Free English PARKER HYPERCHILL ICE360 (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD PARKER HYPERCHILL ICE360 (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the key safety instructions for the PARKER HYPERCHILL ICE360?
Please adhere to the following safety instructions when operating the PARKER HYPERCHILL ICE360:
• Keep the user manual for the entire life of the machine and read it before any operation.
• Every unit is equipped with an electric disconnecting switch for operating in safe conditions. Always use this device to eliminate risks during maintenance.
• The manual is intended for the end-user only for operations performable with closed panels. Operations like installation, commissioning, or maintenance that require opening with tools must be carried out by skilled and qualified personnel.
• Do not exceed the design limits given on the dataplate.
• It is the user’s responsibility to avoid loads different from the internal static pressure. The unit must be appropriately protected whenever risks of seismic phenomena exist.
• Only use the unit for professional work and for its intended purpose.
• Tampering or replacement of any parts by unauthorized personnel and/or improper machine use will invalidate the warranty.
• The user is responsible for analyzing all application aspects and following all applicable industrial and safety standards.
What are the residual risks associated with the PARKER HYPERCHILL ICE360?
The risks that could not be eliminated in the design stage are listed in the table below. Installation, start up, stopping, and maintenance must be performed to avoid creating a hazardous situation.
| Part Affected | Residual Risk | Manner of Exposure | Precautions |
|---|---|---|---|
| Heat exchanger coil | Small cuts | Contact | Avoid contact, wear protective gloves |
| Fan grille and fan | Lesions | Insertion of pointed objects through the grille while the fan is in operation | Do not poke objects of any type through the fan grille or place any objects on the grille |
| Inside the unit: compressor and discharge pipe | Burns | Contact | Avoid contact, wear protective gloves |
| Inside the unit: metal parts and electrical wires | Intoxication, electrical shock, serious burn | Defects in the insulation of the power supply lines upstream of the electrical panel; live metal parts | Adequate electrical protection of the power supply line; ensure metal parts are properly connected to earth |
| Outside the unit: area surrounding the unit | Intoxication, serious burns | Fire due to short circuit or overheating of the supply line upstream of the unit’s electrical panel | Ensure conductor cross-sectional areas and the supply line protection system conform to applicable regulations |
How should I handle transportation and storage of the PARKER HYPERCHILL ICE360?
Transport:
The packed unit must remain:
a) Upright;
b) Protected against atmospheric agents;
c) Protected against impacts.
Handling:
Use a fork-lift truck suitable for the weight to be lifted, avoiding any type of impact.
Inspection:
a) All units are assembled, wired, charged with refrigerant and oil, and tested in the factory.
b) On receiving the machine, check its condition and immediately notify the transport company in case of any damage.
c) Unpack the unit as close as possible to the place of installation.
Storage:
a) Keep the unit packed in a clean place protected from damp and bad weather.
b) Do not stack the units.
c) Follow the instructions given on the package.
What are the characteristics for inlet water and inlet condensation water for the PARKER HYPERCHILL ICE360?
The following table outlines the required water characteristics. If not provided in the supply, fit a mesh filter on the water inlet.
| Temperature | ≥50°F (10°C) | CL- | <50 ppm |
| ΔT IN/OUT | 5-15°C | CaCO3 | 70-150 ppm |
| Max % glycol | 50 | O2 | <0.1 ppm |
| Pressure | 43.5-145 PSIg (3-10 barg) | Fe | <0.2 ppm |
| PH | 7.5-9 | NO3 | <2 ppm |
| Electrical conductivity | 10-500 μS/cm | HCO3- | 70-300 ppm |
| Langelier saturation index | 0-1 | H2S | <0.05 ppm |
| SO4(2-) | <50 ppm | CO2 | <5 ppm |
| NH3 | <1 ppm | Al | <0.2 ppm |
Please note that for special water types such as demineralized, deionized or distilled it is necessary to contact the manufacturer to verify which kind of chiller should be used since the standard material may not be suitable.
When is the use of ethylene glycol required for the PARKER HYPERCHILL ICE360?
If installed outdoors or in an unheated indoor area, the water in the circuit may freeze. To avoid this hazard, you can add an appropriate quantity of antifreeze (ethylene glycol) to the water in circulation. The required percentage depends on the outlet water temperature and the ambient temperature.
| Outlet water temperature [°C] | Ethylene glycol (% vol.) | Ambient temperature |
|---|---|---|
| 4 | 5 | -2 |
| 2 | 10 | -5 |
| 0 | 15 | -7 |
| -2 | 20 | -10 |
| -4 | 25 | -12 |
| -6 | 30 | -15 |
| -10 | 40 | -20 |
How do I perform initial electrical checks and connections for the PARKER HYPERCHILL ICE360?
Before carrying out any operation on the electrical system, make sure that the appliance is disconnected from the electrical power supply. All electrical connections must comply with the applicable regulations in force in the country of installation.
