PHOTON PI-PLUS 11K (01) Image

FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF USER GUIDE
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF USER MANUAL
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF OWNER GUIDE
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF OWNER MANUAL
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF REFERENCE GUIDE
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF REFERENCE MANUAL
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH PHOTON PI-PLUS 11K (01) PDF OPERATING INSTRUCTIONS


CLICK HERE TO DOWNLOAD PHOTON PI-PLUS 11K (01) PDF MANUAL

If this is not the document you want for this product, click here to see if we have any other documents for this product.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What is the purpose of this manual?

This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep manual for future reference.


What is the scope of this manual?

This manual provides safety and installation guidelines as well as information on tools and wiring.


What are the general safety instructions for using the unit?

Before using the unit read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.

To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.

Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.

To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.

Only qualified personnel can install this device with battery.

NEVER charge a frozen battery.

For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.

Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.

Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.

One piece of 150A fuse is provided as over-current protection for the battery supply.

This inverter/charger should be connected to a permanent grounder wiring system. Be sure to comply with local requirements and regulation to install this inverter.

NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.

Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.


What is included in the package upon unpacking?

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

  • The unit x 1

  • User manual 1


How do I prepare the unit for connection?

Before connecting all please take off bottom cover by removing two screws as shown below.


Where should I mount the unit?

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.

  • Mount on a solid surface.

  • Install this inverter at eye level in order to allow the LCD display to be read at all times.

  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.

  • The ambient temperature should be between and to ensure optimal operation.

  • The recommended installation position is to be adhered to the wall vertically.

  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing three screws.

  • 1,2 Use the M6*80mm expansion bolts.

  • 3 Use M4 or M5.


How should I connect the battery to the inverter?

For safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it’s still requested to over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

All wiring must be performed by be qualified personnel.

It’s very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

Rated Capacity Typical Amperage Battery capacity Wire Size Ring Terminal Cable(mm²) Dimensions D(mm) Dimensions L(mm) Torque value
2KVA 88A 100AH 1*6AWG 14 6.4 33.2 2~3 Nm
2*10AWG 6 6.4 23.8
3KVA 132A 100AH 1*4AWG 22 6.4 33.2 2~3 Nm
200AH 2*8AWG 9 6.4 29.2
3.6KVA 165A 200AH 2*4AWG 25 8.4 33.2 5Nm
5KVA 109A 200AH 1*2AWG 38 6.4 39.2 2~3 Nm
2*6AWG 28 6.4 33.2
5.5KVA 121A 200AH 1*2AWG 34 6.4 39.2 2~3 Nm
2*6AWG 14 6.4 33.2
6.2KVA 124A 200AH 1*2AWG 38 8.4 39.2 5Nm
2*4AWG 25 8.4 33.2
8KVA 183.2A 250AH 1*2/0AWG 67.4 8.4 51 5Nm
11KVA 228A 250AH 1*3/0AWG 85 8.4 54 5Nm

Please follow below steps to implement battery connection:

1. Assemble battery ring terminal based on recommended battery cable and terminal size.

2. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

Installation must be performed with care due to high battery voltage in series.

Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).


How do I connect the AC input/output?

Before connecting to AC input power source, please Install a separate AC breaker between inverter and AC input power source. This will ensure the Inverter can be disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of breaker is 32A for 24V system and 63A for 48V system.

There are two terminal blocks with ” IN ” and ” OUT” markings. Please do NOT mis-connect input and output connectors.

All wiring must be performed by qualified personnel.

It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Rated Capacity Gauge Torque value
2KVA 14AWG 08~1.0Nm
3KVA 12AWG 1.2~1.6Nm
3.6KVA 12AWG 1.2~1.6Nm
5KVA 10AWG 1.4~1.6Nm
5.5KVA 10AWG 1.4~1.6Nm
6.2KVA 10AWG 1.4~1.6Nm
8KVA 8AWG 1.4~1.6Nm
11KVA 8AWG 1.4~1.6Nm

Please follow below steps to implement AC input/output connection

1. Before making AC input/output connection be sure to open DC protector or disconnector first.

2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N3 mm.

