Free English PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.


CLICK HERE TO DOWNLOAD PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

What are the important safety instructions for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

Please observe the following safety instructions when installing and operating your PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U:

• The maximum ambient operating temperature for this UPS series is 40°C.

• This UPS is intended ONLY for installation in an indoor, temperature-controlled environment free of conductive contaminants. It is not intended for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA 75.

• The external vents and openings on the UPS are for ventilation. To ensure reliable operation and protect from overheating, these vents must not be blocked or covered.

• Install the UPS in a well-ventilated area, away from excess moisture, heat, dust, flammable gas, or explosives.

• Leave at least 20cm of space at the front and rear of the UPS for proper ventilation.

• Do not mount the UPS with its front or rear panel facing down at any angle.

• Before use, allow the UPS to adjust to room temperature (20°C-25°C) for at least one hour to avoid moisture condensation inside the unit.

• Connect the UPS to a two-pole, three-wire, grounded, utility power AC wall outlet. Do not use extension cords, adapter plugs, or surge strips.

• To reduce the risk of fire, connect only to a utility power circuit provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70.

• To reduce the risk of electrical shock, ensure that the combined sum of the AC leakage current for the UPS and connected equipment does not exceed 3.5mA.

• Disconnect the UPS from the AC wall outlet before installing a computer interface cable if load equipment grounding cannot be verified. Reconnect the power cord only after all signaling connections are made.

• This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. Repairs and battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY.

• Hazardous live parts inside are energized from the battery even when the AC input is disconnected.

• DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS. The mounting brackets are ONLY for securing the UPS to the rack.


How do I de-energize the outputs of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

To de-energize the outputs of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U, follow these steps:

1. If the UPS is on, press and release the On/Off/Test button during the audible alarm’s first beep to turn the UPS off.

2. Disconnect the UPS from the AC wall outlet.

3. To de-energize the UPS completely, disconnect the battery.


How do I use the ON/OFF/TEST button on my PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

The ON/OFF/TEST button on your PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U has multiple functions:

• **Turn On:** When the UPS is connected to an AC source with acceptable voltage, press and release the On/Off/Test button during the audible alarm’s first beep. The UPS will turn on, provide an output, and perform a five-second self-test.

• **Turn Off:** When the UPS is in AC mode, press and release the On/Off/Test button during the audible alarm’s first beep to turn the UPS off.

• **Perform a Self-Test:** With the UPS in AC mode, press and hold the On/Off/Test button until the audible alarm sounds four beeps, and then release. The UPS will perform a ten-second self-test, during which it will switch to battery mode, the On-Battery icon will illuminate, and the alarm will sound.


What is the harmonic distortion output of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U models?

The output of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U is not sinusoidal. It has the following voltage total harmonic distortion and maximum single harmonic distortion:

Model PRO750RT2U PRO1000RT2U PRO1500RT2U PRO2000RT2U
Total harmonic 31.3% 30.3% 37.2% 35.6%
Single harmonic 14.5% 14.9% 18.7% 15.7%

What should I do after receiving my PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

After removing your PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U from its carton, it should be inspected for any damage that may have occurred during shipping. If any damage is found, immediately notify the carrier and place of purchase. The packing materials are designed to minimize shipping damage. In the unlikely case that the UPS needs to be returned, please use the original packing material. PLEASE SAVE THE PACKING MATERIALS!


What do the icons and indicators on the control panel of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U mean?

The control panel on your PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U provides various information through its icons, display, and buttons:

• **AC mode icon:** Illuminates when the UPS is on and operating in AC mode. It extinguishes in Battery mode and blinks when in AVR (Boost and Buck) mode.

• **On-Battery icon:** Illuminates when the UPS is operating in Battery mode and extinguishes in AC mode.

• **Weak/Bad Battery icon:** Illuminates and displays an error code when the UPS detects a weak, bad, or disconnected battery.

• **Fault icon:** Illuminates and displays an error code when the UPS detects an internal fault.

• **Site Wiring icon (SWF):** Illuminates and displays a Site Wiring Fault error code if a site wiring problem is detected.

• **Load Capacity Bar Graph:** Displays the percentage of load connected to the UPS (20%, 40%, 60%, 80%, 100%). If the load exceeds 110%, the Overload and Fault icons will flash, an Overload error code will be displayed, and a constant alarm will sound.

