FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF USER GUIDE
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF USER MANUAL
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF OWNER GUIDE
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF OWNER MANUAL
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF REFERENCE GUIDE
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF REFERENCE MANUAL
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH PHOTON PI-PLUS 6.2K (01) PDF OPERATING INSTRUCTIONS
CLICK HERE TO DOWNLOAD PHOTON PI-PLUS 6.2K (01) PDF MANUAL
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the important safety instructions for this unit?
This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
Before using the unit read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
Only qualified personnel can install this device with battery.
NEVER charge a frozen battery.
For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.
Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
One piece of 150A fuse is provided as over-current protection for the battery supply.
GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounder wiring system. Be sure to comply with local requirements and regulation to install this inverter.
NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
What items are included in the package upon unpacking and inspection?
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
The unit x 1
User manual 1
How should the unit be prepared for connection?
Before connecting all please take off bottom cover by removing two screws as shown below.
How should the unit be mounted?
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction materials.
Mount on a solid surface.
Install this inverter at eye level in order to allow the LCD display to be read at all times.
For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
The ambient temperature should be between and to ensure optimal operation.
The recommended installation position is to be adhered to the wall vertically.
Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws.
1,2 Use the M6*80mm expansion bolts.
3 Use M4 or M5.
What precautions and steps are required for battery connection?
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it’s still requested to over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
| Rated Capacity | Typical Amperage | Battery capacity | Wire Size | Ring Terminal Dimensions | Torque value | ||
|---|---|---|---|---|---|---|---|
| Cable(mm²) | D(mm) | L(mm) | |||||
| 2KVA | 88A | 100AH | 1*6AWG | 14 | 6.4 | 33.2 | 2~3 Nm |
| 2*10AWG | 6 | 6.4 | 23.8 | ||||
| 3KVA | 132A | 100AH | 1*4AWG | 22 | 6.4 | 33.2 | 2~3 Nm |
| 200AH | 2*8AWG | 9 | 6.4 | 29.2 | |||
| 3.6KVA | 165A | 200AH | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm |
| 5KVA | 109A | 200AH | 1*2AWG | 38 | 6.4 | 39.2 | 2~3 Nm |
| 2*6AWG | 28 | 6.4 | 33.2 | ||||
| 5.5KVA | 121A | 200AH | 1*2AWG | 34 | 6.4 | 39.2 | 2~3 Nm |
| 2*6AWG | 14 | 6.4 | 33.2 | ||||
| 6.2KVA | 124A | 200AH | 1*2AWG | 38 | 8.4 | 39.2 | 5Nm |
| 2*4AWG | 25 | 8.4 | 33.2 | ||||
| 8KVA | 183.2A | 250AH | 1*2/0AWG | 67.4 | 8.4 | 51 | 5Nm |
| 11KVA | 228A | 250AH | 1*3/0AWG | 85 | 8.4 | 54 | 5Nm |
Please follow below steps to implement battery connection:
1. Assemble battery ring terminal based on recommended battery cable and terminal size.
2. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver
WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative( – ) must be connected to negative (-).
What are the precautions and steps for AC input/output connection?
CAUTION!! Before connecting to AC input power source, please Install a separate AC breaker between inverter and AC input power source. This will ensure the Inverter can be disconnected during maintenance and fully protected from over current of AC input. The recommended spec of breaker is 32A for 24V system and 63A for 48V system.
CAUTION!! There are two terminal blocks with ” IN ” and ” OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
| Rated Capacity | Gauge | Torque value |
|---|---|---|
| 2KVA | 14AWG | 08~1.0Nm |
| 3KVA | 12AWG | 1.2~1.6Nm |
| 3.6KVA | 12AWG | 1.2~1.6Nm |
| 5KVA | 10AWG | 1.4~1.6Nm |
| 5.5KVA | 10AWG | 1.4~1.6Nm |
| 6.2KVA | 10AWG | 1.4~1.6Nm |
| 8KVA | 8AWG | 1.4~1.6Nm |
| 11KVA | 8AWG | 1.4~1.6Nm |
Please follow below steps to implement AC input/output connection
1. Before making AC input/output connection be sure to open DC protector or disconnector first.
2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N3 mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (ground) first.
Ground (yellow-green)
LINE (brown or black)
Neutral (blue)
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4. Make sure the wires are securely connected
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this inverter/ charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
What are the precautions and guidelines for PV Connection (Solar Charger Models Only)?
