Free English PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the important safety instructions for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
Please observe the following safety instructions when installing and operating your PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U:
Installation Environment:
• This UPS series is ONLY intended to be installed in an indoor temperature-controlled environment that is free of conductive contaminants.
• Do not use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA 75.
• Install the UPS system in a well-ventilated area, away from excess moisture, heat, dust, flammable gas, or explosives.
• The maximum ambient operating temperature for this UPS series is 40°C (0-40°C for Ambient Operation).
Ventilation:
• The external vents and openings on the UPS are provided for ventilation. To ensure reliable operation and protect the UPS from overheating, these vents and openings must not be blocked or covered.
• Leave adequate space (at least 20cm) at the front and rear of the UPS system for proper ventilation.
Electrical Connection:
• Connect the UPS to a two-pole, three-wire, grounded, utility power AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse).
• To reduce the risk of fire, connect only to a utility power circuit provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70.
• Do not use extension cords, adapter plugs, or surge strips.
Electrical Shock Prevention:
• To reduce the risk of electrical shock, the user must ensure that the combined sum of the AC leakage current does not exceed 3.5mA.
• To reduce the risk of electrical shock in conditions where the load equipment grounding cannot be verified, disconnect the UPS from the AC wall outlet before installing a computer interface cable. Reconnect the power cord only after all signaling connections are made.
• Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected.
Handling and Orientation:
• Do not mount the UPS system with its front or rear panel facing down at any angle.
• DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS. The mounting brackets are ONLY for securing the UPS to the rack.
• Before usage, you must allow the UPS system to adjust to room temperature (20°C-25°C or 68°F-77°F) for at least one hour to avoid moisture condensing inside the UPS.
Servicing:
• This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user-serviceable parts. Repairs and battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY.
How do I de-energize the outputs of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
To completely de-energize the outputs of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U, follow these steps:
1. If the UPS is on, press and release the On/Off/Test button during the audible alarm’s first beep to turn the UPS off.
2. Disconnect the UPS from the AC wall outlet.
3. To de-energize the UPS completely, disconnect the battery.
How do I use the On/Off/Test button on the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
The On/Off/Test button on your PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U has multiple functions:
Turn the UPS On: When the UPS is connected to an AC source and there is an acceptable AC voltage present, press and then release the On/Off/Test button during the audible alarm’s first beep. The UPS will turn on, provide an output, and power the load. It will then perform a five-second self-test.
Turn the UPS Off: When the UPS is in AC mode, press and then release the On/Off/Test button during the audible alarm’s first beep to turn the UPS off.
Perform a Self-Test: With the UPS in AC mode, press and hold the On/Off/Test button until the audible alarm sounds four beeps, and then release. The UPS will perform a ten-second self-test. During the test, the UPS will switch to Battery mode, the On-Battery icon will illuminate, and the audible alarm will sound.
What is the harmonic distortion of the output for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U series?
The output of this device is not sinusoidal. It has a voltage total harmonic distortion and maximum single harmonic distortion as shown in the table below:
| Model | PRO750RT2U | PRO1000RT2U | PRO1500RT2U | PRO2000RT2U |
|---|---|---|---|---|
| Total harmonic | 31.3% | 30.3% | 37.2% | 35.6% |
| Single harmonic | 14.5% | 14.9% | 18.7% | 15.7% |
What should I do after receiving my PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
After removing your UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned, please use the original packing material. Since the manufacturer is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS!
What do the icons and indicators on the control panel of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U mean?
The control panel on your PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U provides visual information through various icons and bar graphs:
Status Icons:
• AC mode icon: Illuminates when the UPS is on and operating in AC mode. It extinguishes when in Battery mode and blinks when the UPS is operating in AVR (Boost and Buck) mode.
• On-Battery icon: Illuminates when the UPS is operating in Battery mode and extinguishes when in AC mode.
• Weak/Bad Battery icon: Illuminates and displays an error code when the UPS detects a weak, bad, or disconnected battery. It is extinguished when the battery’s condition is good.