3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (ground) first.

  • Ground (yellow-green)

  • L-LINE (brown or black)

  • N-Neutral (blue)

Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

4. Make sure the wires are securely connected.

Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.


How do I connect the PV modules (Only apply for the model with solar charger)?

Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

All wiring must be performed by a qualified personnel.

It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Typical Amperage Gauge Torque Value
30A 12AWG 1.4~1.6Nm

When choosing the right PV module, be sure to first consider the following requirements:

The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter. The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.

Model Pi-Plus 3.6k Pi-Plus 6.2k Pi-Plus 11k
PV Charging Mode MPPT MPPT MPPT Dual MPPT
MAX.PV Input Power 5000W 6200W 2*5500W
MPPT Tracking Range Vdc 60~500 Vdc 60~500 Vdc 90~500 Vdc
Best voltage 300~400V 300~400V 300~400V
MAX.PV Input Voltage 500Vdc 500Vdc 500Vdc
MAX.PV Charging Current 120A 120A 150A
MAX.AC Charging Current 100A 100A 150A
MAX.Charging Current 120A 120A 150A

Please follow below steps to implement PV module connection:

1. Remove insulation sleeve 10 mm for positive and negative conductors.

2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.

3. Fix wire cover to the inverter with supplied screws as shown in below chart.

4. Check correct polarity of wire from PV modules and PV input connectors. Then, connect positive pole(+) of connection wire to positive pole(+) of PV input connector. Connect negative pole (-)of connection wire to negative pole(-) of PV input connector. Screw two wires tightly in clockwise direction. Recommended tool: 4mm blade screwdriver.


What is the recommended battery capacity for parallel inverters?

Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.

Inverter parallel numbers 2 3 4 5 6 7 8 9
Battery Capacity for 3KW 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
Battery Capacity for 3.6KW 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
Battery Capacity for 5KW 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
Battery Capacity for 5.5KW 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
Battery Capacity for 6.2KW 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
Battery Capacity for 8KW 400AH 600AH 800AH 1000AH 1200AH \ \ \
Battery Capacity for 11KW 500AH 750AH 1000AH 1250AH 1500AH \ \ \

How do I perform final assembly of the unit?

After connecting all wirings, please put bottom cover back by screwing two screws as shown below.


How do I power ON/OFF the unit?

Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.


What are the steps to start up the inverter?

Connect the battery that meets the requirements (battery voltage needs to beyond 23V) or AC (AC needs to confirm the suitable input range depend on the output mode), then you can start up the inverter.

Mains power on:

Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode that represents turn on the machine successfully, then will enter the AC mode.

Battery boot:

Connect to battery, press the power-on button to establish a working power source.

The system will automatically turn on, after waiting for a period of time, the panel will display battery mode that represents turn on the machine successfully, then will enter the battery mode.


How do I shut down the system?

When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.


What are the recommended AC input and output cable sizes for each inverter?

Rated Capacity AWG no. Torque
3KW 12AWG 1.2~1.6Nm
3.6KW 12AWG 1.2~1.6Nm
5KW 10AWG 1.2~1.6Nm
5.5KW 10AWG 1.2~1.6Nm
6.2KW 10AWG 1.2~1.6Nm
8KW 8AWG 1.4~1.6Nm
11KW 8AWG 1.4~1.6Nm

You need to connect the cables of each inverter together. Take the battery cables for example: You need to use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery terminal. The cable size used from joint to battery should be X times cable size in the tables above. X indicates the number of inverters connected in parallel.

Regarding AC input and output, please also follow the same principle.

Make sure all output N wires of each inverter must be connected all the time. Otherwise, it will cause inverter fault in error code #72.

Please install the breaker at the battery and AC input side. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of battery or AC input. The recommended mounted location of the breakers is shown in the figures in 5-1 and 5-2.


What are the recommended breaker specifications for the battery for each inverter?

