What are the general operational characteristics of the FIREYE MP100 and related programmer modules?
The FIREYE MP100, MP100E, MP101, MP102, MP102E, MP230, MP230H, MP560, MP561, and MP562 Programmer Modules are used with the Fireye Modular M-Series II control. The operational characteristics of the control are determined by the selection of the programmer module (e.g. re-ignition, 2-stage capability, pilot cutoff, etc.). The programmer module incorporates a plug-in design for easy installation.
Which FIREYE MP100 series modules feature dipswitches and what do they control?
Some programmer modules (MP230, MP230H, MP560, MP561, and MP562) are equipped with a series of dipswitches. These are used to select Purge Timing, Pilot Trial for Ignition (PTFI) Timing, and Recycle or Non-Recycle operation.
What is the function of the check-run switch on the FIREYE MP100 series modules?
A “check-run” switch is provided on the MP560, MP561, and MP562 programmer modules to assist in testing the size and stabilization of the pilot.
How is the Flame Failure Response Time (FFRT) determined for the FIREYE MP100 system?
Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module.
What are the available Programmer Module selections for the FIREYE MP100 series and their descriptions?
| Part Number | DESCRIPTION |
|---|---|
| MP100/MP100E | Relight operation. |
| MP101 | Same as MP100, except will ignore flame signal in off cycle. |
| MP102/MP102E | Operates like the MP100, except the standing pilot and relight features are eliminated. Ignition safety time is 5 seconds. Control will lockout on flame failure. |
| MP230 | Selectable purge timing, trial-for-ignition timing, and recycle/non-recycle operation. |
| MP230H | Selectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition. For use with two-stage burners. |
| MP560 | Selectable purge timing, pilot-trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch. |
| MP561 | Selectable purge timing, pilot-trial-for-ignition timing, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch. |
| MP562 | Same as MP560, with lockout on loss of air flow. Non-recycle operation. |
Note: Programmers with the suffix “E” (e.g. MP100E) are for use with the MC230 and MC230R chassis only.
How should the FIREYE MP100 Programmer Module be installed?
WARNING: Remove power from the control and remove the control from its wiring base before proceeding.
The Programmer Modules are installed in the chassis using the following steps:
1. Grab hold of the programmer module by the ridged finger grips on the side of the module.
2. Align the module with the guide slots on the opening farthest from the transformer.
3. Insert the module into the pin connectors.
The programmer modules are designed to fit in the proper slot only. DO NOT FORCE THEM.
How do I replace the fuse on the FIREYE MP100 Programmer Module?
The programmer modules are designed with a field-replaceable fuse located on the printed circuit board near the connectors. The fuse will open as a result of an overload condition on terminals 3, 4, or 5.
To replace the fuse:
1. Remove the fuse using a small screwdriver.
2. Install a Fireye replacement fuse (P/N 23-176) or equivalent 2AG, 8 amp fuse (e.g. Littlefuse #225008).
Note: In programmers used with the MC230 and MC230R, use replacement fuse P/N 23-183 or equivalent (3.5 amp, 2AG, SLO-BLO) Littlefuse #22903.5.
What are the agency approvals for the different FIREYE MP100 series models?
| Model | UL | CSA | FM | EN298 |
|---|---|---|---|---|
| MP100 | Yes | Yes | Yes | Yes |
| MP100E | Yes | |||
| MP101 | Yes | Yes | Yes | |
| MP102 | Yes | |||
| MP102E | Yes | |||
| MP230 | Yes | Yes | Yes | |
| MP230H | Yes | Yes | Yes | |
| MP560 | Yes | Yes | Yes | |
| MP561 | Yes | Yes | Yes | |
| MP562 | Yes | Yes | Yes |
Note: Approvals do not apply to MC230 and MC230R Chassis and associated programmers.