What are the safety precautions regarding writing to the EEPROM of the TOSHIBA TOSVERT VF-AS3?
Do not use application of writing into inverter parameters more than 100,000 times for the TOSHIBA TOSVERT VF-AS3. The Life of EEPROM is approximately 100,000 times. Frequent writing to the EEPROM of inverter will cause a memory corruption.
What steps must be performed before wiring and installation of the TOSHIBA TOSVERT VF-AS3 to prevent electric shock?
The following steps must be performed before wiring and installation for the TOSHIBA TOSVERT VF-AS3:
Turn off all input power, wait at least 15 minutes, and confirm that the charge lamp of the drive is no longer lit.
If steps above are not properly performed, this can result in electric shock.
What mandatory safety measures should be used in the system with the TOSHIBA TOSVERT VF-AS3 to prevent serious accidents due to option malfunctions?
Use an emergency stop device and an additional safety device in your system to prevent serious accident due to the option malfunctions of the TOSHIBA TOSVERT VF-AS3.
Usage without any emergency stop device or any additional safety device can result in accident or injury.
What is prohibited regarding RS485 communication cable connections on the TOSHIBA TOSVERT VF-AS3?
Do not connect RS485 communication cable into Ethernet port on the TOSHIBA TOSVERT VF-AS3. Erroneous connection will result in failure.
What mandatory step should be taken regarding the power supply for the TOSHIBA TOSVERT VF-AS3 in case of an emergency stop from an external controller?
Insert an electromagnetic contactor between the inverter and the power supply so that the machine can be stopped without fail from an external controller in case of an emergency for the TOSHIBA TOSVERT VF-AS3.
What function should be set up on the TOSHIBA TOSVERT VF-AS3 to stop the inverter when it is deactivated by an unusual event?
Set up “Communication error trip function (see below)” to stop the TOSHIBA TOSVERT VF-AS3 when the device is deactivated by an unusual event such as tripping, an operating error, power outage, failure, etc. This includes Network Time-Out, Inverter operation at disconnection, Preset speed operation selection.
Deactivated the device may cause an accident, if the “Communication error trip function” is not properly set up.
What are the specifications for the embedded ethernet module of the TOSHIBA TOSVERT VF-AS3?
The embedded ethernet module specifications for the TOSHIBA TOSVERT VF-AS3 are as follows:
| Item | Specification |
|---|---|
| Ethernet connector | Dual RJ45 shielded connector |
| Supported topology | Daisy chain topology, Star topology |
| Supported network | Modbus TCP / EtherNet/IP |
| Indicator | 4 LEDs indicating the communication status and error status. |
What are the Modbus TCP supported functions and command reception time for the TOSHIBA TOSVERT VF-AS3 network specifications?
The network specifications for Modbus TCP on the TOSHIBA TOSVERT VF-AS3 are as follows:
| Item | Specification | |
|---|---|---|
| Modbus TCP | Supported function | Read Holding Registers (0x03) |
| Write Single Register (0x06) | ||
| Write Multiple Registers (0x10) | ||
| Read/Write Multiple Registers (0x17) with I/O scanning | ||
| Read Device Identification (0x2B) | ||
| Command reception time | About 5ms * |
* Command reception time is until the inverter is operated by RUN command from network.
What are the supported objects and communication specifications for EtherNet/IP on the TOSHIBA TOSVERT VF-AS3 (CPU1 version V108 or more)?