• Fault icon: Illuminates and displays an error code when the UPS detects an internal fault. It is extinguished when the UPS is operating properly.
• Site Wiring icon (SWF): Illuminates and displays an error code when the UPS detects a site wiring problem. It is extinguished when the UPS is connected to proper site wiring.
Bar Graphs and Indicators:
• Load Capacity Bar Graph: Displays the amount of load connected to the UPS in 20% increments (20%, 40%, 60%, 80%, 100%).
• Overload Indicator: When the load exceeds 110% of its power rating, the Overload and Fault icons will flash, an Overload error code will be displayed, and the UPS will sound a constant alarm.
• Battery Capacity Bar Graph: Displays the amount of battery capacity available in 20% increments (20%, 40%, 60%, 80%, 100%).
UPS Parameters (viewable via Scroll button):
• Input Voltage and Frequency
• Output Voltage and Frequency
• Connected load KVA and KW
• Estimated Runtime (minutes) in AC mode and Battery mode
LCD Backlight: The backlight illuminates for 20 seconds when the UPS switches to Battery mode and then turns off. When an event or error code occurs, the LCD backlight will turn on and remain on to alert the user.
What are the features of the rear panel of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
The rear panel of the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U includes the following components:
1. Input power cord: For connecting the UPS to utility power. The AC wall outlet should be near the UPS and easily accessible.
2. Input circuit breaker: Trips if the load exceeds the UPS’s power rating.
3. Coax connectors: For transient voltage surge suppression for cable modem, CATV converter, DSS receiver, or DVR.
4. Fan: For ventilation. The fan only operates during battery mode and AVR mode.
5. USB Communications Port: For UPS monitoring and control.
6. Battery Backup output receptacles: Wired into two segments (Load 1 & Load 2) to support the “Load Shedding Function”.
7. Always On Battery Backup output receptacles: These do not support the “Load Shedding Function”. The locking receptacle is only on the PRO2000RT2U model.
8. Option slot: For option cards.
9. Rackmount brackets: For mounting the UPS to the rack.
10. RJ11/45 modular connectors: For transient voltage surge suppression for 10/100/1000 Base-T Network/single line Phone/Fax/Modem.
11. RJ11 EPO (Emergency Power Off) Port: For UPS control. This connection is not for Telecommunication use.
What are the plug and receptacle types for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U series?
| Model # | Input Power Plug (All power cords are 10ft) |
Output Power Receptacles |
|---|---|---|
| PRO750RT2U | NEMA 5-15P | 6-NEMA 5-15R (Controllable) 2-NEMA 5-15R (Always On) |
| PRO1000RT2U | NEMA 5-15P | 6-NEMA 5-15R (Controllable) 2-NEMA 5-15R (Always On) |
| PRO1500RT2U | NEMA 5-15P | 6-NEMA 5-15R (Controllable) 2-NEMA 5-15R (Always On) |
| PRO2000RT2U | NEMA 5-20P | 6-NEMA 5-15/20R (Controllable) 1-NEMA L5-20R (Always On) |
What are the environmental requirements for installing the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
The PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U should be installed in an environment that meets the following criteria:
• Operating Temperature (Maximum): 40°C (+32 to +104°F)
• Operating Elevation: 0 to 3,000m (0 to +10,000 ft)
• Operating and Storage Relative Humidity: 95%, non-condensing
• Storage Temperature: -15 to +45°C (+5 to +113°F)
• Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
The UPS is intended for an indoor temperature-controlled environment free of conductive contaminants. Avoid extremely dusty/unclean areas, locations near heating devices, water, excessive humidity, or direct sunlight. Ensure good air circulation at all times.
How do I connect the batteries in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
This procedure should be performed by QUALIFIED SERVICE PERSONNEL ONLY. The UPS is shipped with the batteries disconnected and they must be connected before use.
1. Remove the UPS from the shipping box and place it on a flat surface. The UPS is extremely heavy; use two or more people.
