.0 48V system default setting: 54.0V: 27 54.0 default: 28 OFF |
| 28 | Reset factory setting | 48V system default setting: 54.0V: 28 ON |
| 29 | Low DC cut-off voltage: If battery power is only power source available, inverter will shut down. If PV energy and battery power are available, inverter will charge battery without AC output. | 24V system default setting: 21.0V: 29 21.0 If self-defined is selected in program 5, this program can be set up. Setting range is from 21.0V to 24.0V for 24V system model and 42.0V to 48.0V for 48V system model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. 48V system default setting: 42.0V: 29 42.0 |
| 30 | Battery equalization | Battery equalization disable (default): 30 EEN 30 EDS If “Flooded” or “User Defined” is selected in program 05, this program can be set up. |
| 31 | Battery equalization voltage | 24V system default setting: 29.2V: EV 31 29.2 48V system default setting: 58.4V: EV 31 58.4 Setting range is from 25.0V to 31.5V for 24V system mode and 48.0V to 61.0V for 48V system model. Increment of each click is 0.1V. |
| 33 | Battery equalized time | 60min (default): 33 60 Setting range is from 5min to 900min. Increment of each click is 5min. |
| 34 | Battery equalized timeout | 120min (default): 34 120 Setting range is from 5min to 900min. Increment of each click is 5min. |
| 35 | Equalization interval | 30days (default): 35 30D Setting range is from 0 to 90 days. Increment of each click is 1 day. |
| 36 | Equalization activated immediately | Enable: 36 AEN Disable (default): 36 ADS If equalization function is enabled in program 30, this program can be set up. If “Enable” is selected in this program, it is to activate battery equalization immediately and the LCD main page will show “EQ”. If “Disable” is selected, it will cancel equalization function until the next activated equalization time arrives based on program 35 setting. At this time, “EQ” will not be shown in the LCD main page. |
| 37 | BMS Function Switch | off (default): BN5 37 OFF Whether to enable the BMS communication function: BN5 37 ON |
| 38 | Bat Soc Under Lock | 38 10 BMS low voltage SOC value, if the BMS SOC value is lower than the set value, the inverter will shut down to protect the battery. |
| 39 | Bat Soc Turn To Ac | When the working mode of the inverter is set to the battery priority mode, the inverter will be forced to enter the mains charging when the SOC of the BMS is lower than the set value. |
| 40 | Bat Soc Turn To Dc | When the working mode of the inverter is set to the battery priority mode, the inverter resumes the DC working mode when the SOC of the BMS is higher than the set value. |
| 41 | Bat Restart Soc | When the inverter is turned on, the SOC must be higher than the set value to work normally. |
| 42 | BMS communication protocol | Choose RS485 communication protocol: 0 |
| 45 | Reset PV energy storage | Not reset (default): 45 NRT Reset: 45 RST |
| 60 | Dual output | Disable (default): 60 L2F Use: 60 L20 Default setting: 44.0V. |
| 61 | Enter the dual output functional voltage point | Default setting: 22.0V: 61 22.0 If battery voltage lowers than inverter setting, the second output will be cut off. Increment of each click is 0.1V. |
| 62 | Enter the dual output functional SOC point | If BMS capacity lowers than SOC setting, the second output will be cut off: 62 15 |
What is battery equalization and how do I apply it?
Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it is recommended to equalize the battery periodically.
To apply equalization function:
You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods:
Setting equalization interval in program 35.
Active equalization immediately in program 36.
When to Equalize:
In stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.
Equalize charging time and timeout:
In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.
However, in the Equalize stage, when battery equalized time is expired and battery voltage does not rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
What are the fault descriptions and their icons?
Fault: The inverter enters the fault mode, the red LED light is always on and the LCD displays the fault code.
