What are the operational characteristics of the FIREYE MP230H Programmer Module?

The FIREYE MP230H provides selectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. It features a 10-second main flame trial-for-ignition and is designed for use with two-stage burners.


How do I install the FIREYE MP230H into the chassis?

To install the module:

1. Grab hold of the programmer module by the ridged finger grips on the side of the module.

2. Align the module with the guide slots on the opening farthest from the transformer.

3. Insert the module into the pin connectors.

The programmer modules are designed to fit in the proper slot only. DO NOT FORCE THEM.


What chassis models are compatible with the FIREYE MP230H?

The Programmer Modules are used with the Fireye Modular M-Series II Chassis. Compatible part numbers include:

For 120VAC: MC120, MC120E, MC120P, MC120R, and MC120RE.

For 240VAC: MC230 and MC230R.


Does the FIREYE MP230H include configurable settings?

Yes, the FIREYE MP230H is equipped with a series of dipswitches to select Purge Timing, Pilot Trial for Ignition (PTFI) Timing, and Recycle or Non-Recycle operation.


How can I check the operating status of the FIREYE MP230H?

LED indicator lights are located on the programmer module to indicate the operating status of the control.


How is the Flame Failure Response Time (FFRT) determined for the FIREYE MP230H?

The Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module used in conjunction with the programmer.


Where is the fuse located on the FIREYE MP230H and why would it open?

The fuse is located on the printed circuit board near the connectors. It is designed to open as a result of an overload condition on terminals 3, 4, or 5.


How do I replace the fuse on the FIREYE MP230H?

In the event the fuse opens, follow these steps:

1. Remove the fuse using a small screwdriver.

2. Install a Fireye replacement fuse (P/N 23-176) or equivalent 2AG, 8 amp fuse (e.g. Littlefuse #225008).

Note: In programmers used with the MC230 and MC230R chassis, use replacement fuse P/N 23-183 or equivalent (3.5 amp, 2AG, SLO-BLO) Littlefuse #22903.5.


How can I measure the flame signal on the FIREYE MP230H system?

Test jacks are provided on the flame amplifier module to permit flame signal measurement during operation.


What agency approvals does the FIREYE MP230H possess?

Part Number UL CSA FM EN298
MP230H Yes Yes Yes

What safety warning should be observed before servicing the FIREYE MP230H?

Remove power from the control and remove the control from its wiring base before proceeding with installation or maintenance.