How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What are the main features of the CARRIER CONNECT 33TCSPL-4 thermostat?
The CARRIER CONNECT 33TCSPL-4 thermostat includes the following features:
• Control of heating, cooling, and fan solid state 24 Vac outputs
• Space temperature sensing (> 0.5°F accuracy from 60°F to 90°F)
• Outdoor temperature sensing using a 10K @ 25°C J Curve (type II) thermistor or Wi-Fi outdoor temperature via GPS location services
• Humidity sensing and control
• Remote humidity sensing from a 33ZCSENDRH-02 Humidity Duct Sensor or 33ZCSENSRH-02 wall sensor
• Remote CO2 sensing from a 0-10 vdc or 4-20 mA sensor
• Wi-Fi connectivity (supports 802.11 a/b/g/n standards)
• Cloud Connectivity using the Carrier Connect mobile app (iOS and Android)
• Optimized installation with “finger friendly” spring-loaded connectors for 16 to 24 AWG wire
• Optimized boot time (5 seconds total)
• 4.3″ segment display
• Thirteen touch points for display buttons
• OTA functionality (reprogrammable via Wi-Fi)
What are the technical specifications of the CARRIER CONNECT 33TCSPL-4 thermostat?
| Power requirements | 24 Vac +/- 10% @ 3VA |
| Network Requirements | Wi-Fi connectivity supports Wi-Fi: 802.11 a/b/g/n standards on 2.4 GHz networks |
| Environmental temperature range | Operating: 32° to 104°F (0° to 40°C) Storage: -40° to 135°F (-40° to 57°C) |
| Humidity range | Operating: 10% to 95%, non-condensing, 32° to 104°F (0° to +40°C) Storage: 10% to 95%, non-condensing |
| Connections | Connectors P104 and P105. 2 banks of “finger friendly” spring type terminal blocks intended to be wired by the end-user or installer |
| Inputs | • C – connection • R – connection • H – 0-10 Volt input • T – remote thermistor |
| Outputs | Connections: Y3, O/B, Y2, Y1, G, W1, and W2 |
| Communications | 485 signal: A+ and B |
| Mounting | Standard 4 x 2 in. electrical box using the 6-32 x 1/2 in. mounting screws and plastic wall anchors provided |
| Overall dimensions | Width: 5.15 in. (13.1 cm) Height: 3.25 in. (8.2 cm) Depth: 0.95 in. (2.4 cm) |
| BACnet Support | Conforms to the BACnet Application Specific Controller (B-ASC) Device Profile as defined in ANSI/ ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 14 |
| Listed by | FCC Part 15, Subpart J compliant |
Which terminals on the CARRIER CONNECT 33TCSPL-4 are used for outputs and what do they control?
| Terminal | Output for… | is energized when the thermostat has a… |
|---|---|---|
| G | Fan | fan demand |
| W1 | First Stage Heat or AUX Heat | first stage heat or aux heat demand |
| W2 | Second stage heat or AUX heat | second stage heat or aux heat demand |
| Y1 | First stage cooling or HP heating output | first stage cooling or HP heating output |
| Y2 | Second Stage Cooling or HP Heating Output | second stage cooling or HP heating demand |
| O | Reversing Valve Output | reversing valve demand |
| Y3 | Third Stage AC Cooling | third stage AC cooling demand |
| O or Y3 or W2 | Humidifier Output | humidification demand NOTE: You can connect to any of these 3 outputs that are unused and select it in the system settings menu. |
| O, Y3, and W2 | HumidiMiZer™ demand | HumidiMiZer™ demand NOTE: You can connect to any of these 3 terminals that are unused and select it in the system settings menu. |
| O, Y3, and W2 | Economizer or Occupancy | the thermostat is running in occupied mode, as determined by the program, the occupancy input, BMS occupancy, or an override condition NOTE: You can connect to any of these 3 terminals that are unused and select it in the system settings menu. |
How do I connect a remote input like a sensor or contacts to the CARRIER CONNECT 33TCSPL-4 thermostat?
To connect a remote input, use the specified type of wire and cable for maximum signal integrity. The remote sensor input terminals are C, R, H, and T.