2. Grasp the battery door on the left-hand side, pull it outward, and then set it aside. No tools are required for this step.
3. Verify proper polarity. Connect the battery connectors together. Some sparking may occur; this is normal.
4. Re-install the battery door on the UPS.
5. Connecting the batteries is complete.
How do I install the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U in a rack?
To install the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U in a standard 19″ (46.5cm) rack, follow these steps. The UPS is extremely heavy, so use two or more people for installation.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS. The mounting brackets are ONLY for securing the UPS to the rack.
1. Mount the UPS into the rack and secure it with the four retaining screws provided. Do not move the rack after the units have been installed, as the rack may become unstable due to the weight distribution.
2. The Rackmount Configuration is complete. You can now proceed with connecting your equipment.
How do I set up the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U in a tower configuration?
The PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U can be installed in an upright tower configuration using the provided tower brackets. The UPS is extremely heavy, so use two or more people for installation.
1. Once the location is determined, place the UPS on a flat surface. Remove the rackmount brackets from the UPS and then place the tower brackets in the desired location.
2. Rotate the LCD panel to be read in the upright position. There is a small slot on each side of the LCD panel. Insert a small flat head screwdriver into one of the small slots and gently pry the LCD outward. Position the LCD panel so that it reads upright, then gently press it back into the front panel.
3. Slide the UPS into the tower brackets. Make sure that the UPS is stable.
4. The Tower Configuration is complete. You can now proceed with connecting your equipment.
NOTE: The UPS must be installed in the proper upright position to avoid damaging the batteries. Once the UPS is placed in the tower brackets, looking at the front panel, the YELLOW Battery disconnected label on the top cover of the UPS MUST be on your left-hand side.
How do I mount the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U on a wall?
A wallmount bracket kit is available for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U. The kit includes two wall mounting brackets, ten retaining screws, and a wallmount template. The UPS is extremely heavy; use two or more people for installation.
1. Once the location has been determined, place the UPS on a flat surface and remove the rackmount brackets.
2. Rotate the LCD panel to read in the upright position. Insert a small flat head screwdriver into one of the small slots on the side of the LCD panel and gently pry it outward. Position it correctly, then press it back into the front panel.
3. Align the wall mounting brackets with the screw holes on the side panels of the UPS and attach them with the six retaining screws.
4. Use the template to mark the screw hole positions on the wall. Use caution and wear protective gear for your hands and eyes when operating power tools.
5. Attach the four retaining screws to the wall, ensuring they are screwed into structural material. Clean the area of any loose material. Do not tighten the screws all the way; leave approximately 3/8″ of the retaining screws sticking out.
6. Position the UPS so that the mounting bracket keyed holes line up with the four retaining screws. Slide the UPS down until it rests securely on the screws.
7. Tighten the four retaining screws to secure the UPS to the wall.
8. The Wallmount Configuration is complete. You may now connect your equipment.
NOTE: The UPS must be installed in the proper upright position to avoid damaging the batteries. When attached to the wall, looking at the front panel, the YELLOW Battery disconnected label on the top cover of the UPS MUST be on your left-hand side.
How do I connect equipment and power to the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
Connecting Equipment to the UPS:
Plug your equipment into the output receptacles on the rear panel of the UPS. Ensure that you do not exceed the maximum output rating of the UPS. DO NOT PLUG EXTENSION CORDS, ADAPTER PLUGS, OR SURGE STRIPS into the output receptacles.
CAUTION! DO NOT connect a laser printer, copier, vacuum cleaner, or any other large electrical device into the output receptacles of the UPS.
Connecting the UPS to an AC Source:
Plug the UPS into a two-pole, three-wire, grounded receptacle only. The AC wall outlet shall be near the UPS and easily accessible. DO NOT PLUG THE UPS INTO EXTENSION CORDS, ADAPTER PLUGS, SURGE STRIPS, OR POWER STRIPS. Do not cut the input plug off and attempt to hardwire the UPS, as doing so will void the warranty.