Fault Reference Code:
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 |
| 02 | Over temperature or NTC is not connected well. | 02- |
| 03 | Battery voltage is too high. | 03- |
| 04 | Battery voltage is too low. | 04- |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05- |
| 06 | Output voltage is too high. | 06- |
| 07 | Over load time out. | 07- |
| 08 | Bus voltage is too high. | 08- |
| 09 | Bus soft start failed. | 09- |
| 51 | Over currents or surge. | 51- |
| 52 | Bus voltage is too low. | 52- |
| 53 | Inverter soft start failed. | 53- |
| 55 | Over DC voltage in AC output. | 55- |
| 57 | Current sensor failed. | 57- |
| 58 | Output voltage is too low. | 58- |
| 59 | PV voltage is over limitation. | 59- |
| 60 ▲ | If battery status is not allowed to charge and discharge after the communication between the inverter and battery is successful, it will show code 60 to stop charging and discharging the battery. | |
| 61 ▲ | Communication lost. After battery is connected, the communication signal is not detected for 3 minutes, the buzzer will beep. After 10 minutes, the inverter will stop charging and discharging to the lithium battery. Communication lost occurs after the inverter and battery are connected successfully, the buzzer beeps immediately. | |
| 69 ▲ | If battery status is not allowed to charge after the communication between the inverter and battery is successful, it will show code 69 to stop charging the battery. | |
| 70 ▲ | If battery status must charge after the communication between the inverter and battery is successful, it will show code 70 to charge the battery. | |
| 71 ▲ | If battery status is not allowed to discharge after the communication between the inverter and battery is successful, it will show code 71 to stop discharge battery. | |
| 71 | Firmware version inconsistent | 71- |
| 72 | Current sharing fault | 72- |
| 80 | CAN fault | 80- |
| 81 | Host loss | 81- |
| 82 | Synchronization loss | 82- |
| 83 | Battery voltage detected different | 83- |
| 84 | AC input voltage and frequency detected different | 84- |
| 85 | AC output current unbalance | 85- |
| 86 | AC output mode setting is different | 86- |
What are the warning descriptions and their icons?
Alarm: The red LED flashes, and the LCD displays an alarm code; the inverter does not enter the failure mode.
Warning Indicator:
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 02 | Over temperature | None | 02 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| 16 | High AC input (>280VAC) during BUS soft start | None | 16 |
| EQ | Battery equalization | None | EQ |
| BP | Battery is not connected | None | BP |
How do I troubleshoot common problems with the solar inverter?
| Problem | LCD/LEDs/Buzzer | Explanation/Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. |
1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UP–>appliance) |
| Green LED is flashing. | Set “Solar First” as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 105% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 07 If PV input voltage is higher than specification, the output power will be derated. At this time, if the connected load is higher than derated output power, it will cause overload. |
Reduce the number of PV modules in series or the connected load. | ||
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Internal temperature of inverter component is over 100°C Battery is over-charged The battery voltage is too high. |
Return to repair center. Check if the specification and quantity of batteries meet requirements. |
|
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. |
|
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. | ||
| Fault code 59 | PV input voltage is beyond the specification. | Reduce the number of PV modules in series. |
How do I mount units for parallel operation?
When installing multiple units, follow the chart provided in the PDF. For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit. Ensure each unit is installed at the same level.
How do I perform wiring connection for parallel operation?
It is requested to connect to the battery for parallel operation. The cable size of each inverter is shown below:
| Rated Capacity | Wire Size | Cable mm² | Ring Terminal Dimensions D (mm) | Ring Terminal Dimensions L (mm) | Torque value |
|---|---|---|---|---|---|
| 3KW | 1*4AWG | 22 | 6.4 | 33.2 | 2~3Nm |
| 3.6KW | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm |
| 5KW | 1*2AWG | 38 | 6.4 | 33.2 | 2~3Nm |
| 5.5KW | 1*2AWG | 38 | 6.4 | 39.2 | 2~3Nm |
| 6.2KW | 1*2AWG | 38 | 8.4 | 39.2 | 2~3Nm |
| 8KW | 1*2/0AWG | 67.4 | 8.4 | 51 | 5Nm |
| 11KW | 1*3/0AWG | 85 | 8.4 | 54 | 5Nm |
Be sure the length of all battery cables is the same. Otherwise, there will be a voltage difference between the inverter and battery, causing parallel inverters not to work.
Do not connect the current sharing cable between inverters which are in different phases. Otherwise, it may damage the inverters.
Each inverter should connect to PV modules separately.
How do I commission the inverters for parallel operation in single phase?
Step 1: Check the following requirements before commissioning:
Correct wire connection
Ensure all breakers in Line wires of load side are open and each Neutral wire of each unit is connected together.
Step 2: Turn on each unit and set “PAL” in LCD setting program 4 of each unit. Then shut down all units.
Note: It is necessary to turn off the switch when setting the LCD program. Otherwise, the setting cannot be programmed.
Step 3: Turn on each unit.
Master and slave units are randomly defined.
CLICK HERE TO DOWNLOAD PHOTON PI-PLUS 3.6K (01) PDF MANUAL