Wire and Cable Specifications:
| Power | N/A |
| Description | Stranded, twisted pair |
| Conductor | If < 100 ft (30.5 meters) 22 AWG, unshielded If > 100 ft (30.5 meters) 22 AWG, shielded |
| Maximum length | 500 feet (152 meters) |
| Insulation | Plenum rated |
| Thermistor | 10K Type II (CP/MCI) |
You can use the remote sensor inputs for:
• OAT
• T55
• SAT
• Occupancy contacts
• Econ Fault
How do I wire the CARRIER CONNECT 33TCSPL-4 thermostat for space temperature sensor averaging?
To average the temperature reading across multiple sensors, you can wire them in a series-parallel combination. This ensures the thermostat receives an averaged resistance value, translating to an averaged temperature reading.
For 4 Sensors:
Wire the four sensors in a series-parallel circuit. This typically involves creating two pairs of sensors wired in series, and then wiring these two pairs in parallel to each other. Connect the final leads to the thermostat’s remote sensor terminals.
For 9 Sensors:
Wire the nine sensors in a series-parallel circuit. This involves creating three sets of three sensors wired in series. Then, wire these three sets in parallel to each other. Connect the final leads to the thermostat’s remote sensor terminals.
How do I wire the CARRIER CONNECT 33TCSPL-4 for BACnet communication?
For BACnet communication, use the specified wire type for maximum signal integrity and connect it to the A+ and B- terminals on the thermostat. Do not terminate the shield at the thermostat and ensure you maintain the same polarity.
Wire and Cable Specifications:
| Cable | 22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire |
| Maximum length | 2000 feet (610 meters) per segment |
| Baud rate | 9600 bps, 19.2 kbps, 38.4 kpbs, or 76.8 kbps, 115.2 kbps |
How do I register and set up a mobile device for the CARRIER CONNECT 33TCSPL-4 thermostat?
Downloading the Connect™ App provides enhanced access to your device. The App is available for Apple IOS® (7.0 or later) or Android (4.2 or later) devices. Search for “Carrier Connect™ Thermostat”.
1. After downloading the Connect™ App, select USER SETUP and Register New Account.
2. Enter an email address that you can access on your mobile device to receive the confirmation email.
3. Select SETUP NEW THERMOSTAT and follow the Connect™ App instructions.
4. After registering the thermostat, enter the servicing contractor’s name and phone number on the SERVICE INFO screen.
5. On the THERMOSTATS screen, select the thermostat from the list and the mobile app’s HOME screen will appear.
What can I do with the Carrier Connect website or app for my CARRIER CONNECT 33TCSPL-4?
After you register for an account, you can access the thermostat through the app or website to perform the following actions:
• Monitor the thermostat operation
• Set up occupied and unoccupied (holiday) schedules
• Adjust setpoints
• Share thermostat access with other users
• Create groups of thermostats that you have registered
• Create groups of thermostats that other owners have shared with you
• Get online product information
• Find local dealer support
The app and website have several screens to manage your thermostat:
| Screens | Use to… |
| SETPOINTS | Adjust the occupied and unoccupied setpoints by selecting each temperature. |
| FAN | View and modify fan settings. The default is AUTO. You can also select ON for continuous fan operation. |
| HUMIDITY | Adjust the thermostat’s humidify and dehumidify setpoints. |
| PROGRAM | Set Occupied and Unoccupied start times, adjust times in 15-minute increments, copy schedules to other days, and adjust setpoints for each period. (Not available in non-programmable mode). |
| HOLIDAY | Set HOLIDAY (unoccupied) periods. Options include setting a length from 1 to 365 days, same day of each week, or a specific day of a specific week. |
| SETTINGS | Enter the name and location of the thermostat. You can also enter an email address for alerts and a mobile phone number for text alerts. |
| ALERTS | Displays a list of alerts that have been flagged in the thermostat. |
| SERVICE | Displays the name and phone number of the service company responsible for servicing the system. |
| CO2 | Displays a graph for up to 30 days of CO2 history, including the high and average for today and the last 30 days. |
How do I use the user interface on the CARRIER CONNECT 33TCSPL-4 thermostat?