The EtherNet/IP specifications for the TOSHIBA TOSVERT VF-AS3 (CPU1 version V108 or more) are as follows:
| Item | Specification | |
|---|---|---|
| EtherNet/IP (CPU1 version V108 or more) | Supported Object | Identity Object (0x01) |
| Message Router Object (0x02) | ||
| Assembly Object (0x04) | ||
| Connection Manager Object (0x06) | ||
| Motor Data Object (0x28) | ||
| Control Supervisor Object (0x29) | ||
| AC/DC Drive Object (0x2A) | ||
| Parameter access 1 Object (0x64) | ||
| Parameter access 2 Object (0x65) | ||
| Port Object (0xF4) | ||
| TCP/IP Interface Object (0xF5) | ||
| Ethernet Link Object (0xF6) | ||
| I/O assembly instances | 20/70, 21/71, 22/72, 23/73 (AC Drive Device profile) 100/150, 101/151, 102/152, 105/155, 107/157 (Vender specification) | |
| Command reception time | About 5ms * | |
| Ethernet | Baud rate | Auto negotiation (10/100Mbps, Full/Half duplex) |
| IP configuration mode | Fixed, BOOTP, DHCP | |
| Auto MDI-X | Supported | |
| LLDP | Supported | |
| Web server | Inverter status monitor, inverter parameter monitor/configuration, network status monitor, password lock, access management | |
| SNTP | Supported (Setup from Web server interface) |
* Command reception time is until the inverter is operated by RUN command from network.
What is the behavior of the LNK1 LED and LNK2 LED on the TOSHIBA TOSVERT VF-AS3 module?
The behavior of the LNK1 LED and LNK2 LED on the TOSHIBA TOSVERT VF-AS3 module for Link Activity is:
| Color and behavior | Meaning |
|---|---|
| OFF | No link |
| Green blinking | Network activity at 100 Mbit/s |
| Green ON | Link established at 100 Mbit/s |
| Yellow blinking | Network activity at 10 Mbit/s |
| Yellow ON | Link established at 10 Mbit/s |
What is the behavior of the MS LED on the TOSHIBA TOSVERT VF-AS3 module?
The behavior of the MS LED on the TOSHIBA TOSVERT VF-AS3 module for Module Status is:
| Color and behavior | Meaning |
|---|---|
| OFF | Device does not have IP address or powered off |
| Flashing Green/Red (250ms cycle) | Power on testing |
| Green flashing (500ms cycle) | Device has not been configured |
| Green ON | Device is operating correctly |
| Red flashing (500ms cycle) | Device has detected a communication error |
| Red ON | Device has detected a non-recoverable error |
What is the behavior of the NS LED on the TOSHIBA TOSVERT VF-AS3 module?
The behavior of the NS LED on the TOSHIBA TOSVERT VF-AS3 module for Network Status is:
| Color and behavior | Meaning |
|---|---|
| OFF | The device does not have IP address or powered off |
| Flashing Green/Red (250ms cycle) | Power on testing |
| Green flashing (500ms cycle) | Device has a valid IP, but no command word connection |
| Green ON | A connection is established to control the command word |
| Red flashing (500ms cycle) | An established connection to control the command word is closed or timed out |
| Red ON | Duplicated IP |
How can the IP address of the TOSHIBA TOSVERT VF-AS3 be obtained using a DHCP server?
To obtain the IP address by using the DHCP server for the TOSHIBA TOSVERT VF-AS3:
Select “IP Setting” on Embedded Ethernet setting screen and set “2: DHCP.”
Connect the inverter and the equipment with a DHCP server function, and reset the inverter.
Check that the IP settings have been obtained by the monitor display in Embedded Ethernet setting screen.
How can the IP address of the TOSHIBA TOSVERT VF-AS3 be set manually?
To set the IP address manually for the TOSHIBA TOSVERT VF-AS3:
Select “IP Setting” on the Embedded Ethernet setting screen and set “0: Fixed.”
Set “IP Address”, “Mask”, “Gateway” to arbitrary values, and reset the inverter. If you don’t know Gateway address, you may set the value of “0.0.0.0” for “Gateway” setting.
Check that the IP settings have been changed by Embedded Ethernet setting screen.
What are the common parameters for the TOSHIBA TOSVERT VF-AS3?