• **Battery Capacity Bar Graph:** Displays the percentage of available battery capacity (20%, 40%, 60%, 80%, 100%).

• **UPS Parameters Display:** Shows Input Voltage and Frequency, Output Voltage and Frequency, Connected load in KVA and KW, and Estimated Runtime in minutes.

• **Multi-Function On/Off/Test button:** Turns the UPS on or off and initiates a self-test.

• **Alarm Silencer button:** When in Battery mode, pressing this button will silence the audible alarm. The alarm cannot be silenced during a Low Battery Warning (LBW) condition.

• **Scroll button:** Allows you to scroll through the UPS parameters available on the LCD screen.

NOTE: The LCD backlight illuminates for 20 seconds when the UPS switches to Battery mode. If an event or error code occurs, the backlight will turn on and remain on.


What are the features of the rear panel of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

1. **Input power cord:** For connecting the UPS to utility power. The AC wall outlet should be near the UPS and easily accessible.

2. **Input circuit breaker:** Trips if the load exceeds the UPS’s power rating.

3. **Coax connectors:** For transient voltage surge suppression for devices like cable modems, CATV converters, DSS receivers, or DVRs.

4. **Fan:** For ventilation. It operates only during battery mode and AVR mode.

5. **USB Communications Port:** For UPS monitoring and control.

6. **Battery Backup output receptacles:** These are wired into two segments (Load 1 & Load 2) to support the “Load Shedding Function”.

7. **Always On Battery Backup output receptacles:** These do not support the “Load Shedding Function”. The locking receptacle is only on the PRO2000RT2U model.

8. **Option slot:** For option cards.

9. **Rackmount brackets:** For mounting the UPS to the rack.

10. **RJ11/45 modular connectors:** For transient voltage surge suppression for 10/100/1000 Base-T Network or a single line Phone/Fax/Modem.

11. **RJ11 EPO (Emergency Power Off) Port:** For UPS control. This connection is not for Telecommunication use.

The output power receptacles vary by model:

Model # Output Power Receptacles
PRO750RT2U 6-NEMA 5-15R (Controllable), 2-NEMA 5-15R (Always On)
PRO1000RT2U 6-NEMA 5-15R (Controllable), 2-NEMA 5-15R (Always On)
PRO1500RT2U 6-NEMA 5-15R (Controllable), 2-NEMA 5-15R (Always On)
PRO2000RT2U 6-NEMA 5-15/20R (Controllable), 1-NEMA L5-20R (Always On)

What are the recommended environmental conditions for installing the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

The PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U is intended to be installed in an indoor temperature-controlled environment free of conductive contaminants. Select a location with good air circulation at all times. Avoid extremely dusty/unclean areas, locations near heating devices, water, excessive humidity, or direct sunlight. The environmental specifications are:

• **Operating Temperature (Maximum):** 40°C (+32 to +104°F)

• **Operating Elevation:** 0 to 3,000m (0 to +10,000 ft)

• **Operating and Storage Relative Humidity:** 95%, non-condensing

• **Storage Temperature:** -15 to +45°C (+5 to +113°F)

• **Storage Elevation:** 0 to 15,000m (0 to +50,000 ft)


How do I connect the batteries on the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

This procedure should be performed by QUALIFIED SERVICE PERSONNEL ONLY. The UPS is shipped with batteries disconnected.

1. Remove the UPS from the shipping box and place it on a flat surface. Use two or more people as the UPS is extremely heavy. (NOTE: No tools are required for removing or installing the battery door.)

2. Grasp the battery door on the left-hand side, pull it outward, and set it aside.

3. Verify proper polarity and connect the battery connectors together. (NOTE: Some sparking may occur; this is normal.)

4. Re-install the battery door on the UPS.

5. Connecting the batteries is complete. You may now proceed with the rackmount, tower, or wallmount configuration.


How do I install the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U in a rackmount configuration?

The UPS is heavy; use the appropriate number of personnel when installing.

1. Mount the UPS into the rack and secure it with the four retaining screws provided. Use two or more people when installing. Do not move the rack after the units have been installed, as it may become unstable due to the weight distribution.

2. The Rackmount Configuration is complete. Proceed to “Connecting your Equipment”.

CAUTION: DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS. They are ONLY for securing the UPS to the rack.


How do I configure the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U for a tower setup?

The UPS is extremely heavy; use two or more people when installing.