Dormant Screen
This screen is displayed when you are not interacting with the thermostat. It shows the room temperature prominently. A banner scrolls through the date, time, humidity, outdoor air temperature, and any active faults. Touching the screen transitions to the Home screen (or Lock screen if enabled).
Home Screen
This is the main interaction screen. It displays the current space temperature, mode, fan status, and heating/cooling setpoints. A banner at the top cycles system information. From the home screen, you can:
• change the mode
• force an occupied or unoccupied override
• change the setpoints
• set the filter reminder
• enter the menu for more advanced functionality
Accessing Schedules and Settings:
• Access the program schedule by holding the bottom middle button (labeled OCC, UNOCC, or RESUME SCHEDULE) for 3 seconds.
• Access the installer configurations by setting the MODE to OFF and holding the MENU button for 5 seconds.
How do I use the Occupancy/Enter PIN screen on the CARRIER CONNECT 33TCSPL-4?
The Occupancy/ENTER PIN screen is displayed when you touch the dormant screen if the lockout feature is enabled.
• To enter the PIN: Press one of the 3 digits in the center of the display, then use the up or down arrows to adjust the value. Repeat for the other digits. When the 3-digit PIN is correct, press SAVE.
• Temporary Override: This screen has an OCC/UNOCC button to temporarily override the program schedule settings without knowing the PIN. This override remains active until the next scheduled period or until the MAX HOLD time expires.
• Correct PIN: If the correct PIN is entered, the thermostat displays the home screen and remains unlocked until it returns to the dormant screen.
• Incorrect PIN: If an incorrect PIN is entered, an “INVALID PIN” message displays for 3 seconds. If an invalid PIN is entered 5 consecutive times, the thermostat is locked out for 15 minutes. The banner will display “LOCKOUT” and the remaining time.
How do I change the setpoints on the CARRIER CONNECT 33TCSPL-4?
You can change the setpoints from the home screen using the up and down arrows.
• OFF mode: Setpoints, occupancy button, and arrows do not display.
• HEAT or EHEAT mode: Only the heat setpoint displays and can be adjusted.
• COOL mode: Only the cool setpoint displays and can be adjusted.
• AUTO mode: Both setpoints display. The up and down arrows adjust the last setpoint that was changed. To adjust the opposite setpoint, touch the setpoint value on the display (e.g., touch “HEAT TO 70”) to make it active, then use the arrows. The setpoints maintain a 2-degree deadband.
Overriding the Schedule
Pressing the center button at the bottom of the display (e.g., UNOCC) changes the setpoints to the program schedule’s occupied or unoccupied settings. When an override is active, the button label changes to RESUME SCHEDULE, and the banner shows the time remaining in the override. The thermostat returns to the schedule at the next programmed period, when the max hold timer expires, or when you press RESUME SCHEDULE.
How do I change the fan setting on the CARRIER CONNECT 33TCSPL-4?
The fan’s current state is displayed on the home screen above the MENU button. To change the fan setting:
1. Press MENU. The current fan setting is displayed.
2. Press SELECT.
3. Use the up and down arrows to toggle the fan setting between AUTO and ON.
4. Press SAVE.
• ON: Specifies continuous fan that is always running.
• AUTO: Specifies that the fan only runs while actively heating or cooling.
If the fan setting differs from the program schedule, the banner displays “FAN OVERRIDE”.
How do I change the system mode on the CARRIER CONNECT 33TCSPL-4?
You can change the mode from the home screen by pressing the MODE button. Repeatedly pressing the button cycles through the available modes (e.g., OFF, HEAT, COOL, AUTO, EHEAT). Some modes may not be available based on the installer configuration.
Changing from one mode to another does not affect operation until the selection has remained constant for at least 5 seconds. This allows the system to satisfy any MINIMUM ON timer requirements and then restart the MINIMUM OFF timer before turning on equipment in the new mode.
How do I use the menu for advanced features on the CARRIER CONNECT 33TCSPL-4?
The menu allows access to more advanced features of the thermostat.
1. When you press the MENU button, the first menu option is CURRENT FAN.
2. Press SELECT to activate the up and down arrows for that setting.
3. Press the up or down arrows to advance through the different menu options to view or change the value for each setting.