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Recommended PV cable size:
| Typical Amperage | Gauge | Torque Value |
|---|---|---|
| 30A | 12AWG | 1.4~1.6Nm |
PV module selection:
When choosing the right PV module, be sure to first consider the following requirements:
The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter. The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.
How should PV module wires be connected?
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
3. Fix wire cover to the inverter with supplied screws as shown in below chart.
4. Check correct polarity of wire from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Screw two wires tightly in clockwise direction. Recommended tool: 4mm blade screwdriver.
How is the final assembly performed after wiring?
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
How do I power the unit On/Off?
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.
What are the steps to start up the inverter?
Connect the battery that meets the requirements (battery voltage needs to beyond 23V) or AC (AC needs to confirm the suitable input range depend on the output mode), then you can start up the inverter.
Mains power on
Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode that represents turn on the machine successfully, then will enter the AC mode.
Battery boot
Connect to battery, press the power-on button to establish a working power source.
The system will automatically turn on, after waiting for a period of time, the panel will display battery mode that represents turn on the machine successfully, then will enter the battery mode.
How do I shut down the system?
When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.
How do I use the operation and display panel?
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
Function Keys
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
LED Indicator
| LED Indicator | Messages |
|---|---|
| AC/INV (Green) | Solid On: Output is powered by utility in Line mode. |
| AC/INV (Green) | Flashing: Output is powered by battery or PV in battery mode. |
| CHG (Green) | Solid On: Battery is fully charged. |
| CHG (Green) | Flashing: Battery is charging. |
| FAULT (Red) | Solid On: Fault occurs in the inverter. |
| FAULT (Red) | Flashing: Warning condition occurs in the inverter. |
LCD Display Icons
| Icon | Function description |
|---|---|
| Input Source Information | |
| AC | Indicates the AC input. |
| PV | Indicates the PV input. |
| INPUTBATT | Indicate input voltage, input frequency, PV voltage, charger current, charger power, battery voltage. |
| Configuration Program and Fault Information | |
| (88) | Indicates the setting programs. |
| (88 with triangle) | Indicates the warning and fault codes. |
| (88 with A and triangle) | Warning: flashing with warning code |
| (88 with ERROR) | Fault: lighting with fault code |
| Output Information | |
| OUTPUTBATTLOAD | Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. |
| Battery Information | |
| CHARGING | Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode. |
How do I interpret the battery charging status in AC mode?
| Status | Battery voltage | LCD Display |
|---|---|---|
| Constant Current mode/ Constant Voltage mode | <2V/cell | 4 bars will flash in turns. |
| Constant Current mode/ Constant Voltage mode | 2~2.083V/cell | Bottom bar will be on and the other three bars will flash in turns. |
| Constant Current mode/ Constant Voltage mode | 2.083~2.167V/cell | Bottom two bars will be on and the other two bars will flash in turns. |
| Constant Current mode/ Constant Voltage mode | > 2.167 V/cel | Bottom three bars will be on and the top bar will flash. |
| Floating mode. Batteries are fully charged. | 4 bars will be on. |
How do I interpret the battery capacity in battery mode?
| Load Percentage | Battery Voltage | LCD Display |
|---|---|---|
| Load>50% | <1.85V/cell | (Empty battery icon) |
| Load>50% | 1.85V/cell~1.933V/cell | (1 bar on battery icon) |
| Load>50% | 1.933V/cell~2.017V/cell | (2 bars on battery icon) |
| Load>50% | >2.017V/cell | (3 bars on battery icon) |
| Load<50% | <1.892V/cell | (Empty battery icon) |
| Load<50% | 1.892V/cell~1.975V/cell | (1 bar on battery icon) |
| Load<50% | 1.975V/cell~2.058V/cell | (2 bars on battery icon) |
| Load<50% | >2.058V/cell | (3 bars on battery icon) |
How do I interpret the load level information?
| Load Level | ||||
|---|---|---|---|---|
| Indicates overload. | ||||
| Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%. | 0%~24% | 25%~49% | 50%~74% | 75%~100% |
How do I interpret the Mode Operation Information on the LCD?
| Operation mode | Description | LCD display |
|---|---|---|
| Standby mode | No output is supplied by the unit but it still can charge batteries. | Charging by utility and PV energy. |
| Charging by utility | ||
| Charging by PV energy. | ||
| No charging. | ||
| Fault mode | Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on. | Charging by utility and PV energy. |
| PV energy and utility can charge batteries. | Charging by utility | |
| Charging by PV energy. | ||
| No charging. | ||
| Line Mode | The unit will provide output power from the mains. It will also charge the battery at line mode. | Charging by utility and PV energy. |
| Charging by utility. | ||
| Battery Mode | The unit will provide output power from battery and PV power. | |
| Battery free mode | The device will provide output power from the PV power supply. |
How do I mute the unit alarm?
| Mute Operation |
|---|
| Indicates unit alarm is disabled. |
How do I set the LCD display information?