1. Once the location is determined, place the UPS on a flat surface, remove the rackmount brackets, and place the tower brackets in the desired location.

2. The LCD panel can be rotated. Insert a small flat head screwdriver into one of the small slots on the side of the LCD panel and gently pry it outward. Position the LCD panel so that it reads in the upright position, then gently press it back into the front panel.

NOTE: The UPS must be installed in the proper upright position to avoid damaging the batteries. When placed in the tower brackets, the YELLOW Battery disconnected label on the top cover must be on your left-hand side when looking at the front panel.

3. Slide the UPS into the tower brackets. Make sure the UPS is stable.

4. The Tower Configuration is complete. Proceed to “Connecting your Equipment”.


How do I install the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U in a wallmount configuration?

The UPS is extremely heavy; use two or more people for installation. A wallmount bracket kit is required.

1. Once the location is determined, place the UPS on a flat surface and remove the rackmount brackets.

2. Rotate the LCD panel to read in the upright position by gently prying it outward with a small flat head screwdriver.

NOTE: The UPS must be installed in the proper upright position. Once attached to the wall, the YELLOW Battery disconnected label on the top cover must be on your left-hand side when looking at the front panel.

3. Align the wall mounting brackets with the screw holes on the side panels of the UPS and attach with the six retaining screws.

4. Use the template to mark the screw hole positions on the wall. Use caution and wear protective gear when operating power tools.

5. Attach the four retaining screws to the wall, ensuring they are screwed into structural material. Leave approximately 3/8″ of the screws sticking out.

6. Position the UPS so that the mounting bracket keyed holes line up with the four retaining screws. Slide the UPS down until it rests securely on the screws.

7. Tighten the four retaining screws to secure the UPS to the wall.

8. The Wallmount Configuration is complete. Proceed to “Connecting your Equipment”.


How do I connect equipment and an AC power source to the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

To connect your equipment and power source:

• **Connecting Equipment:** Plug your equipment into the output receptacles on the rear panel. Ensure you do not exceed the maximum output rating of the UPS. DO NOT plug extension cords, adapter plugs, or surge strips into the output receptacles. CAUTION: DO NOT connect a laser printer, copier, vacuum cleaner, or any other large electrical device to the UPS.

• **Connecting to an AC Source:** Plug the UPS into a two-pole, three-wire, grounded receptacle only. The AC outlet should be near the UPS and easily accessible. DO NOT plug the UPS into extension cords, adapter plugs, surge strips, or power strips. Do not cut the input plug off and attempt to hardwire the UPS.

• **Checking Site Wiring Fault:** After plugging the UPS into the AC wall outlet, check the Site Wiring Fault (SWF) icon on the front panel. If the SWF icon is illuminated, the UPS is plugged into an improperly wired AC outlet. Have a qualified electrician correct the problem.

• **Charging the Battery:** The UPS charges the internal batteries whenever it’s connected to an acceptable AC source (90-150VAC). It is recommended to charge the batteries for a minimum of 4 hours before use. If the UPS is stored for a prolonged period, the batteries must be recharged for at least 24 hours every 90 days.


How does the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U operate and provide protection?

This Line-Interactive UPS protects equipment from blackouts, brownouts, overvoltages, and surges. Its AVR (Automatic Voltage Regulation) function continuously corrects voltages to a safe level. During normal AC operation, the UPS quietly protects your system.

When a blackout, brownout, or overvoltage occurs, the UPS transfers to battery mode. The On Battery indicator will illuminate, and an audible alarm will sound once every ten seconds.

When commercial power returns to an acceptable level, the UPS automatically transfers back to AC mode and starts recharging the batteries.

During an extended outage, when approximately two minutes of backup time remain, a Low Battery Warning alarm will sound twice every five seconds. When the batteries reach a predetermined level, the UPS will automatically shut down to protect them from over-discharging.

Once commercial power returns, the UPS will automatically restart, providing safe power to the connected equipment.


What do the different alarms mean on the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

• **ON BATTERY:** When the UPS is on battery power, the AC mode icon extinguishes, the On-Battery icon illuminates, and an audible alarm sounds one beep every 10 seconds. The LCD displays the estimated runtime remaining.

• **LOW BATTERY WARNING:** When batteries reach the predetermined low level, the audible alarm sounds two beeps every five seconds. The LCD displays error code E07. This indicates approximately two minutes of runtime remaining before the UPS shuts down.