• You must press SAVE to store the current value and return to the SELECT screen.
• Press CANCEL to revert the value to the last saved value and return to the SELECT screen.
• Press DEFAULT to set the value to the factory default and then press SAVE to store it.
How do I test the HVAC system with the CARRIER CONNECT 33TCSPL-4?
The installer can use the Installer Test setting to test the HVAC system.
1. From the installer settings menu, navigate to INSTALLER TEST and press SELECT to open it. The HOME and SELECT buttons are replaced with MODE and CANCEL buttons.
2. Press MODE to cycle through OFF, COOL, HEAT, and EHEAT. The availability of modes depends on the installer configuration.
• The selected MODE operates each equipment stage for 3 minutes.
• The center of the display shows a countdown timer for the current stage.
• When the countdown reaches zero, if another stage exists, the banner text changes to 2ND STAGE and a new 180-second countdown starts. If no other stage exists, the test cycle ends and the MODE is set to OFF.
• During HEAT or EHEAT modes with a configured humidifier, the humidifier output is energized.
• During COOL mode with a configured HumidiMiZer™, the dehumidifier output is energized.
3. Press CANCEL to turn off the currently running equipment and return to the installer menu.
The INSTALLER TEST will terminate after 20 minutes of inactivity, and the home screen will be displayed.
How do I restore the CARRIER CONNECT 33TCSPL-4 to factory default settings?
This setting allows the installer to reset all system settings back to factory default values.
From the RESTORE DEFAULTS screen in the installer menu, press and hold the DEFAULT button to start a 5-second countdown. At the end of 5 seconds, the factory settings are restored. You can release the DEFAULT button at any time before 5 seconds to cancel the countdown.
After the settings are restored, the control returns to the BACNET ENABLE screen to allow the installer to properly configure the thermostat.
Factory Defaults:
| HEATING EQUIP TYPE | GAS |
| HEATING EQUIP STAGES | 1 |
| COMPRESSOR EQUIP TYPE | A/C |
| COMPRESSOR EQUIP STAGES | 1 |
| AUTO ALLOWED? | YES |
| AUTO CHANGEOVER | 30 MIN |
| PROG OR NON-PROG | PROG |
| MAX TEMP HOLD TIME | 2 |
| FAHRENHEIT OR CELSIUS | °F |
| SMART RECOVERY | 30 |
| FAN ON WITH W | YES |
| REVERSING VALVE | COOL |
| SPACE TEMP OFFSET | OFF |
| SPACE HUM OFFSET | 0% |
| HUM SOURCE | STAT |
| REMOTE HUM SCALING | 2-10 |
| REMOTE SENSOR | NONE |
| COOL LOCKOUT | OFF |
| LOW COOL LOCKOUT TEMP | OFF |
| LOW HEAT LOCKOUT TEMP | OFF |
| TIME B/W FUEL TYPES | 15 MIN |
| CYCLES PER HOUR | 4 |
| HUMIDIFIER | NO |
| DEHUMIDIFIER | NO |
| MAX HEAT SETPOINT | 88°F |
| MIN COOL SETPOINT | 52°F |
| AUX HEAT LOCKOUT | OFF |
| HP LOCKOUT | OFF |
| STAGE DELAY | 10 MIN |
| FORCED STAGE UP | 30 MIN |
| DIFFERENTIAL | 1.0°F |
| AIR FILTER REMINDER | 3000 HRS |
| OCCUPANCY OUTPUT | OFF |
| OCCUPANCY INPUT | OCCUPIED |
| BACNET ENABLE | NO |
| MSTP BAUD RATE | 76.8k |
| MSTP MAC | 1 |
| BACNET UTC OFFSET | 5h, 0min (EST) |
| MSTP MAX MASTER | 127 |
| DEVICE ID | 160000 + last 4 of S/N |
| DEVICE NAME | DEVICE16 + last 4 of S/N |
| DEVICE LOCATION | LOCATION |
| DEVICE DESCRIPTION | DESCRIPTION |
| BACNET BMS OCCUPANCY | NO |
| BACNET CONFIG WRITE ENABLE | NO |
| NETWORK GP OUT TIMEOUT | 2 MIN |
| NETWORK GP Y3 MODE | OFF |
| NETWORK GP W2 MODE | OFF |
| NETWORK GP OB MODE | OFF |
How do I set up Wi-Fi on the CARRIER CONNECT 33TCSPL-4 thermostat?