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order input voltage, input frequency, PV voltage, charging current, charging power battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.
| Selectable information | LCD display |
|---|---|
| Input voltage / Output voltage (Default Display Screen) | Input Voltage=230V, output voltage=230V |
| Input frequency | Input frequency =50Hz |
| PV voltage | PV voltage=260V |
| PV current | PV current = 2.5A |
| PV power | PV power = 500W |
| AC and PV charging current | AC and PV charging current=50A |
| PV charging current | PV charging current=50A |
| AC charging current | AC charging current=50A |
| AC and PV charging power | AC and PV charging power=500W |
| PV charging power | PV charging power=500W |
| AC charging power | AC charging power=500W |
| Battery voltage and output voltage | Battery voltage =25.5V, output voltage 230V |
| Output frequency | Output frequency=50Hz |
| Load percentage | Load percent=70% |
| Load in VA | When connected load is lower than 1kVA, load in VA will present xxxVA like below chart. |
| Load in VA | When load is larger than 1kVA (>=1KVA), load in VA will present x.xkVA like below chart. |
| Load in Watt | When load is lower than 1kW, load in W will present xxxW like below chart. |
| Load in Watt | When load is larger than 1kW (>=1KW), load in W will present x.xkW like below chart. |
| Battery voltage / DC discharging current | Battery voltage = 25.5V, discharging current = 1A |
| Main CPU version checking | Main CPU version 00014.04 |
| Setting BMS communication success display | The left side shows the lithium battery temperature and the right side shows the lithium battery capacity. |
| Setting BMS communication success display | The input current of the lithium battery is displayed on the left side, and the output current of the lithium battery is displayed on the right side. |
What are the warning descriptions for the unit?
Alarm: The red LED flashes, and the LCD displays an alarm code, the inverter does not enter the failure mode.
Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | (icon of fan) |
| 02 | Over temperature | None | (icon of thermometer) |
| 03 | Battery is over-charged | Beep once every second | (icon of battery charging) |
| 04 | Low battery | Beep once every second | (icon of low battery) |
| 07 | Overload | Beep once every 0.5 second | (icon of overload) |
| 10 | Output power derating | Beep twice every 3 seconds | (icon of power derating) |
| 15 | PV energy is low. | Beep twice every 3 seconds | (icon of PV panel) |
| 16 | High AC input (>280VAC) during BUS soft start | None | (icon of AC input) |
| 49 | Battery equalization | None | (icon of battery equalization) |
| 6P | Battery is not connected | None | (icon of battery not connected) |
What do the fault codes indicate and how do I troubleshoot them?
Fault: The inverter enters the fault mode, the red LED light is always on and the LCD displays the fault code.
Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | (fan icon) |
| 02 | Over temperature or NTC is not connected well. | (thermometer icon) |
| 03 | Battery voltage is too high. | (battery voltage icon) |
| 04 | Battery voltage is too low. | (low battery icon) |
| 05 | Output short circuited or over temperature is detected by internal converter components. | (output circuit icon) |
| 06 | Output voltage is too high. | (output voltage icon) |
| 07 | Over load time out. | (overload icon) |
| 08 | Bus voltage is too high | (bus voltage icon) |
| 09 | Bus soft start failed | (bus soft start icon) |
| 51 | Over currents or surge | (over current icon) |
| 52 | Bus voltage is too low | (low bus voltage icon) |
| 53 | Inverter soft start failed | (inverter soft start icon) |
| 55 | Over DC voltage in AC output | (DC voltage in AC output icon) |
| 57 | Current sensor failed | (current sensor icon) |
| 58 | Output voltage is too low | (low output voltage icon) |
| 59 | PV voltage is over limitation | (PV voltage icon) |
Fault Code Display and Troubleshooting:
| Problem | LCD/LED/Buzzer | Explanation/Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication | 1. The battery voltage is far too low.(<1.4V/Cell) 2. Internal fuse tripped. |
1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UP–>appliance) |
| Green LED is flashing. | Set “Solar First” as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 105% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 07 | If PV input voltage is higher than specification, the output power will be derated. At this time, if connected loads is higher than derated output power, it will cause overload. | Reduce the number of PV modules in series or the connected load. | |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Internal temperature of inverter component is over 100°C | Return to repair center. | |
| Fault code 03 | Battery is over-charged | Check if spec and quantity of batteries are meet requirements. | |
| Fault code 03 | The battery voltage is too high. | ||
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. |
|
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. | ||
| Fault code 59 | PV input voltage is beyond the specification. | Reduce the number of PV modules in series. |
What are the code references for communication issues?
