Free English PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the important safety and installation instructions for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
CAUTION!
The maximum ambient operating temperature for this UPS series is 40°C (0 – 40°C for Ambient Operation).
This UPS series is ONLY intended to be installed in an indoor temperature controlled environment that is free of conductive contaminants. It is not intended for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA 75.
Connect the UPS to a two pole, three wire, grounded, utility power AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse). Do not use extension cords, adapter plugs, or surge strips.
To reduce the risk of fire, connect only to a utility power circuit provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70.
To reduce the risk of electrical shock, the user must ensure that the combined sum of the AC leakage current does not exceed 3.5mA.
To reduce the risk of electrical shock where load equipment grounding cannot be verified, disconnect the UPS from the AC wall outlet before installing a computer interface cable. Reconnect the power cord only after all signaling connections are made.
DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS. The mounting brackets are ONLY for securing the UPS to the rack.
WARNING!
This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY.
Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected.
Installation Environment:
The external vents and openings on the UPS are provided for ventilation. To ensure reliable operation and protect from overheating, these vents and openings must not be blocked or covered.
Install the UPS system in a well-ventilated area, away from excess moisture, heat, dust, flammable gas or explosives.
Leave adequate space (at least 20cm) at the front and rear of the UPS system for proper ventilation.
Do not mount the UPS system with its front or rear panel facing down at any angle.
Before usage, you must allow the UPS system to adjust to room temperature (20°C-25°C or 68°F-77°F) for at least one hour to avoid moisture condensing inside the UPS.
How do I turn the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U on, turn it off, or perform a self-test?
The multi-function ON / OFF / TEST BUTTON is used for these operations.
Turn the UPS On: When the UPS is connected to an AC source with acceptable voltage, press and then release the On/Off/Test button during the audible alarm’s first beep. The UPS will provide an output, power the load, and perform a five-second self-test. After the self-test, it is ready for normal operation.
Turn the UPS Off: When the UPS is in AC mode, press and then release the On/Off/Test button during the audible alarm’s first beep.
Perform a Self-Test: With the UPS in AC mode, press and hold the On/Off/Test button until the audible alarm sounds four beeps, and then release. The UPS will perform a ten-second self-test, during which it will switch to battery mode, the On-Battery icon will illuminate, and the audible alarm will sound.
How do I completely de-energize the outputs of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
Follow these steps to completely de-energize the UPS:
1. If the UPS is on, press and release the On/Off/Test button during the audible alarm’s first beep to turn the UPS off.
2. Disconnect the UPS from the AC wall outlet.
3. To de-energize the UPS completely, disconnect the battery.
What should I do if my PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U is causing interference with radio or television reception?
If the equipment causes interference, which can be determined by turning the equipment off and on, you are encouraged to try to correct the interference by one or more of the following measures:
Re-orient the receiving antenna.
Relocate the computer with respect to the receiver.
Move the computer away from the receiver.
Plug the computer into a different outlet so that the computer and receiver are on different branch circuits.
Shielded communications interface cables must be used with this product.
What do the icons and indicators on the control panel of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U mean?
Icons:
AC mode icon: Illuminates when the UPS is on and operating in AC mode. It extinguishes in Battery mode and blinks when the UPS is in AVR (Boost and Buck) mode.
On-Battery icon: Illuminates when the UPS is operating in Battery mode. It extinguishes in AC mode.
Weak/Bad Battery icon: Illuminates and displays an error code when the UPS detects a weak, bad, or disconnected battery. It is extinguished when the battery’s condition is good.
Fault icon: Illuminates and displays an error code when the UPS detects an internal fault. It is extinguished when the UPS is operating properly.
Site Wiring icon (SWF): Illuminates and displays an error code when the UPS detects a site wiring problem. It is extinguished when connected to proper site wiring.
Bar Graphs:
Load Capacity Bar Graph: Displays the amount of connected load as 20%, 40%, 60%, 80%, or 100%. If the load exceeds 110%, the Overload and Fault icons will flash, an Overload error code will be displayed, and a constant alarm will sound.
Battery Capacity Bar Graph: Displays the amount of available battery capacity as 20%, 40%, 60%, 80%, or 100%.
Buttons:
Multi-Function On/Off/Test button: Turns the unit on/off and initiates a self-test.
Alarm Silencer button: In Battery mode, pressing this button will silence the audible alarm. The alarm will be re-activated if the UPS reaches the Low Battery Warning (LBW) threshold and cannot be silenced during the LBW alarm.
Scroll button: Allows the user to scroll through the UPS parameters available on the LCD screen.