Initial Checks
1) The power supply voltage and frequency must correspond to the values stamped on the chiller nameplate. The power supply characteristics must not deviate from the tolerance limits indicated on the electrical diagram (+/- 10% for voltage; +/- 1% for frequency).
2) The power supply must be symmetrical (effective voltages and phase angles of consecutive phases must be equal). The maximum permissible voltage imbalance is 2%.
Connection
1) The electrical power supply must be connected using a 4-wire cable (3 phase conductors and an earth conductor, with no neutral).
2) Pass the cable through the cable entry on the rear panel and connect the phase and neutral to the terminals of the main isolator switch (QS); connect the earth wire to the earth terminal (PE).
3) Ensure that the supply cable has at its source protection against direct contact of at least IP2X or IPXXB.
4) On the supply line, install a residual-current circuit breaker with a trip rating of 0.3A, with the current rating indicated in the reference electrical diagram, and an appropriate short circuit current rating. The nominal current (In) of the magnetic circuit breaker must be equal to the FLA with an intervention curve type D.
5) The maximum grid impedance value is 0.274 ohm.
Subsequent Checks
Check that the machine and auxiliary equipment are earthed and protected against short circuit and/or overload.
What are the functions of the control panel buttons on the PARKER HYPERCHILL ICE360?
| P0 | Isolator switch. |
| P1 | Shows alarms on the display, switches off the buzzer if activated and resets alarms. |
| P2 | Enables access to the menu for selecting the group of parameters. |
| P3 | Cancels an operation. |
| P4 | Shifts the cursor or increases the value of a parameter. |
| P5 | Shifts the cursor or decreases the value of a parameter. |
| P6 | Shifts the cursor from one parameter to another or confirms a parameter. |
LED Indicators:
| LED | ON | OFF | FLASHING |
|---|---|---|---|
| P1 | – | No Alarm | Alarm present. |
| P2 | Machine ON | Machine OFF | – |
How do I start the PARKER HYPERCHILL ICE360?
Attention: Wait for the “30 seconds” boot start up to complete.
1. Compressor Heating:
Connect the power supply to the machine by turning the main isolator switch QS [P0] to ON. For the FL2 option, the crankcase heater must be activated 24 hours before starting the machine.
2. Start Procedure:
1. Switch on and wait for the “Status Unit: OFF” screen to appear.
2. Press the P2 button to enter the “main” menu.
3. The “Main menu” will appear. “On” should be selected.
4. Press the P6 button. The message “ON” will appear.
5. Press the P6 button again and the arrow will start flashing.
6. Press the P6 button one last time to start the chiller.
How do I perform adjustments at commissioning for the PARKER HYPERCHILL ICE360?
a) Temperature setting: To adopt a new setting, see heading 4.5.
b) Verify pump operation: Use the pressure gauge (read P1 and P0) and check the pressure limit values (Pmax and Pmin) on the pump data plate. The condition Pmin < (P1-P0) < Pmax should be met.
c) Verify correct pump operation under normal running conditions and check that the amperage is within the limits on the data plate.
d) Top up hydraulic circuit: Switch off the chiller and top up the hydraulic circuit at the “SET” temperature.
e) Check temperatures: Ensure the “treated” water temperature does not fall below 5 °C and the ambient temperature does not fall below 5 °C. If necessary, add glycol as explained in section 3.4.2.
How do I stop the PARKER HYPERCHILL ICE360?
1. From the main operating screen, press the P2 button to enter the “main” menu.
2. Use the P5 button to scroll down and select “OFF”.
3. Press the P6 button. The message “OFF” appears on the screen.
4. Press the P6 button again, and the arrow will start flashing.
5. Press the P6 button one final time to stop the chiller. The status will change to “Status Unit: OFF”.
Warning: Do not turn off the main switch QS [P0] to ensure that any antifreeze protection devices will still receive electrical power.
How do I change the set point on the PARKER HYPERCHILL ICE360?
1. Press the P2 button to enter the “main” menu.
2. Use the P5 button to scroll down and select “DIrE”.
3. Press the P6 button. The message “DIrE” appears.
4. Use the P5 button to select the first parameter, which is the set point (“SEt Temperature Control Set Point”).
5. Press the P6 button to enter the parameter setting screen.
6. Use the P4 (up) or P5 (down) buttons to modify the value.
7. Press the P6 button to confirm the new value.
8. Press the P3 (Esc) button to exit.
How does the compressor on the PARKER HYPERCHILL ICE360 operate?
The ON/OFF of the compressors depends on the water outlet temperature (b1) with reference to the “set” and “dif” parameters. The compressor ON/OFF logic also depends on the ambient temperature.
| Ambient Temperature | ON/OFF compressor |
|---|---|
| > 10°C | step control |
| < 10°C | together |
Example (Ambient temp. < 10°C):
If set = 7°C and dif = 4°C, when the water inlet temperature reaches 9°C (7 + 2), compressor 1 starts. When it reaches 11°C (7 + 4), compressor 2 starts.
