What are the key safety instructions for the PARKER HYPERCHILL ICE310?

When operating the PARKER HYPERCHILL ICE310, please adhere to the following safety instructions:

• The user manual should be kept for the entire life of the machine and read before any operation.

• Every unit is equipped with an electric disconnecting switch for operating in safe conditions. Always use this device to eliminate risks during maintenance.

• The manual is intended for the end-user for operations performable with closed panels. Operations like installation, commissioning, or maintenance requiring the opening of panels with tools must be carried out by skilled and qualified personnel.

• Do not exceed the design limits given on the dataplate.

• It is the user’s responsibility to avoid loads different from the internal static pressure. The unit must be appropriately protected whenever risks of seismic phenomena exist.

• Only use the unit for professional work and for its intended purpose.

• Tampering or replacement of any parts by unauthorized personnel and/or improper machine use will invalidate the warranty.


What are the residual risks associated with the PARKER HYPERCHILL ICE310?

The risks that could not be eliminated in the design stage are listed in the following table. Installation, start-up, stopping, and maintenance must be performed in a way to avoid creating any hazardous situation.

Part Affected Residual Risk Manner of Exposure Precautions
heat exchanger coil small cuts contact avoid contact, wear protective gloves
fan grille and fan lesions insertion of pointed objects through the grille while the fan is in operation do not poke objects of any type through the fan grille or place any objects on the grille
inside the unit: compressor and discharge pipe burns contact avoid contact, wear protective gloves
inside the unit: metal parts and electrical wires intoxication, electrical shock, serious burn defects in the insulation of the power supply lines upstream of the electrical panel; live metal parts adequate electrical protection of the power supply line; ensure metal parts are properly connected to earth
outside the unit: area surrounding the unit intoxication, serious burns fire due to short circuit or overheating of the supply line upstream of the unit’s electrical panel ensure conductor cross-sectional areas and the supply line protection system conform to applicable regulations

How should I transport, handle, inspect, and store my PARKER HYPERCHILL ICE310?

Transport:

The packed unit must remain:

a) Upright;

b) Protected against atmospheric agents;

c) Protected against impacts.

Handling:

Use a fork-lift truck suitable for the weight to be lifted, avoiding any type of impact.

Inspection:

a) All units are assembled, wired, charged with refrigerant and oil, and tested in the factory.

b) On receiving the machine, check its condition. Immediately notify the transport company in case of any damage.

c) Unpack the unit as close as possible to the place of installation.

Storage:

a) Keep the unit packed in a clean place protected from damp and bad weather.

b) Do not stack the units.

c) Follow the instructions given on the package.


What are the operating space and foundation requirements for the PARKER HYPERCHILL ICE310?

Operating Space:

To allow an unrestricted air flow around the chiller and easy access for servicing, ensure the area around the unit is kept free of obstacles. Leave a space of at least 2 metres above the refrigerator in models with vertical emission of condensation air.

Foundation:

The unit must be placed on a level surface which will support its weight.


What are the required characteristics for the water used in the PARKER HYPERCHILL ICE310?

The following table outlines the required characteristics for inlet water and inlet condensation water. If not provided in the supply, fit a mesh filter on the water inlet.

Temperature ≥50°F (10°C) CL- <50 ppm
ΔT IN/OUT 5-15°C CaCO₃ 70-150 ppm
Max % glycol 50 O₂ <0.1 ppm
Pressure 43.5-145 PSIg (3-10 barg) Fe <0.2 ppm
PH 7.5-9 NO₃ <2 ppm
Electrical conductivity 10-500 μS/cm HCO₃- 70-300 ppm
Langelier saturation index 0-1 H₂S <0.05 ppm
SO₄²- <50 ppm CO₂ <5 ppm
NH₃ <1 ppm Al <0.2 ppm

Please note that for special water types such as demineralized, deionized or distilled it is necessary to contact the manufacturer to verify which kind of chiller should be used since the standard material may not be suitable.


When should I use antifreeze with my PARKER HYPERCHILL ICE310, and in what quantities?

If the PARKER HYPERCHILL ICE310 is installed outdoors or in an unheated indoor area, the water in the circuit may freeze when not in operation. To avoid this, you can add an appropriate quantity of antifreeze (ethylene glycol) to the water in circulation. The required percentage depends on the outlet water temperature and ambient temperature.