LCD Parameters Displayed:
Input Voltage and Frequency
Output Voltage and Frequency
Connected load KVA and KW
Estimated Runtime (minutes) in AC mode and Battery mode
What are the connections on the rear panel of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
1. Input power cord: For connecting the UPS to utility power.
2. Input circuit breaker: Trips if the load exceeds the UPS’s power rating.
3. Coax connectors: For transient voltage surge suppression for cable modem, CATV converter, DSS receiver, or DVR.
4. Fan: For ventilation. Operates only during battery mode and AVR mode.
5. USB Communications Port: For UPS monitoring and control.
6. Battery Backup output receptacles: Wired into two segments (Load 1 & Load 2) to support the “Load Shedding Function”.
7. Always On Battery Backup output receptacles: Does not support “Load Shedding Function”.
8. Option slot: For option cards.
9. Rackmount brackets: For mounting the UPS to the rack.
10. RJ11/45 modular connectors: For transient voltage surge suppression for 10/100/1000 Base-T Network/single line Phone/Fax/Modem.
11. RJ11 EPO (Emergency Power Off) Port: For UPS control. Not for Telecommunication use.
How do I install the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
First, select a proper location. The UPS is intended for an indoor, temperature-controlled environment free of conductive contaminants. Do not operate in dusty areas, near heat, water, excessive humidity, or in direct sunlight. Ensure good air circulation at all times.
The UPS is shipped with the internal batteries disconnected. You must connect the batteries before putting the UPS into service.
Connecting the Batteries (Qualified Service Personnel Only):
1. Remove the UPS from the shipping box and place on a flat surface.
2. Grasp the battery door on the left-hand side, pull it outward, and set it aside.
3. Verify proper polarity. Connect the battery connectors together. Some sparking may occur; this is normal.
4. Re-install the battery door on the UPS.
5. Proceed with your chosen configuration (Rackmount, Tower, or Wallmount).
What are the steps for a rackmount configuration of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
The UPS comes with mounting brackets for a standard 19″ rack pre-installed. CAUTION: The UPS is extremely heavy. Use two or more people when installing.
1. Mount the UPS into the rack and secure with the four retaining screws provided. Do not move the rack after the units have been installed, as it may become unstable due to weight distribution.
2. The Rackmount Configuration is complete. Proceed to “Connecting your Equipment”.
What are the steps for a tower configuration of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
CAUTION: The UPS is extremely heavy. Use two or more people when installing.
1. Once the location is determined, place the UPS on a flat surface, remove the rackmount brackets, and then place the tower brackets in the desired location.
2. The LCD panel can be rotated. Insert a small flat head screwdriver into one of the small slots on the side of the LCD panel and gently pry it outward. Position it to read in the upright position, then gently press it back into the front panel.
NOTE: The UPS must be installed in the proper up-right position to avoid battery damage. When placed in the tower brackets, the YELLOW Battery disconnected label on the top cover must be on your left-hand side.
3. Slide the UPS into the tower brackets. Make sure the UPS is stable.
4. The Tower Configuration is complete. Proceed to “Connecting your Equipment”.
What are the steps for a wallmount configuration of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
A wallmount bracket kit is required. CAUTION: The UPS is extremely heavy. Use two or more people when installing.
1. Once the location is determined, place the UPS on a flat surface and remove the rackmount brackets.
2. The LCD panel can be rotated. Insert a small flat head screwdriver into one of the small slots on the side of the LCD panel and gently pry it outward. Position it to read in the upright position, then gently press it back into the front panel.
NOTE: The UPS must be installed in the proper up-right position to avoid battery damage. When attached to the wall, the YELLOW Battery disconnected label on the top cover must be on your left-hand side.
3. Align the wall mounting brackets with the screw holes on the side panels of the UPS and attach with the six retaining screws.
4. Use the template to mark the screw hole positions on the wall. Always wear protective gear when operating power tools.
5. Attach the four retaining screws to the wall, ensuring they are screwed into structural material. Do not tighten the screws all the way; leave approximately 3/8″ of the screws sticking out.
6. Position the UPS so that the mounting bracket keyed holes line up with the four retaining screws. Slide the UPS down until it rests securely on the screws.
7. Tighten the four retaining screws to secure the UPS to the wall.
8. The Wallmount Configuration is complete. Proceed to “Connecting your Equipment”.
How do I connect equipment and charge the battery of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
Connecting Your Equipment:
Plug your equipment into the output receptacles on the rear panel. Do not exceed the maximum output rating of the UPS. DO NOT plug extension cords, adapter plugs, or surge strips into the output receptacles. CAUTION! DO NOT connect a laser printer, copier, vacuum cleaner or any other large electrical device to the UPS.
Connecting to an AC Source:
Plug the UPS into a two pole, three wire, grounded receptacle only. The AC wall outlet should be near the UPS and easily accessible. DO NOT cut the input plug off and attempt to hardwire the UPS.