Example (Ambient temp. > 10°C):
If set = 7°C and dif = 4°C, when the water inlet temperature reaches 11°C (7 + 4), compressors 1 and 2 start.
Warning: A compressor can only restart after a stop of 6 minutes.
How do I manage alarms on the PARKER HYPERCHILL ICE360?
When the P1 button is red, an alarm is present. Press the button to see the type of alarm (e.g., HP1 High pressure Alarm Circuit 1).
To clear the alarm, you must eliminate the cause of the fault and carry out the necessary repair. After the repair:
1. Press the P1 button.
2. If the message “noAL” appears, press the P1 button again to reset the alarm.
What do the digital input alarms for the PARKER HYPERCHILL ICE360 indicate?
| CODE | DESCRIPTION | RESET |
|---|---|---|
| HP1 | High pressure alarm 1 from pressure switch* | M |
| LP1 | Low pressure alarm 1 from pressure switch | M |
| tP | Pump thermal cutout alarm | M |
| dP | Water tank low water level alarm / No water flow | M |
| HP2 | High pressure alarm 2 from pressure switch* | M |
| LP2 | Low pressure alarm 2 from pressure switch | M |
| PI1 | Protection alarm compressor 1 / Phases monitor | M |
| PI2 | Protection alarm compressor 2 / Phases monitor | M |
| PI4 | Protection alarm compressor 4 / Phases monitor | M |
* HP1/Hp2: once the cause of the outage has been eliminated, there is a button on the pressure switch to press to reset the component, then it is necessary to perform the reset from the display; this type of intervention requires qualified and specialized personnel.
What do the analog input alarms for the PARKER HYPERCHILL ICE360 indicate?
| AI | CODE | DESCRIPTION | RESET |
|---|---|---|---|
| b1 | HA1 | Tank water outlet water high temperature alarm | Warning |
| LA1 | Tank water outlet water low temperature alarm | A | |
| St1 | Sensor open circuit or short circuit | M | |
| b2 | HA2 | Evaporator 1 outlet water high temperature alarm | Warning |
| LA2 | Evaporator 1 outlet water low temperature alarm | A | |
| St2 | Sensor open circuit or short circuit | M | |
| b5 | HA5 | High ambient temperature warning | Warning |
| LA5 | Low ambient temperature warning | Warning | |
| St5 | Sensor open circuit or short circuit | M | |
| P1 | SP1 | Transducer open circuit or short circuit | A |
| P2 | SP2 | Transducer open circuit or short circuit | A |
What is the preventive maintenance schedule for the PARKER HYPERCHILL ICE360?
To guarantee lasting maximum chiller efficiency and reliability, carry out the following:
• Every 4 months: Clean the condenser fins and make sure compressor electrical absorption is within the dataplate values.
• Yearly (W version): In case of encrustations inside the condenser, introduce and circulate a specific detergent liquid.
• Every 3 years: Installation of kit for maintenance.
During periodic maintenance, the electrical system and electrical panel must also be checked in accordance with local legislation. A visual inspection of the equipment and electrical conductors should also be performed where possible, and the correct tightening of the terminals of the power components must be verified.
What should I do if the outlet water temperature on my PARKER HYPERCHILL ICE360 exceeds the set value?
If the outlet water temperature exceeds the set value, this could be due to excessive water flow or high thermal load. The remedy is to reduce the flow rate of the water to be cooled.
What should I do if the compressor on my PARKER HYPERCHILL ICE360 stops due to the high-pressure switch?
If the compressor stops due to the high-pressure switch, check the following potential causes and remedies:
• High ambient temperature: Return the ambient temperature to below the specified limit.
• Condenser fins dirty: Clean the fins of the condenser.
• Condenser surfaces clogged: Clear the front surface of the condenser.
• Fan rotates backwards: Swap over the phase wires.
• Leaks in circuit, system discharged: Check for leaks, repair, and charge the circuit.
• Pressure switch broken or incorrectly calibrated: Replace the pressure switch.
What should I do if the compressor on my PARKER HYPERCHILL ICE360 stops due to the low-pressure switch?
If the compressor stops due to the low-pressure switch, check the following potential causes and remedies:
• Refrigerant filter clogged: Renew the filter.
• Insufficient water flow: Increase the flow rate of the fluid to be cooled.
• Thermostatic bulb discharged: Renew the valve.
• Thermostatic valve incorrectly calibrated: Recalibrate the valve.
What are the causes and remedies if the compressor suction line on my PARKER HYPERCHILL ICE360 is frosted?
If the compressor suction or liquid line is frosted, it may be due to a clogged refrigerant filter. The remedy is to renew the filter.
What does it mean if the compressor on my PARKER HYPERCHILL ICE360 runs for long periods and is noisy?
If the compressor runs for long periods and is noisy, it could indicate that the compressor components have deteriorated. The solution is to repair or replace the compressor.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD PARKER HYPERCHILL ICE360 (01) PDF DOCUMENT