Checking the Site Wiring Fault:
After plugging the UPS into the AC wall outlet, check the Site Wiring Fault (SWF) icon on the front panel. If the SWF icon is illuminated, the UPS is plugged into an improperly wired AC wall outlet. If the UPS indicates a Site Wiring Fault (SWF), have a Qualified Electrician correct the problem.
Charging the Battery:
The UPS will charge the internal batteries whenever it is connected to an AC source with an acceptable voltage (90-150VAC). It is recommended that the batteries be charged for a minimum of 4 hours before use. If the UPS is going to be stored for a prolonged period, the batteries must be recharged for at least twenty-four hours every ninety days.
How do the different alarms on the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U function?
The PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U uses audible alarms to alert you to different conditions:
• On Battery: When the UPS is operating on batteries, the audible alarm will sound one beep every 10 seconds. The AC mode icon will extinguish, and the On-Battery icon will illuminate.
• Low Battery Warning: When the batteries reach the predetermined low level (approximately two minutes of runtime remaining), the audible alarm will sound two beeps every five seconds. The LCD will display error code E07. This alarm cannot be silenced.
• Weak/Bad Battery: If the battery is weak, bad, or disconnected, the Weak/Bad Battery icon will illuminate, the LCD will display error code E06, and the audible alarm will sound three beeps every five minutes until the battery is reconnected or replaced.
• Overload: When the connected load exceeds the UPS’s power rating, the Overload icon will illuminate, the LCD will display error code E02, and the audible alarm will sound continuously in both AC and Battery modes. This alarm will remain on until the excess load is removed.
• UPS Fault: When the UPS detects an internal fault, the Fault icon will illuminate, an error code will be displayed, the audible alarm will sound continuously, and the output will be turned off. In some cases, this may be cleared by turning the UPS off and then on.
What are the Load Shedding and Emergency Power Off (EPO) functions on the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
Load Shedding Function:
The output receptacles are electrically wired into two segments (labeled Load 1 & Load 2). You can control these two segments individually or both at the same time using the Power Monitoring Software or an SNMP card. This allows for non-critical loads to be shut down to preserve battery runtime for more critical equipment. The output segment labeled ‘Always On’ does not support the Load Shedding function.
Emergency Power Off (EPO) Function:
Connect one end of an RJ11 cable to the EPO port and the other end to an EPO switch. In either AC or Battery mode, shorting pin 4 to pin 5 for approximately 0.5 seconds will shut down the UPS. The UPS must be turned on to restart. The LCD screen will display ‘EPo’ when this function is active.
How do I troubleshoot common issues with the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
| Symptom / Error Code | Cause / What To Do |
|---|---|
| UPS will not turn on. | Press the On/Off/Test button and release after one beep. |
| UPS operates in battery mode only, even though there is AC present. | Reset the input circuit breaker by pressing the plunger back in. If the input circuit breaker trips after the UPS restarts, reduce the load on the UPS. |
| The AC mode icon is blinking and the alarm is silent. | The UPS is in either the Boost or the Buck mode. It is performing its intended function. |
| UPS does not provide expected runtime. | Charge the batteries for 8-hours and retest. If the runtime is still less than expected, the batteries may need to be replaced. |
| The AC mode icon is illuminated, but there is no output. | Disconnect the computer cable from the UPS, press the On button. If UPS works normally, the software had control of the UPS. |
| Fault icon is illuminated and a constant alarm. | The UPS has an internal problem, call for service. |
| Error Code: E01. UPS is shutdown. | The UPS has detected a short-circuit on its output. Check the attached load. |
| Error Code: E02. Overload icon is illuminated and a constant alarm. | Check the specifications and remove part of the load. If the UPS shuts down because of an Overload, the UPS must perform an Inverter function or a Self Test to clear the Overload Alarm. |
| Error Code: E03. Over Temperature Shutdown. | The internal or ambient temperature has exceeded the safe operating range for the UPS. Check the specifications. |
| Error Code: E04: Inverter/Output Failure Shutdown. | The UPS has an internal fault, call for service. |
| Error Code: E05. Charger Failure Warning. | The charger has failed, call for service. |
| Error Code: E06. Weak/Bad Battery icon is illuminated. | Check the battery connections, charge the batteries for 8-hours and retest, or replace the batteries. |
| Error Code: E07. Low Battery Warning. | The UPS’s battery reserve is low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion. |
| Error Code: E08. SWF icon is illuminated. | Have a qualified electrician correct the service wiring. |
What precautions should I take when replacing the battery in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY. Observe these precautions:
General Warnings:
• The UPS contains potentially hazardous voltages. Do not disassemble the UPS beyond the battery replacement procedure.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
• Do not dispose of batteries in a fire, as they may explode. The batteries are recyclable and contain lead; dispose of them properly according to local codes.
