What is the function of the FIREYE MP560 Programmer Module?

The FIREYE MP560 Programmer Module is used with the Fireye Modular M-Series II control. The operational characteristics of the control are determined by the selection of the programmer module. This specific module incorporates a plug-in design for easy installation and is equipped with a series of dipswitches and a “check-run” switch.


How do I install the FIREYE MP560 Programmer Module into the chassis?

To install the module, follow these steps:

1. Remove power from the control and remove the control from its wiring base.

2. Grab hold of the programmer module by the ridged finger grips on the side of the module.

3. Align the module with the guide slots on the opening farthest from the transformer.

4. Insert the module into the pin connectors.

The programmer modules are designed to fit in the proper slot only. Do not force them.


What settings can be adjusted using the dipswitches on the FIREYE MP560?

The FIREYE MP560 is equipped with a series of dipswitches to select Purge Timing, Pilot Trial for Ignition (PTFI) Timing, and Recycle or Non-Recycle operation.


What is the purpose of the “check-run” switch on the FIREYE MP560?

A “check-run” switch is provided on the FIREYE MP560 programmer module to assist in testing size and stabilization of the pilot.


How can I identify the operating status of the FIREYE MP560?

LED indicator lights are on the programmer module, indicating the operating status of the control.


How is the Flame Failure Response Time (FFRT) determined for the FIREYE MP560 system?

Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module.


Where is the fuse located on the FIREYE MP560?

The fuse is located on the printed circuit board near the connectors.


What causes the fuse to open on the FIREYE MP560?

The fuse will open as a result of an overload condition on terminals 3, 4, or 5.


How do I replace the fuse on the FIREYE MP560 and what replacement part should I use?

To replace the fuse:

1. Remove the fuse using a small screwdriver.

2. Install the appropriate replacement fuse.

For standard applications, use a Fireye replacement fuse (P/N 23-176) or equivalent 2AG, 8 amp fuse (e.g., Littlefuse #225008).

In programmers used with the MC230 and MC230R chassis, use replacement fuse P/N 23-183 or equivalent (3.5 amp, 2AG, SLO-BLO) Littlefuse #22903.5.


What are the specific features of the FIREYE MP560 compared to other programmer modules?

Part Number Description
MP100/MP100E Relight operation.
MP101 Same as MP100, except will ignore flame signal in off cycle.
MP102/MP102E Operates like the MP100, except the standing pilot and relight features are eliminated. Ignition safety time is 5 seconds. Control will lockout on flame failure.
MP230 Selectable purge timing, trial-for-ignition timing, and recycle/non-recycle operation.
MP230H Selectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition. For use with two-stage burners.
MP560 Selectable purge timing, pilot-trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch.
MP561 Selectable purge timing, pilot-trial-for-ignition timing, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch.
MP562 Same as MP560, with lockout on loss of air flow. Non-recycle operation.

Note: Programmers with the suffix “E” (e.g. MP100E) are for use with the MC230 and MC230R chassis only.


What agency approvals does the FIREYE MP560 have?

UL CSA FM EN298