Rated Capacity 1 unit* Rated Capacity 1 unit*
3KW 150A/70VDC 6.2KW 150A/70VDC
3.6KW 200A/70VDC 8KW 300A/70VDC
5KW 150A/70VDC 11KW 300A/70VDC
5.5KW 150A/70VDC

*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.


What are the recommended breaker specifications for AC input with single phase?

Rated Capacity 2 units 3 units 4 units 5 units 6 units 7 units 8 units 9 units
3KW 80A/230VAC 120A/230VAC 160A/230VAC 200A/230VAC 240A/230VAC 280A/230VAC 320A/230VAC 360A/230VAC
3.6KW 80A/230VAC 120A/230VAC 160A/230VAC 200A/230VAC 240A/230VAC 280A/230VAC 320A/230VAC 360A/230VAC
5KW 80A/230VAC 120A/230VAC 160A/230VAC 200A/230VAC 240A/230VAC 280A/230VAC 320A/230VAC 360A/230VAC
5.5KW 80A/230VAC 120A/230VAC 160A/230VAC 200A/230VAC 240A/230VAC 280A/230VAC 320A/230VAC 360A/230VAC
6.2KW 80A/230VAC 120A/230VAC 160A/230VAC 200A/230VAC 240A/230VAC 280A/230VAC 320A/230VAC 360A/230VAC
8KW 120A/230VAC 180A/230VAC 240A/230VAC 300A/230VAC 360A/230VAC / / /
11KW 120A/230VAC 180A/230VAC 240A/230VAC 300A/230VAC 360A/230VAC / / /

Note 1: Also, a circuit breaker should be installed at the AC input of each inverter, and the selection of the circuit breaker should refer to the AC input current of the machine nameplate.

Note 2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units.


What information is displayed on the LCD screen?

Icon Function description
AC Indicates the AC input.
PV Indicates the PV input.
INPUTBATT Indicate input voltage, input frequency, PV voltage, charger current, charger power, battery voltage.
88 Indicates the setting programs.
88 Indicates the warning and fault codes.
A (Warning) flashing with warning code
ERROR (Fault) lighting with fault code
OUTPUTBATTLOAD Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
CHARGING Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode.

How do I navigate the LCD setting menus?

After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button exit.