Electrical Shock & Burn Prevention:
• The battery system can present a risk of electrical shock and produce sufficient current to burn wire or tools rapidly.
• Remove watches, rings, or other metal objects.
• Use hand tools with insulated handles.
• Wear protective eye gear (goggles), rubber gloves, and boots.
• Do not lay tools or other metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting the battery terminals.
• Determine if the battery is inadvertently grounded. If it is, remove the source of the grounding. Contact with any part of a grounded battery can result in an electrical shock.
Battery Type:
• Replace the batteries with the same number and type as originally installed. These UPSs contain sealed non-spillable maintenance-free lead-acid batteries with pressure-operated vents.
What are the replacement battery part numbers for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U series?
| Model # | PRO750RT2U | PRO1000RT2U | PRO1500RT2U | PRO2000RT2U |
|---|---|---|---|---|
| Battery Module Part # | BM0072 | BM0073 | BM0074 | BM0075 |
What is the procedure for replacing the battery in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
The batteries in the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U are hot-swappable, meaning they can be replaced without powering down the entire UPS system. To hot-swap, start with step 6. For a full power-down replacement, start with step 1.
1. Turn off the equipment that is plugged into the output of the UPS.
2. Press the On/Off/Test Button on the front panel to turn the UPS off.
3. Unplug the UPS’s AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Grasp the battery door on the left-hand side, pull it outward, and then set it aside. No tools are required.
7. Disconnect the battery connectors.
8. Remove the four retaining screws for the battery retaining bracket.
9. Remove the battery retaining bracket and set it aside.
10. Grasp the battery pull tab and gently pull the battery module out of the UPS and set it aside. The battery module is heavy, use caution. DO NOT use the battery wires to pull the module out.
11. Slide the new battery module into the UPS.
12. Re-install the battery retaining bracket.
13. Re-install the four retaining screws for the battery retaining bracket.
14. Verify proper polarity. Reconnect the battery connectors together. Some sparking might occur; this is normal.
15. Re-install the battery door on the UPS.
16. Properly dispose of the old batteries at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.
17. The UPS is now ready for normal operation.
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the battery module, you must initiate a self-test to clear the alarm. To initiate a self-test, see section 4 “TEST BUTTON”.
What are the system specifications for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U series?