The common parameters for the TOSHIBA TOSVERT VF-AS3 are:
| Title | Comm. No. | Parameter name | Description | Default setting |
|---|---|---|---|---|
| CMOd | 0003 | Command mode selection | 0: Terminal 1: Operation panel, Extension panel 2: Embedded Ethernet 3: RS485 communication (connector 1) 4: RS485 communication (connector 2) 5: Communication option |
0 |
| FMOd | 0004 | Frequency setting mode selection 1 | 0: – 1: Terminal RR 2: Terminal RX 3: Terminal II 4: Terminal AI4 (option) 5: Terminal AI5 (option) 6-9: – 10: Touch wheel 1 (power off or press OK to save) 11: Touch wheel 2 (press OK to save) 12: Sr0 13,14: – 15: Terminal Up/Down frequency 16: Pulse train 17: High resolution pulse train (option) 18,19: – 20: Embedded Ethernet 21: RS485 communication (connector 1) 22: RS485 communication (connector 2) 23: Communication option |
1 |
| AUE | 0032 | Eco-standby power setting | 0: – 1: Embedded Ethernet OFF (Unable to communicate with Ethernet) |
0 |
| F519 | 0519 | Setting of acceleration / deceleration time unit | 0: – 1: 0.01s unit (0 after execution) 2: 0.1s unit (0 after execution) |
0*1 |
| F749 | 0749 | Integrating wattmeter display unit selection | 0: 1.0=1kWh 1: 1.0=10kWh 2: 1.0=100kWh 3: 1.0=1000kWh 4: 1.0=10000kWh 5: 1.0=100000kWh |
*2 |
| F830 | 0830 | MODBUS continuous address | 0: Disabled 1: Enabled |
0 |
| F856 | 0856 | Number of motor pole pair for communication | 1: 2 pole 2: 4 pole 3: 6 pole 4: 8 pole 5: 10 pole 6: 12 pole 7: 14 pole 8: 16 pole |
2 |
| F897 | 0897 | Parameter Writing | 0: Storage to memory device 1: Storage to memory device except by communication |
0 |
| F899 | 0899 | Communication function reset | 0: – 1: Reset option and inverter (after execution: 0) |
0 |
*1 0.1s unit is selected as default setting.
*2 Default setting values vary depending on the capacity.
What are the communication parameters for the TOSHIBA TOSVERT VF-AS3?
The communication parameters for the TOSHIBA TOSVERT VF-AS3 are:
| Title | Comm. No. | Parameter name | Description | Default setting |
|---|---|---|---|---|
| C081 to C096 | C081 to C096 | Device Name 1-16*1 | Max 16 characters Default setting1 function ([tyP] = “3”) does not work for this parameter. |
0 |
| C606 | C606 | Emb Eth. Communication error detection delay | 0.0 – 100.0 sec. | 0.0 |
| C607 | C607 | Emb Eth. Communication error operation | 0: Turn off bit 10, 14 and 15 of FA36 1: Continue running 2: Deceleration stop 3: Coast stop 4: Network error stop (E-43 trip) 5: Preset speed operation (by C608 setting) |
4 |
| C608 | C608 | Emb Eth. Preset speed at communication error | 0: None 1 to 15: Preset speed |
0 |
| C609 | C609 | Emb Eth. Communication error detection | 0: Always 1: Communication command (Frequency command and command from Emb Eth.) enabled 2: 1 + during run |
1 |
| C610 | C610 | Emb Eth. IP setting mode*1 | 0: Fixed 1: BOOTP 2: DHCP |
2 |
| C611 to C614 | C611 to C614 | Emb Eth. IP address setting value*1 | The IP address of the device. These fields are effective settings at [C610] = “0”. | 0.0.0.0 |
| C615 to C618 | C615 to C618 | Emb Eth. Subnet mask setting value*1 | The subnet mask of the device. These fields are effective settings at [C610] = “0”. | 0.0.0.0 |
| C619 to C622 | C619 to C622 | Emb Eth. Default gateway setting value*1 | The gateway IP address of the device. These fields are effective settings at [C610] = “0”. | 0.0.0.0 |