Outlet water temperature [°C] Ethylene glycol (% vol.) Ambient temperature
4 5 -2
2 10 -5
0 15 -7
-2 20 -10
-4 25 -12
-6 30 -15
-10 40 -20

What are the functions of the control panel buttons on the PARKER HYPERCHILL ICE310?

P0 Isolator switch.
P1 Shows alarms on the display, switches off the buzzer if activated and resets alarms.
P2 Enables access to the menu for selecting the group of parameters.
P3 Cancels an operation.
P4 Shifts the cursor or increases the value of a parameter.
P5 Shifts the cursor or decreases the value of a parameter.
P6 Shifts the cursor from one parameter to another or confirms a parameter.

How do I start the PARKER HYPERCHILL ICE310?

Follow these steps to start the chiller:

1. Compressor Heating: Connect the power supply to the machine by turning the main isolator switch QS [P0] to ON. For the FL2 option, the crankcase heater must be activated 24 hours before starting the machine. Incorrect operation can damage the compressor.

2. Start: Switch on and wait for the “Status Unit : OFF” screen to appear.

3. Press the button [P2] to enter the “main” menu.

4. The screen will show “On”, “OFF”, and “USER”.

5. Press the button [P6]. The message “ON” will appear.

6. Press the button [P6] again, and the arrow will start flashing.

7. Press the button [P6] a final time to start the chiller.

Note: Wait for the boot start-up of “30 seconds”.


How do I stop the PARKER HYPERCHILL ICE310?

Follow these steps to stop the chiller:

1. From the main operating screen, press the [P2] button to enter the “main” menu.

2. Press the [P5] button to scroll down and select “OFF”.

3. Press the [P6] button. The message “OFF” appears with a flashing arrow.

4. Press the [P6] button again to confirm.

5. The chiller will stop, and the display will show “Status Unit : OFF”.

Warning: Do not turn off the main switch QS [P0] to ensure that any antifreeze protection devices will still receive electrical power.


How do I change the set point on the PARKER HYPERCHILL ICE310?

Follow these steps to change the temperature set point:

1. Press the [P2] button to enter the “main” menu.

2. Press the [P5] button to scroll and select “DIrE”.

3. Press the [P6] button. The message “DIrE” appears.

4. Press the [P5] button. The first parameter shown is the set point (SEt – Temperature Control – Set Point).

5. Press the [P6] button to enter the parameter setting mode.

6. Press the [P4] or [P5] buttons to modify the value.

7. Press the [P6] button to confirm the new setting.

8. Press the [P3] button to exit (ESC).


How does the compressor on the PARKER HYPERCHILL ICE310 operate?

The ON/OFF of the compressors depends on the water outlet temperature (b1) with reference to the “set” and “dif” parameters. The compressor ON/OFF logic also depends on the ambient temperature.

Ambient Temperature ON/OFF compressor
> 10°C step control
< 10°C together

Example (ambient temp. <10°C, set = 7°C, dif = 4°C):

• when the water inlet temperature reaches 9°C (7 + 2): compressor 1 starts;

• when the water inlet temperature reaches 11°C (7 + 4): compressor 2 starts.

Example (ambient temp. >10°C, set = 7°C, dif = 4°C):

• when the water inlet temperature reaches 11°C (7 + 4): compressors 1 and 2 start.

Warning: A compressor can only restart after a stop of 6 minutes.


How do I manage alarms on the PARKER HYPERCHILL ICE310?

When the [P1] button is red, an alarm is present. Press the button to see the type of alarm (e.g., HP1 High pressure Alarm). To clear the alarm, you must first eliminate the cause of the fault and carry out the repair. After the repair, press the [P1] button again. If the message “noAL” appears, press [P1] one more time to reset the alarm.

Digital Input Alarms

CODE DESCRIPTION RESET
HP1 High pressure alarm 1 from pressure switch* M
LP1 Low pressure alarm 1 from pressure switch M
tP Pump thermal cutout alarm M
dP Water tank low water level alarm / No water flow M
HP2 High pressure alarm 2 from pressure switch* M
LP2 Low pressure alarm 2 from pressure switch M
PI1 Protection alarm compressor 1 / Phases monitor M
PI2 Protection alarm compressor 2 / Phases monitor M
PI4 Protection alarm compressor 4 / Phases monitor M

* HP1/HP2: once the cause of the outage has been eliminated, there is a button on the pressure switch to press to reset the component, then it is necessary to perform the reset from the display; this type of intervention requires qualified and specialized personnel.

