Free English FIREYE MP562 (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.


CLICK HERE TO DOWNLOAD FIREYE MP562 (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

How is the FIREYE MP562 Programmer Module installed into the chassis?

The FIREYE MP562 Programmer Modules are used with the Fireye Modular M-Series II Chassis. To install the module, follow these steps:

1. Remove power from the control and remove the control from its wiring base before proceeding.

2. Grab hold of the programmer module by the ridged finger grips on the side of the module.

3. Align the module with the guide slots on the opening farthest from the transformer.

4. Insert the module into the pin connectors.

The programmer modules are designed to fit in the proper slot only. DO NOT FORCE THEM.


What features and operational characteristics are associated with the FIREYE MP562?

The FIREYE MP562 is equipped with a series of dipswitches to select Purge Timing, Pilot Trial for Ignition (PTFI) Timing, and Recycle or Non-Recycle operation. It features LED indicator lights to indicate the operating status of the control.

Additionally, a “check-run” switch is provided on the FIREYE MP562 programmer module to assist in testing the size and stabilization of the pilot. Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module.


How do I replace the fuse on the FIREYE MP562?

The programmer modules are designed with a field-replaceable fuse located on the printed circuit board near the connectors. The fuse will open as a result of an overload condition on terminals 3, 4, or 5. To replace the fuse:

1. Remove the fuse using a small screwdriver.

2. For standard applications, install a Fireye replacement fuse (P/N 23-176) or equivalent 2AG, 8 amp fuse (e.g. Littlefuse #225008).

3. For programmers used with the MC230 and MC230R chassis, use replacement fuse P/N 23-183 or equivalent (3.5 amp, 2AG, SLO-BLO) Littlefuse #22903.5.


What are the specific operational descriptions for the FIREYE MP562 and other available modules?

Part Number DESCRIPTION
MP100/MP100E Relight operation.
MP101 Same as MP100, except will ignore flame signal in off cycle.
MP102/MP102E Operates like the MP100, except the standing pilot and relight features are eliminated. Ignition safety time is 5 seconds. Control will lockout on flame failure.
MP230 Selectable purge timing, trial-for-ignition timing, and recycle/non-recycle operation.
MP230H Selectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition. For use with two-stage burners.
MP560 Selectable purge timing, pilot-trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch.
MP561 Selectable purge timing, pilot-trial-for-ignition timing, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch.
MP562 Same as MP560, with lockout on loss of air flow. Non-recycle operation.

Note: Programmers with the suffix “E” (e.g. MP100E) are for use with the MC230 and MC230R chassis only.


What agency approvals does the FIREYE MP562 possess?

The following table outlines the agency approvals for the FIREYE MP562 and related modules:

  UL CSA FM EN298
MP100 Yes Yes Yes Yes
MP100E       Yes
MP101 Yes Yes Yes  
MP102       Yes
MP102E       Yes
MP230 Yes Yes Yes  
MP230H Yes Yes Yes  
MP560 Yes Yes Yes  
MP561 Yes Yes Yes  
MP562 Yes Yes Yes  

Approvals do not apply to MC230 and MC230R Chassis and associated programmers.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD FIREYE MP562 (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.