| C641 to C650 | C641 to C650 | Emb Eth. Scanner input select 1 to 10 | 0: No action 1: FA36 (Emb Ethernet command 1) 2: FA38 (Emb Ethernet command 2) 3: FA37 (Emb Ethernet frequency command) 4: FA40 (Emb Ethernet torque command) 5: FA50 (Terminal output data) 6: FA51 (Terminal FM data) 7: FA52 (Terminal AM data) 8: F601 (Stall prevention level 1) 9: F441 (Power running torque limit level 1) 10: F443 (Regenerative torque limit level 1) 11: F460 (Speed control response 1) 12: F461 (Speed control stabilization coefficient 1) 13: ACC (Acceleration time 1)*2 14: dEC (Deceleration time 1)*2 15: UL (Upper limit frequency) 16: vb (Manual torque boost 1) 17: vLv (Base frequency voltage 1) |
C641: 1 C642: 3 C643 to C644: 0 |
| C651 to C660 | C651 to C660 | Emb Eth. Scanner output select 1 to 10 | 0: No action 1: FD01 (Inverter status 1) 2: FD00 (Output frequency) 3: FD03 (Output current) 4: FD05 (Output voltage) 5: FC91 (Alarm code) 6: FD22 (PID feedback value) 7: FD06 (Input terminal status) 8: FD07 (Output terminal status) 9: FE35 (Terminal RR input value) 10: FE36 (Terminal RX input value) 11: FE37 (Terminal II input value) 12: FD04 (Input voltage (DC detection)) 13: FD16 (Speed feedback frequency (real time)) 14: FD18 (Torque) 15: FE60 (My function monitor output 1) 16: FE61 (My function monitor output 2) 17: FE62 (My function monitor output 3) 18: FE63 (My function monitor output 4) 19: F880 (Free memorandum) 20: FD29 (Input power) 21: FD30 (Output power) 22: FE14 (Cumulative operation time) 23: FE40 (Terminal FM output value) 24: FE41 (Terminal AM output value) 25: FD20 (Torque current) 26: FD23 (Motor overload factor) 27: FD24 (Inverter overload factor) 28: FD25 (Braking resistor overload factor) 29: FD26 (Motor load factor) 30: FD27 (Inverter load factor) 31: FE56 (Terminal S4/S5 pulse train input value) 32: FE70 (Inverter rated current) 33: FE76 (Input cumulative power) 34: FE77 (Output cumulative power) 35: FD83 (Internal temperature 1) 36: FC90 (Trip code) |
C651: 1 C652: 2 C653 to C654: 0 |
| C661 | C661 | Emb Eth. I/O write memory | 0: RAM 1: EEPROM |
0 |
| C666 | C666 | Emb Eth. I/O scan timeout detection time | 0: Disable 0.1-30.0 s |
2.0 |
| C667 | C667 | Emb Eth. I/O scan setting *1*4 | 0: Disable 1: Enable |
1 |
| C668 | C668 | Emb Eth. Web server*1 | 0: Disabled 1: Enabled |
1 |
| C669 | C669 | Emb Eth. Web server reset | 0: – 1: Execution (after execution: 0) |
0 |
| C670 | C670 | Emb Eth. Unit ID | 0-247*3 | 0 |
| C671 | C671 | Emb Eth. Message timeout detection time*1*4 | 0: Disable 0.1-100.0 s |
2.0 |
| C672 | C672 | Parameter for manufacturer | – | – |
| C680 | C680 | EmbEth. Inverter to inverter communication select*1*4 | 0: Disabled 1: Inverter to inverter communication 2: Pump control |
0 |
| C681 | C681 | EmbEth. Inverter to inverter communication ID *1*4 | 0: Leader 1-9: Follower 1-9 |
0 |
| C682 | C682 | EmbEth. Inverter to inverter communication*1*4 | 0: Follower (0Hz command when Leader fails) 1: Follower (continue running when Leader fails) 2: Follower (emergency off when Leader fails) 3: Leader (transmit frequency command) 4: Leader (transmit output frequency signal) 5: Leader (transmit torque command) 6: Leader (transmit output torque command) |
0 |
How do I access the Embedded Ethernet setting screen guidance function on the TOSHIBA TOSVERT VF-AS3 LCD panel?