To display the SETUP WI-FI screen, press the Wi-Fi icon on the home screen.
Connect to a network:
If the thermostat is not connected to a Wi-Fi network and NO is displayed on the SETUP WIFI screen, follow these steps:
1. Press the SELECT button.
2. Change NO to YES.
3. Press SAVE.
This puts the thermostat into the setup mode, ready to receive Wi-Fi join commands from the Carrier Connect Mobile App. When the thermostat is in setup mode and not connected, the SSID will be a factory-configured value starting with “CMML” followed by 12 numbers. You will need these 12 digits to connect via the mobile app.
What do the timers and deadband settings on the CARRIER CONNECT 33TCSPL-4 mean?
MINIMUM OFF timer
Once a heating or cooling demand is satisfied, this timer is set to a 300-second (5 minutes) value and counts down. Heating and cooling outputs are de-energized for the entire duration of this timer to prevent short-cycling of the equipment.
MINIMUM ON timer
Once a heating or cooling output becomes active, this 5-minute timer begins to count down. The output will not de-energize until the timer reaches zero and the demand is satisfied. If the user changes the setpoint to satisfy the demand, this timer is ignored, and the equipment turns off.
Non-volatile memory
The thermostat stores settings in non-volatile memory to ensure they remain after a power outage. Stored items include: Installer settings, Menu settings, Program schedule, Date and time, Software information, Dealer information, and Fault/system event information.
Deadband
The thermostat controls the number of degrees between the heating and cooling setpoints. The deadband setting is fixed at 2°F. If a user changes a setpoint that violates this deadband, the opposite mode setpoint is automatically “pushed” to maintain the 2°F separation.
What do the faults and system events on the CARRIER CONNECT 33TCSPL-4 mean?
Faults and system events are displayed in the home and dormant screen banners. A history of the 5 most recent events can be viewed in the Carrier Connect mobile app under Alerts.
| Faults / Events | Description |
|---|---|
| ID TEMP SENSOR HIGH | Fault becomes active when main thermistor reads > 100°F. Cleared when temperature ≤ 99°F. |
| ID TEMP SENSOR LOW | Fault becomes active when main thermistor reads < 39°F. Cleared when temperature ≥ 40°F. |
| REMOTE SENSOR HIGH | Remote temperature > 122°F; only flagged if remote sensor is set to INDOOR or AVERAGE. |
| REMOTE SENSOR LOW | Remote temperature = 0°F; only flagged if remote sensor is set to INDOOR or AVERAGE. |
| ID TEMP RANGE HIGH | In cooling mode, space temperature is greater than the cool setpoint plus the Maximum Setpoint Error for a specified time. |
| ID TEMP RANGE LOW | In heating mode, space temperature is less than the heat setpoint minus the Maximum Setpoint Error for a specified time. |
| HUM SENSOR FAILURE | Humidity sensor timed out (reading is > 99% or 0%). |
| HUMIDITY RANGE HIGH | Humidity reading is > 90%. |
| HUMIDITY RANGE LOW | Humidity reading is < 10%. |
| OUTDOOR TEMP FAILURE | OD temp > 127°F or < -60°F. |
| NO WI-FI SERVER | Not connected to Ayla server. |
| NO WI-FI ROUTER | Router signal strength is zero (not connected). |
| WI-FI HARDWARE FAULT | Communications error occurred with Wi-Fi module. |
| LOCKOUT 5 WRONG PINS | An incorrect PIN was entered 5 consecutive times. |
| ECONOMIZER FAULT | Remote sensor is set to ECFL and there is a short between terminals T and C. |
| HIGH CO2 | CO2 is above the programmed threshold (default 1100 PPM). |
| System Events | |
| FILTER REMINDER | Filter change reminder is active (run hours have expired or remote input shorted). |