FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF DOCUMENT. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF USER GUIDE. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF USER MANUAL. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF OWNER GUIDE. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF OWNER MANUAL. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF REFERENCE GUIDE. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF INSTRUCTION GUIDE. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF REFERENCE MANUAL. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF INSTRUCTION MANUAL. FREE ENGLISH VERTIV POWERIT IMD-5M (01) PDF OPERATING INSTRUCTIONS.


CLICK HERE TO DOWNLOAD VERTIV POWERIT IMD-5M (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What are the general replacement guidelines for the Interchangeable Monitoring Device (IMD) on the VERTIV POWERIT IMD-5M?

The plastic carrier (IMD) portion of the PDU is designed to be field replaceable by qualified service personnel only. The IMD for the VERTIV POWERIT IMD-5M is designed to be replaced while the PDU is still connected to AC Mains power.

CAUTION: Observe proper precautions for handling electrostatic components.


What are the initial steps and precautions before removing the IMD module from the VERTIV POWERIT IMD-5M?

Before removing the old IMD module, please follow these important steps and precautions:

CAUTION: The IMD is still connected internally. Do not pull it more than 2 inches from the chassis.

NOTE: Be sure to have the new IMD module ready for installation immediately after the removal of the old IMD.

1. Remove the disposable ESD wrist strap from the package, remove the adhesive backing, and attach it to the PDU. Put the wrist strap on your arm so that it has contact with bare skin.


How do I remove the IMD-3E module from the VERTIV POWERIT IMD-5M PDU?

a. Insert the Vertiv IMD Removal Tool as shown. Be sure to press the tool in level, pressing in until the tool is flush with the face of the IMD. Some older versions may require overlays to be removed prior to inserting the tool.

b. Carefully pull the tool and IMD straight out about 2 inches. Remove the tool from the IMD.

c. Note the keyed position of the connector for installing the new IMD.


How do I remove the IMD-5M module from the VERTIV POWERIT IMD-5M PDU?

a. Press the removal tabs on the face of the IMD inward.

b. Carefully pull the IMD straight out about 2 inches.

c. Note the keyed position of the connector for installing the new IMD.


How do I install the new IMD-5M module on the VERTIV POWERIT IMD-5M?

IMPORTANT: Ensure you have the wrist strap on before proceeding.

1. Connect the cable to the replacement IMD-5M module. Ensure that the cable connector is inserted into the correct connector (8-pin or 10-pin) on the IMD board.

2. Tuck the excess cable back into the PDU and slide the IMD straight in. Press with both thumbs until the IMD snaps into place.