Checking the Site Wiring Fault:
After plugging the UPS into the AC wall outlet, check the Site Wiring Fault (SWF) icon on the front panel. If the SWF icon is illuminated, the UPS is plugged into an improperly wired AC wall outlet. Have a Qualified Electrician correct the problem.
Charging the Battery:
The UPS will charge the batteries whenever it is connected to an AC source with acceptable voltage (90-150VAC). It is recommended that the batteries be charged for a minimum of 4 hours before use. If the UPS is stored for a prolonged period, the batteries must be recharged for at least twenty-four hours every ninety days.
What do the different alarms on the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U mean?
ON BATTERY: When operating on batteries, the AC mode icon extinguishes, the On-Battery icon illuminates, and the audible alarm will sound one beep every 10 seconds.
LOW BATTERY WARNING: When batteries reach a predetermined low level (approximately two minutes of runtime remaining), the audible alarm will sound two beeps every five seconds. The LCD will display error code E07. This alarm cannot be silenced.
WEAK/BAD BATTERY: If the battery is weak, bad, or disconnected, the Weak/Bad Battery icon will illuminate, the LCD will display error code E06, and the audible alarm will sound three beeps every five minutes. It is recommended to let the UPS charge overnight before performing another battery test to confirm the condition.
OVERLOAD: When the connected load exceeds the UPS power rating, the Overload icon will illuminate, the LCD will display error code E02, and the audible alarm will sound continuously. This will continue until the excess load is removed or the UPS shuts down.
UPS FAULT: When an internal fault is detected, the Fault icon will illuminate, an error code will be displayed, the audible alarm will sound continuously, and the output will be turned off. This may sometimes be cleared by turning the UPS off and then on. If not, the unit requires service.
How do I troubleshoot common problems and error codes with the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
| Symptom / Error Code | Cause / What To Do |
|---|---|
| UPS will not turn on. | Press the On/Off/Test button and release after one beep. |
| UPS operates in battery mode only, even though there is AC present. | Reset the input circuit breaker by pressing the plunger back in. If the input circuit breaker trips after the UPS restarts, reduce the load on the UPS. |
| The AC mode icon is blinking and the alarm is silent. | The UPS is in either the Boost or the Buck mode. It is performing its intended function. |
| UPS does not provide expected runtime. | Charge the batteries for 8-hours and retest. If the runtime is still less than expected, the batteries may need to be replaced. |
| The AC mode icon is illuminated, but there is no output. | Disconnect the computer cable from the UPS, press the On button. If UPS works normally, the software had control of the UPS. |
| Fault icon is illuminated and a constant alarm. | The UPS has an internal problem, call for service. |
| Error Code: E01. UPS is shutdown. | The UPS has detected a short-circuit on its output. Check the attached load. |
| Error Code: E02. Overload icon is illuminated and a constant alarm. | Check the specifications and remove part of the load. If the UPS shuts down because of an Overload, the UPS must perform an Inverter function or a Self Test to clear the Overload Alarm. |
| Error Code: E03. Over Temperature Shutdown. | The internal or ambient temperature has exceeded the safe operating range for the UPS. Check the specifications. |
| Error Code: E04: Inverter/Output Failure Shutdown. | The UPS has an internal fault, call for service. |
| Error Code: E05. Charger Failure Warning. | The charger has failed, call for service. |
| Error Code: E06. Weak/Bad Battery icon is illuminated. | Check the battery connections, charge the batteries for 8-hours and retest, or replace the batteries. |
| Error Code: E07. Low Battery Warning. | The UPS’s battery reserve is low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion. |
| Error Code: E08. SWF icon is illuminated. | Have a qualified electrician correct the service wiring. |
What precautions should be taken when replacing the batteries in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY. Typical battery life is 3 to 5 years.
WARNING! This UPS contains potentially hazardous voltages. Do not disassemble the UPS beyond the battery replacement procedure.
CAUTION:
Do not open or mutilate batteries. Released electrolyte is harmful and may be toxic.
Do not dispose of batteries in a fire. The batteries may explode. The batteries are recyclable and contain lead.
The battery system can present a risk of electrical shock. Observe these precautions:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If it is, remove the source of grounding.
Replace the batteries with the same number and type as originally installed. These UPSs contain sealed non-spillable maintenance-free lead acid batteries.
What is the procedure for replacing the batteries in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
These batteries are hot-swappable. If there is a power interruption while replacing the batteries with the UPS on, the load will not be backed up. To hot-swap, start with step number 6.
1. Turn off the equipment that is plugged into the output of the UPS.
2. Press the On/Off/Test Button on the front panel to turn the UPS off.
3. Unplug the UPS’s AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Grasp the battery door on the left hand side, pull it outward and then set it aside.
