How do I install the FIREYE MP100E Programmer Module?
The FIREYE MP100E Programmer Modules are used with the Fireye modular M-Series II Chassis. To install the module:
1. Remove power from the control and remove the control from its wiring base before proceeding.
2. Grab hold of the programmer module by the ridged finger grips on the side of the module.
3. Align the module with the guide slots on the opening farthest from the transformer.
4. Insert the module into the pin connectors.
The programmer modules are designed to fit in the proper slot only. DO NOT FORCE THEM. Installation should not be considered complete until pilot turndown and other appropriate performance tests have been successfully completed.
How do I replace the fuse on the FIREYE MP100E?
The programmer modules are designed with a field-replaceable fuse located on the printed circuit board near the connectors. The fuse will open as a result of an overload condition on terminals 3, 4, or 5. To replace it:
1. Remove the fuse using a small screwdriver.
2. Install the correct replacement fuse.
For the FIREYE MP100E (which carries the “E” suffix indicating use with MC230 and MC230R chassis), use replacement fuse P/N 23-183 or equivalent (3.5 amp, 2AG, SLO-BLO) Littlefuse #22903.5.
What are the different programmer module selections and their descriptions?
| Part Number | DESCRIPTION |
|---|---|
| MP100/MP100E | Relight operation. |
| MP101 | Same as MP100, except will ignore flame signal in off cycle. |
| MP102/MP102E | Operates like the MP100, except the standing pilot and relight features are eliminated. Ignition safety time is 5 seconds. Control will lockout on flame failure. |
| MP230 | Selectable purge timing, trial-for-ignition timing, and recycle/non-recycle operation. |
| MP230H | Selectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition. For use with two-stage burners. |
| MP560 | Selectable purge timing, pilot-trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch. |
| MP561 | Selectable purge timing, pilot-trial-for-ignition timing, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch. |
| MP562 | Same as MP560, with lockout on loss of air flow. Non-recycle operation. |
Note: Programmers with the suffix “E” (e.g. FIREYE MP100E) are for use with the MC230 and MC230R chassis only.
What are the agency approvals for the FIREYE MP100E and other modules?
| Model | UL | CSA | FM | EN298 |
|---|---|---|---|---|
| MP100 | Approved | Approved | Approved | Approved |
| MP100E | Approved | |||
| MP101 | Approved | Approved | Approved | |
| MP102 | Approved | |||
| MP102E | Approved | |||
| MP230 | Approved | Approved | Approved | |
| MP230H | Approved | Approved | Approved | |
| MP560 | Approved | Approved | Approved | |
| MP561 | Approved | Approved | Approved | |
| MP562 | Approved | Approved | Approved |
Note: Approvals do not apply to MC230 and MC230R Chassis and associated programmers.
What is the description and operation of the FIREYE MP100E?
The FIREYE MP100E Programmer Module is used with the Fireye Modular M-Series II control. The operational characteristics are determined by the selection of the programmer module. The MP100E specifically provides “Relight operation” and is designed for use with the MC230 and MC230R chassis only.
The module incorporates a plug-in design for easy installation and features LED indicator lights to indicate the operating status of the control. Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module.