| PRO750RT2U | PRO1000RT2U | PRO1500RT2U | PRO2000RT2U | |
|---|---|---|---|---|
| SYSTEM SPECIFICATIONS | ||||
| Topology | Line-Interactive, Simulated Sine Wave | |||
| Maximum Power Capacity | 750VA / 525W | 1000VA / 700W | 1500VA / 1050W | 2000VA / 1400W |
| INPUT | ||||
| Number of Phase | Single (1Ø2W +G) | |||
| Nominal Voltage | 120VAC | |||
| Acceptable Input voltage | 0 – 150VAC | |||
| Voltage Range | 90 – 150VAC | |||
| Frequency Limits | 60 Hz, ±6Hz | |||
| Low Voltage Transfer Point | 89V resets to Utility Power at 94V or higher | |||
| High Voltage Transfer Point | 151V resets to Utility Power at 146V or lower | |||
| Protection | Resettable Circuit Breaker | |||
| Power Cord (10ft) | NEMA 5-15P | NEMA 5-20P | ||
| OUTPUT NON-BATTERY OPERATION | ||||
| Voltage Range | 103 – 136VAC | |||
| Voltage Regulation | 120VAC: ±13.3% | |||
| Frequency Range | 60Hz: 54 – 66Hz | |||
| Efficiency (Line Mode) | >96% (Full Load) | |||
| OUTPUT BATTERY OPERATION | ||||
| Waveform Type | Simulated Sine Wave | |||
| Nominal Voltage | 120VAC | |||
| Voltage Regulation | 120VAC ±5% (until Low Battery Warning) | |||
| Frequency | 60Hz, ±0.5Hz (unless synchronized to utility) | |||
| Transfer Time | 6-10 ms Typical | |||
| Overload Capacity | AC Mode: 110% for 1-minute then shutdown, 150% Shutdown Immediately DC Mode: 110% for 20-seconds then shutdown, 150% Shutdown Immediately |
|||
| Protection | Over-Current, Short-Circuit Protected and Latching Shutdown | |||
| Receptacles (NEMA) | 8: 5-15R | 6: 5-15/20R 1: L5-20R |
||
What are the battery specifications for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U series?
| PRO750RT2U | PRO1000RT2U | PRO1500RT2U | PRO2000RT2U | |
|---|---|---|---|---|
| Battery Type | Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid | |||
| Typical Recharge Time | 8-hours to 90% capacity from a full load discharge | |||
| Typical Battery Life | 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life. | |||
| Battery Module Part # | BM0072 | BM0073 | BM0074 | BM0075 |
| Runtime: Full Load (minutes) | 5 | 4 | 4 | 4 |
| Runtime: Half Load (minutes) | 15 | 14 | 14 | 14 |
What are the surge protection and filtering specifications for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U?
| UPS Surge Energy Rating | 960 J |
| Surge Current Capability | 6500 Amps total (one time 8 to 20us waveform) |
| Response Time | 0 ns (instantaneous) normal mode; <5 ns common mode |
| Surge voltage let-through (as a percentage of an applied ANSI C62.41 Cat. A ±2 kV) | < 0.30% |
| Noise Filter | >45db normal and common mode EMI/RFI suppression |
| Audible Noise at 1 m (3 ft.) | <45 dBA |
| Network/Phone/Fax/Modem transient voltage surge protection | 10/100/1000 Base-T network, single line phone, Fax or Modem. 1-in / 1-out combo RJ11/45 connectors |
| Coax transient voltage surge protection | Cable modem, CATV converter, DSS receiver, DVR. 1-in / 1-out |
What are the physical specifications for the PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U series?
| PRO750RT2U / PRO1000RT2U | PRO1500RT2U / PRO2000RT2U | |
|---|---|---|
| Size – Net (L X W X H) | 16.1 X 18.9 X 3.4″ 410 X 480.6 X 86.2 mm |
20.1 X 18.9 X 3.4″ 510 X 480.6 X 86.2 mm |
| Size – Shipping (L X W X H) | 22.4 X 21.7 X 9.4″ 570 X 550 X 240 mm |
26.4 X 22.4 X 9.4″ 670 X 570 X 240 mm |
| PRO750RT2U | PRO1000RT2U | PRO1500RT2U | PRO2000RT2U | |
|---|---|---|---|---|
| Weight – Net | 31.3 lbs / 14.2 Kgs | 35.7 lbs / 16.2 Kgs | 48.7 lbs / 22.1 Kgs | 62.8 lbs / 28.5 Kgs |
| Weight – Shipping | 37.5 lbs / 17.0 Kgs | 41.9 lbs / 19.0 Kgs | 56.4 lbs / 25.6 Kgs | 70.5 lbs / 32.0 Kgs |
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD PARA SYSTEMS MINUTEMAN PRO-RT 2U PRO750RT2U (01) PDF DOCUMENT