Program Description Selectable option
00 Exit setting mode Escape
01 Output source priority: To configure load power source priority Utility first (default): Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
Solar first: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time.
BU priority: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
02 Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) 60A (default)
Setting range is from 10A to maximum charging current. Increment of each click is 10A.
03 AC input voltage range Appliances (default): If selected, acceptable AC input voltage range will be within 90-280VAC.
UPS: If selected, acceptable AC input voltage range will be within 170-280VAC.
05 Battery type AGM (default)
User-Defined: If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
Flooded
06 Auto restart when overload occurs Restart disable (default)
Restart enable
07 Auto restart when over temperature occurs Restart disable (default)
Restart enable
08 ECO function: System will temporarily stop when the load is low in battery mode. disable (default)
enable
09 Output frequency 50Hz (default)
60Hz
10 Output voltage 220V
230V (default)
240V
11 Maximum utility charging current 30A (default)
Setting range is 2A, then from 10A to max.AC charging current. Increment of each click is 10A.
12 Setting voltage point back to utility source when selecting “SBU priority” in program 01. Available options in 24 system model: 23.0V (default)
Setting range is from 22V to 25.5V. Increment of each click is 0.5V.
Available options in 48 system model: 46V (default)
Setting range is from 44V to 51V. Increment of each click is 1V.
13 Setting voltage point back to battery mode when selecting “SBU priority” in program 01. Available options in 24 system model: Battery fully charged 27V (default)
Setting range is from 24V to 29V. Increment of each click is 0.5V.
16 Charger source priority: To configure charger source priority Utility first: Utility will charge battery as first priority. Solar energy will charge battery only when utility power is not available.
Solar first: Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
Solar and Utility (default): Solar energy and utility will charge battery at the same time.
Only Solar: Solar energy will be the only charger source no matter utility is available or not.
18 Alarm control Alarm on (default)
Alarm off
19 Auto return to default display screen Return to default display screen (default): If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage/output voltage) after no button is pressed for 1 minute.
Stay at latest screen: If selected, the display screen will stay at latest screen user finally switches.
20 Backlight control Backlight on (default)
Backlight off
22 Beeps while primary source is interrupted Alarm on (default)
Alarm off
23 Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. Bypass disable (default)
Bypass enable
25 Record Fault code Record enable (default)
Record disable
26 Bulk charging voltage (C.V voltage) 24V system default setting: 28.2V
48V system default setting: 56.4V
If self-defined is selected in program 5, this program can be set up. Setting range is from 25.0V to 31.5V for 24V system model and 48.0V to 61.0V for 48V system model. Increment of each click is 0.1V.
27 Floating charging voltage 24V system default setting: 27.0V
48V system default setting: 54.0V
default:
28 Reset factory setting 48V system default setting: 54.0V
default:
29 Low DC cut-off voltage: If battery power is only power source available inverter will shut down. If PV energy and battery power are available, inverter will charge battery without AC output. 24V system default setting: 21.0V
If self-defined is selected in program 5, this program can be set up. Setting range is from 21. 0V to 24. 0V for 24V system model and 42.0V to 48.0V for 48V system model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
48V system default setting: 42.0V
30 Battery equalization Battery equalization disable (default)
If “Flooded” or “User Defined” is selected in program 05, this program can be set up.
31 Battery equalization voltage 24V system default setting: 29.2V
48V system default setting: 58.4V
Setting range is from 25.0V to 31.5V for 24V system mode and 48.0V to 61.0 V for 48V system model. Increment of each click is 0.1V.
33 Battery equalized time 60min (default): Setting range is from 5min to 900min. Increment of each click is 5min.
34 Battery equalized timeout 120min (default): Setting range is from 5min to 900min. Increment of each click is 5min.
35 Equalization interval 30days (default): Setting range is from 0 to 90 days. Increment of each click is 1 day.
36 Equalization activated immediately Enable
Disable (default)
If equalization function is enabled in program 30, this program can be set up. If “Enable” is selected in this program, it’s to activate battery equalization immediately and LCD main page will shows “EQ “. If “Disable” is selected, it will cancel equalization function until next activated equalization time arrives based on program 35 setting. At this time, “EQ” will not be shown in LCD main page.
37 BMS Function Switch off (default)
on
Whether to enable the BMS communication function
38 Bat Soc Under Lock BMS low voltage SOC value, if the BMS SOC value is lower than the set value, the inverter will shut down to protect the battery.
39 Bat Soc Turn To Ac When the working mode of the inverter is set to the battery priority mode, the inverter will be forced to enter the mains charging when the SOC of the BMS is lower than the set value.
40 Bat Soc Turn To Dc When the working mode of the inverter is set to the battery priority mode, the inverter resumes the DC working mode when the SOC of the BMS is higher than the set value.
41 Bat Restart Soc When the inverter is turned on, the SOC must be higher than the set value to work normally.
42 BMS communication protocol Choose RS485 communication protocol
45 Reset PV energy storage Not reset (default)
Reset
60 Dual output Disable (default)
Use
61 Enter the dual output functional voltage point Default setting: 44.0V
Default setting: 22.0V
If battery voltage lower than inverter setting, second output will be cutted of. Increment of each click is 0.1V.
62 Enter the dual output functional SOC point If BMS capacity lower than SOC setting, second output will be cutted of.

How do I apply the Equalization Function?

You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

1. Setting equalization interval in program 35.

2. Active equalization immediately in program 36.

When to Equalize:

In stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Equalize charging time and timeout:

In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.


What happens during commissioning in single phase parallel operation?

Step 1: Check the following requirements before commissioning:

  • Correct wire connection

  • Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are connected together.

Step 2: Turn on each unit and set “PAL” in LCD setting program 4 of each unit. And then shut down all units.

It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be programmed.

Step 3: Turn on each unit.

Master and slave units are randomly defined.



CLICK HERE TO DOWNLOAD PHOTON PI-PLUS 11K (01) PDF MANUAL


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.