Related information code will be displayed on LCD screen. Please check inverter LCD screen for the operation.
| Code | Description |
|---|---|
| 60 | If battery status is not allowed to charge and discharge after the communication between the inverter and battery is successful, it will show code 60 to stop charging and discharging battery. |
| 61 | Communication lost After battery is connected, communication signal is not detected for 3 minutes, buzzer will beep. After 10 minutes, inverter will stop charging and discharging to lithium battery. Communication lost occurs after the inverter and battery is connected successfully, buzzer beeps immediately. |
| 69 | If battery status is not allowed to charge after the communication between the inverter and battery is successful, it will show code 69 to stop charging battery. |
| 70 | If battery status must to charge after the communication between the inverter and battery is successful, it will show code 70 to charge battery. |
| 71 | If battery status is not allowed to discharge after the communication between the inverter and battery is successful, it will show code 71 to stop discharge battery. |
How do I apply the battery equalization function?
You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:
1. Setting equalization interval in program 35.
2. Active equalization immediately in program 36.
When to Equalize
In stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
Equalize charging time and timeout
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
How do I mount the unit for parallel operation?
When installing multiple units, please follow below chart.
NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx.50 cm above and below the unit. Be sure to install each unit in the same level.
How do I wire the units for parallel operation?
NOTICE: It’s requested to connect to battery for parallel operation.
The cable size of each inverter is shown below:
Recommended battery cable and terminal size for each inverter:
| Rated Capacity | Wire Size | Ring Terminal Dimensions | Torque value | ||
|---|---|---|---|---|---|
| Cable mm² | D (mm) | L (mm) | |||
| 3KW | 1*4AWG | 22 | 6.4 | 33.2 | 2~3Nm |
| 3.6KW | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm |
| 5KW | 1*2AWG | 38 | 6.4 | 33.2 | 2~3Nm |
| 5.5KW | 1*2AWG | 38 | 6.4 | 39.2 | 2~3Nm |
| 6.2KW | 1*2AWG | 38 | 8.4 | 39.2 | 2~3Nm |
| 8KW | 1*2/0AWG | 67.4 | 8.4 | 51 | 5Nm |
| 11KW | 1*3/0AWG | 85 | 8.4 | 54 | 5Nm |
WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between inverter and battery to cause parallel inverters not working.
What are the LCD setting options for parallel operation?
Setting Program:
| Program | Description | Selectable option |
|---|---|---|
| 04 | AC output mode This setting is only available when the inverter is in standby mode (Switch off). |
Single: 04 516 When the units are used in parallel with single phase, please select “PAL” in program 4. |
| Parallel: 04 PAL It is required to have at least 3 inverters or maximum 9 inverters to support three-phase equipment. It’s required to have at least one inverter in each phase or it’s up to four inverters in one phase please-2 for detailed information. Please select “3P1” in program 4 for the inverters connected to phase, “3P2” in program 4 for the inverters connected to L2 phase and “3P3” in program 4 for the inverters connected to L3 phase. |
||
| L1 phase: 04 391 Be sure to connect share current cable to units which are on the same phase. Do NOT connect share current cable between units on different phases. |
||
| L2 phase: 04 392 Besides, power saving function will be automatically disabled. |
||
| L3 phase: 04 393 |
How do I commission parallel units in single phase?
Step 1: Check the following requirements before commissioning:
Correct wire connection
Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are connected together.
Step 2:
Turn on each unit and set “PAL” in LCD setting program 4 of each unit. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be programmed.
Step 3: Turn on each unit.
NOTE: Master and slave units are randomly defined.
CLICK HERE TO DOWNLOAD PHOTON PI-PLUS 6.2K (01) PDF MANUAL