7. Disconnect the battery connectors.
8. Remove the four retaining screws for the battery retaining bracket.
9. Remove the battery retaining bracket and set aside.
10. Grasp the battery pull tab and gently pull the battery module out of the UPS and set it aside. CAUTION, the battery module is heavy. DO NOT use the battery wires to pull the battery module out.
11. Slide the new battery module into the UPS.
12. Re-install the battery retaining bracket.
13. Re-install the four retaining screws for the battery retaining bracket.
14. Verify proper polarity. Reconnect the battery connectors together. NOTE: Some sparking might occur, this is normal.
15. Re-install the battery door on the UPS.
16. Properly dispose of the old batteries at an appropriate recycling facility.
17. The UPS is now ready for normal operation.
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the battery module, you must initiate a self-test to clear the alarm. To initiate a self-test, see the section on the “ON / OFF / TEST BUTTON”.
What are the technical specifications for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
SYSTEM SPECIFICATIONS
| Model Number | PRO1000RT2U |
| Topology | Line-Interactive, Simulated Sine Wave |
| Maximum Power Capacity | 1000VA / 700W |
INPUT
| Number of Phase | Single (1Ø2W +G) |
| Nominal Voltage | 120VAC |
| Acceptable Input voltage | 0 – 150VAC |
| Voltage Range | 90 – 150VAC |
| Frequency Limits | 60 Hz, ±6Hz |
| Low Voltage Transfer Point | 89V resets to Utility Power at 94V or higher |
| High Voltage Transfer Point | 151V resets to Utility Power at 146V or lower |
| Protection | Resettable Circuit Breaker |
| Power Cord (10ft) | NEMA 5-15P |
OUTPUT NON-BATTERY OPERATION
| Voltage Range | 103 – 136VAC |
| Voltage Regulation | 120VAC: ±13.3% |
| Frequency Range | 60Hz: 54 – 66Hz |
| Efficiency (Line Mode) | >96% (Full Load) |
OUTPUT BATTERY OPERATION
| Waveform Type | Simulated Sine Wave |
| Nominal Voltage | 120VAC |
| Voltage Regulation | 120VAC ±5% (until Low Battery Warning) |
| Frequency | 60Hz, ±0.5Hz (unless synchronized to utility) |
| Transfer Time | 6-10 ms Typical |
| Overload Capacity | AC Mode: 110% for 1-minute then shutdown, 150% Shutdown Immediately DC Mode: 110% for 20-seconds then shutdown, 150% Shutdown Immediately |
| Protection | Over-Current, Short-Circuit Protected and Latching Shutdown |
| Receptacles (NEMA) | 8: 5-15R |
BATTERY SYSTEM
| Battery Type | Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid |
| Typical Recharge Time | 8-hours to 90% capacity from a full load discharge |
| Typical Battery Life | 3 to 5 years. Environmental factors do affect battery life. |
| Battery Module Part # | BM0073 |
| Runtime: Full Load (minutes) | 4 |
| Runtime: Half Load (minutes) | 14 |
SURGE PROTECTION AND FILTERING
| UPS Surge Energy Rating | 960J |
| Surge Current Capability | 6500 Amps total (one time 8 to 20us waveform) |
| Response Time | 0 ns (instantaneous) normal mode; <5 ns common mode |
| Surge voltage let-through | < 0.30% |
| Noise Filter | >45db normal and common mode EMI/RFI suppression |
| Audible Noise at 1 m (3 ft.) | <45 dBA |
| Network/Phone/Fax/Modem transient voltage surge protection | 10/100/1000 Base-T network, single line phone, Fax or Modem. 1-in / 1-out combo RJ11/45 connectors |
| Coax transient voltage surge protection | Cable modem, CATV converter, DSS receiver, DVR. 1-in / 1-out |
ENVIRONMENTAL
| Operating Temperature | 0 to 40°C (+32 to +104°F) |
| Operating Elevation | 0 to 3000m (0 to +10,000 ft) |
| Operating/Storage Humidity | 5-95% Non-Condensing |
| Storage Temperature | -15 to +45°C (+5 to +113°F) |
| Storage Elevation | 0 to 15,000m (0 to +50,000 ft) |
PHYSICAL
| Size – Net L X W X H | 16.1 X 18.9 X 3.4″ / 410 X 480.6 X 86.2 mm |
| Weight – Net | 35.7 lbs / 16.2 Kgs |
| Size – Shipping L X W X H | 22.4 X 21.7 X 9.4″ / 570 X 550 X 240 mm |
| Weight – Shipping | 41.9 lbs / 19.0 Kgs |
What is the harmonic distortion of the output for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO1000RT2U?
The output of this device is not sinusoidal. It has a voltage total harmonic distortion and maximum single harmonic distortion as shown in the table below:
| Model | PRO1000RT2U |
|---|---|
| Total harmonic | 30.3% |
| Single harmonic | 14.9% |