Analog Input Alarms

AI CODE DESCRIPTION RESET
b1 HA1 Tank water outlet water high temperature alarm Warning
LA1 Tank water outlet water low temperature alarm A
St1 Sensor open circuit or short circuit M
b2 HA2 Evaporator 1 outlet water high temperature alarm Warning
LA2 Evaporator 1 outlet water low temperature alarm A
St2 Sensor open circuit or short circuit M
b5 HA5 High ambient temperature warning Warning
LA5 Low ambient temperature warning Warning
St5 Sensor open circuit or short circuit M
P1 SP1 Transducer open circuit or short circuit A
P2 SP2 Transducer open circuit or short circuit A

How do I perform preventive maintenance on the PARKER HYPERCHILL ICE310?

To guarantee lasting maximum chiller efficiency and reliability, carry out the following:

Every 4 months: Clean the condenser fins and make sure compressor electrical absorption is within the dataplate values.

Yearly – W version: In case of encrustations inside the condenser, introduce and circulate a specific detergent liquid.

During periodic maintenance, the electrical system on the machine and the electrical panel must also be checked in accordance with local legislation. Additionally, a visual inspection of the equipment and electrical conductors should always be performed where possible, and the correct tightening of the terminals of the power components must also be verified.

Every 3 years: Installation of kit for maintenance every 3 years.


What should I do if the outlet water temperature exceeds the set value on my PARKER HYPERCHILL ICE310?

If the outlet water temperature exceeds the set value, it may be due to excessive water flow or a high thermal load. The remedy is to reduce the flow rate of the water being cooled.


What should I do if the compressor on my PARKER HYPERCHILL ICE310 stops due to the high-pressure switch?

If the compressor stops due to the operation of the high-pressure switch, check the following potential causes and apply the corresponding remedy:

Cause: High ambient temperature. Remedy: Return the ambient temperature to below the specified limit.

Cause: Condenser fins are dirty. Remedy: Clean the fins of the condenser.

Cause: Condenser surfaces are clogged. Remedy: Clear the front surface of the condenser.

Cause: Fan rotates backwards. Remedy: Swap over the phasewires.

Cause: Pressure switch is broken or incorrectly calibrated. Remedy: Replace the pressure switch.


What should I do if the compressor on my PARKER HYPERCHILL ICE310 stops due to the low-pressure switch?

If the compressor stops due to the operation of the low-pressure switch, investigate the following potential causes and remedies:

Cause: Refrigerant filter is clogged. Remedy: Renew the filter.

Cause: Insufficient water flow. Remedy: Increase the flow rate of the fluid to be cooled.

Cause: Thermostatic bulb is discharged. Remedy: Renew the valve.

Cause: Thermostatic valve is incorrectly calibrated. Remedy: Recalibrate the valve.

Cause: Leaks in the circuit, or the system is discharged. Remedy: Check for leaks, repair them, and charge the circuit.


What does it mean if the compressor suction line on my PARKER HYPERCHILL ICE310 is frosted?

A frosted compressor suction line can be caused by several issues. Check the following:

Cause: Insufficient water flow. Remedy: Increase the flow rate of the fluid to be cooled.

Cause: Thermostatic bulb is discharged. Remedy: Renew the valve.

Cause: Thermostatic valve is incorrectly calibrated. Remedy: Recalibrate the valve.


Why does my PARKER HYPERCHILL ICE310 compressor run for long periods and is noisy?

If the compressor runs for long periods and is noisy, it could be due to one of the following reasons:

Cause: Compressor components have deteriorated. Remedy: Repair or replace the compressor.

Cause: The refrigerant filter is clogged. Remedy: Renew the filter.

Cause: There are leaks in the circuit, or the system is discharged. Remedy: Check for leaks, repair them, and then charge the circuit.


How should the PARKER HYPERCHILL ICE310 be dismantled and disposed of?

The refrigerant and the lubricating oil contained in the circuit must be recovered in conformity with current local environmental regulations. The refrigerant fluid is recovered before final scrapping of the equipment.

Component Recycling / Disposal
frame and panels steel/epoxy resin polyester
pipes/collectors copper/aluminium/carbon steel
pipe insulation NBR rubber
compressor steel/copper/aluminium/oil
condenser steel/copper/aluminium
fan aluminium
refrigerant R407C (HFC)
valve brass/copper
electrical cable copper/PVC

Equipment containing electrical components must be disposed of separately and collected with electrical and electronic waste according to local and current legislation.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.