• **WEAK/BAD BATTERY:** If the battery is weak, bad, or disconnected, the Weak/Bad Battery icon illuminates, the Battery Capacity Bar Graph turns off, the LCD displays error code E06, and an audible alarm sounds three beeps every five minutes. It is recommended to let the UPS charge overnight before performing another battery test.

• **OVERLOAD:** If the connected load exceeds the UPS’s power rating, the Overload icon illuminates, the LCD displays error code E02, and the audible alarm sounds continuously. This alarm will remain on until the excess load is removed or the UPS shuts down. To clear a shutdown overload alarm, remove part of the load, turn the UPS on, and then perform a battery test.

• **UPS FAULT:** If the UPS detects an internal fault, the Fault icon illuminates, an error code is displayed, the alarm sounds continuously, and the output is turned off. Sometimes this can be cleared by turning the UPS off and on. If not, the unit requires service.


How do I troubleshoot common issues with the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

Symptom / Error Code Cause / What To Do
UPS will not turn on. Press the On/Off/Test button and release after one beep.
UPS operates in battery mode only, even though there is AC present. Reset the input circuit breaker by pressing the plunger back in. If the input circuit breaker trips after the UPS restarts, reduce the load on the UPS.
The AC mode icon is blinking and the alarm is silent. The UPS is in either the Boost or the Buck mode. It is performing its intended function.
UPS does not provide expected runtime. Charge the batteries for 8-hours and retest. If the runtime is still less than expected, the batteries may need to be replaced.
The AC mode icon is illuminated, but there is no output. Disconnect the computer cable from the UPS, press the On button. If UPS works normally, the software had control of the UPS.
Fault icon is illuminated and a constant alarm. The UPS has an internal problem, call for service.
Error Code: E01. UPS is shutdown. The UPS has detected a short-circuit on its output. Check the attached load.
Error Code: E02. Overload icon is illuminated and a constant alarm. Check the specifications and remove part of the load. If the UPS shuts down because of an Overload, the UPS must perform an Inverter function or a Self Test to clear the Overload Alarm.
Error Code: E03. Over Temperature Shutdown. The internal or ambient temperature has exceeded the safe operating range for the UPS. Check the specifications.
Error Code: E04: Inverter/Output Failure Shutdown. The UPS has an internal fault, call for service.
Error Code: E05. Charger Failure Warning. The charger has failed, call for service.
Error Code: E06. Weak/Bad Battery icon is illuminated. Check the battery connections, charge the batteries for 8-hours and retest, or replace the batteries.
Error Code: E07. Low Battery Warning. The UPS’s battery reserve is low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion.
Error Code: E08. SWF icon is illuminated. Have a qualified electrician correct the service wiring.

What are the safety precautions for replacing the battery in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY. The battery system can present a risk of electrical shock. Observe these precautions:

1. Remove watches, rings, or other metal objects.

2. Use hand tools with insulated handles.

3. Wear protective eye gear (goggles), rubber gloves, and boots.

4. Do not lay tools or other metal parts on top of batteries.

5. Disconnect the charging source prior to connecting or disconnecting the battery terminals.

6. Determine if the battery is inadvertently grounded. If it is, remove the source of grounding. Contact with any part of a grounded battery can result in an electrical shock.

CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful.

CAUTION: Do not dispose of batteries in a fire. The batteries may explode.

CAUTION: Replace the batteries with the same number and type as originally installed in the UPS. These UPSs contain sealed non-spillable maintenance-free lead acid batteries.


What are the replacement battery module part numbers for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U models?

Model # PRO750RT2U PRO1000RT2U PRO1500RT2U PRO2000RT2U
Battery Module Part # BM0072 BM0073 BM0074 BM0075

What is the step-by-step procedure for replacing the battery in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

The batteries in this UPS are hot-swappable. If there is a power interruption while replacing batteries with the UPS on, the load will not be backed up. To hot-swap, start with step 6.

1. Turn off the equipment that is plugged into the output of the UPS.

2. Press the On/Off/Test Button on the front panel to turn the UPS off.

3. Unplug the UPS’s AC power cord from the AC wall outlet.

4. Unplug the equipment from the output receptacles of the UPS.

5. Unplug the computer interface cable from the rear panel of the UPS.

6. Grasp the battery door on the left-hand side, pull it outward, and then set it aside.

7. Disconnect the battery connectors.

8. Remove the four retaining screws for the battery retaining bracket.

9. Remove the battery retaining bracket and set it aside.

10. Grasp the battery pull tab and gently pull the battery module out of the UPS and set it aside. NOTE: DO NOT use the battery wires to pull the battery module out. Use caution, the battery module is heavy.

11. Slide the new battery module into the UPS.

12. Re-install the battery retaining bracket.

13. Re-install the four retaining screws for the battery retaining bracket.

14. Verify proper polarity. Reconnect the battery connectors together. (NOTE: Some sparking might occur; this is normal.)

15. Re-install the battery door on the UPS.

16. Properly dispose of the old batteries at an appropriate recycling facility.

17. The UPS is now ready for normal operation.

NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the module, you must initiate a self-test to clear the alarm. To initiate a self-test, see the “TEST BUTTON” instructions in the operation section.


What are the system specifications for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U models?

Feature PRO750RT2U PRO1000RT2U PRO1500RT2U PRO2000RT2U
SYSTEM SPECIFICATIONS
Topology Line-Interactive, Simulated Sine Wave
Maximum Power Capacity 750VA / 525W 1000VA / 700W 1500VA / 1050W 2000VA / 1400W
INPUT
Number of Phase Single (1Ø2W +G)
Nominal Voltage 120VAC
Acceptable Input voltage 0 – 150VAC
Voltage Range 90 – 150VAC
Frequency Limits 60 Hz, ±6Hz
Low Voltage Transfer Point 89V resets to Utility Power at 94V or higher
High Voltage Transfer Point 151V resets to Utility Power at 146V or lower
Protection Resettable Circuit Breaker
Power Cord (10ft) NEMA 5-15P NEMA 5-20P
OUTPUT NON-BATTERY OPERATION
Voltage Range 103 – 136VAC
Voltage Regulation 120VAC: ±13.3%
Frequency Range 60Hz: 54 – 66Hz
Efficiency (Line Mode) >96% (Full Load)
OUTPUT BATTERY OPERATION
Waveform Type Simulated Sine Wave
Nominal Voltage 120VAC
Voltage Regulation 120VAC ±5% (until Low Battery Warning)
Frequency 60Hz, ±0.5Hz (unless synchronized to utility)
Transfer Time 6-10 ms Typical
Overload Capacity AC Mode: 110% for 1-minute then shutdown, 150% Shutdown Immediately
DC Mode: 110% for 20-seconds then shutdown, 150% Shutdown Immediately
Protection Over-Current, Short-Circuit Protected and Latching Shutdown
Receptacles (NEMA) 8: 5-15R 6: 5-15/20R
1: L5-20R

What are the battery, surge, environmental, and physical specifications for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U?

Category Specification Details
BATTERY SYSTEM Battery Type Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid
Typical Recharge Time 8-hours to 90% capacity from a full load discharge
Typical Battery Life 3 to 5 years. Environmental factors affect battery life.
Battery Module Part # BM0072, BM0073, BM0074, BM0075
Runtime Full Load: 4-5 mins / Half Load: 14-15 mins (varies by model)
SURGE PROTECTION AND FILTERING UPS Surge Energy Rating 960 J
Surge Current Capability 6500 Amps total (one time 8 to 20us waveform)
Response Time 0 ns (instantaneous) normal mode; <5 ns common mode
Surge voltage let-through < 0.30%
Noise Filter >45db normal and common mode EMI/RFI suppression
Audible Noise at 1 m (3 ft.) <45 dBA
Network/Phone/Fax/Modem and Coax protection 1-in / 1-out ports provided
ENVIRONMENTAL Operating Temperature 0 to 40°C (+32 to +104°F)
Operating Elevation 0 to 3000m (0 to +10,000 ft)
Operating/Storage Humidity 5 – 95% Non-Condensing
Storage Temperature -15 to +45°C (+5 to +113°F)
Storage Elevation 0 to 15,000m (0 to +50,000 ft)
PHYSICAL Size – Net (L X W X H) PRO750/1000RT2U: 16.1 X 18.9 X 3.4″
PRO1500/2000RT2U: 20.1 X 18.9 X 3.4″
Weight – Net Ranges from 31.3 lbs (14.2 Kgs) to 62.8 lbs (28.5 Kgs) depending on model

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO2000RT2U (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.