To access the Embedded Ethernet setting screen of the guidance function on the TOSHIBA TOSVERT VF-AS3 LCD panel, follow this operation:
[ESC] key => Select “3. Guidance function” => [OK] key => Select “3.1 Embedded Ethernet” => [OK] key
What settings can be configured using the Embedded Ethernet setting screen on the TOSHIBA TOSVERT VF-AS3?
The Embedded Ethernet setting screen on the TOSHIBA TOSVERT VF-AS3 allows you to set IP address setting mode, IP address, subnet mask, default gateway and device name. In addition, you can check the currently settings in the monitor display by scrolling the screen.
How is the command data converted during inverter-to-inverter communication for frequency value on the TOSHIBA TOSVERT VF-AS3?
When transmitting frequency command or output frequency, data is converted using [FH: Maximum frequency] on the TOSHIBA TOSVERT VF-AS3 as below:
f_c (%) = (Leader frequency value(Hz) × 10000) / (Leader maximum frequency(Hz) * (1=0.01%))
Calculation results of 1 (0.01%) or less are rounded down. As a result, a maximum error of 0.01% occurs.
How are frequency commands converted after they are received by follower inverters during inverter-to-inverter communication on the TOSHIBA TOSVERT VF-AS3?
The conversion details of frequency commands after they are received by followers on the TOSHIBA TOSVERT VF-AS3 result in the value written to the RAM as a frequency command value:
f_c (Hz) = (Reception data(%) × Follower maximum frequency(Hz)) / 10000 (1=0.01Hz)
Calculation results of 1 (0.01 Hz) or less are rounded down. As a result, a maximum error of 0.01 Hz occurs.
What are the setting example configurations for the leader and followers for parameter setting via embedded ethernet on the TOSHIBA TOSVERT VF-AS3?
For the parameter setting example for embedded ethernet on the TOSHIBA TOSVERT VF-AS3, where frequency reference and operation command are input from the panel of the leader and transmitted to the follower by inverter to inverter communication:
Parameters of the leader (examples):
[CMOd] = “1” Example: Operation panel
[FMOd] = “10” Example: Touch wheel 1
[C610] = “0” Fixed
[C611] = “192”
[C612] = “168”
[C613] = “1”
[C614] = “10”
[C611] = “255”
[C612] = “255”
[C613] = “255”
[C614] = “0”
[C680] = “1” Inverter to inverter communication
[C681] = “0” Leader
[C682] = “3” Leader (transmit frequency command)
Parameters of the followers (examples):
[CMOd] = “2” Embedded Ethernet
[FMOd] = “20” Embedded Ethernet
[C610] = “0”
[C611] = “192”
[C612] = “168”
[C613] = “1”
[C614] = “20”
[C611] = “255”
[C612] = “255”
[C613] = “255”
[C614] = “0”
[C680] = “1” Inverter to inverter communication
[C681] = “1” Follower 1
[C682] = “0” Follower (0Hz command when Leader fails)
What are the details for setting the [FA36: Communication command1 from embedded ethernet] bits on the TOSHIBA TOSVERT VF-AS3?
The details for the bits in [FA36: Communication command1 from embedded ethernet] on the TOSHIBA TOSVERT VF-AS3 are:
| bit | Function | 0 | 1 | Operating condition | Note |
|---|---|---|---|---|---|
| 0 | Preset speed switching 1 | 0000: Preset speed operation OFF*1 | 0001-1111: Setting of preset speed operation frequencies (1-15) | b | Preset speed operation is disabled or preset speed operation frequencies (1-15) are set by specifying bits for preset speed operation frequencies 1-4. |
| 1 | Preset speed switching 2 | 0001-1111: Setting of preset speed operation frequencies (1-15) | b | ||
| 2 | Preset speed switching 3 | 0001-1111: Setting of preset speed operation frequencies (1-15) | b | ||
| 3 | Preset speed switching 4 | 0001-1111: Setting of preset speed operation frequencies (1-15) | b | ||
| 4 | V/f switching 1*2 | V/f 1 | V/f 2 | b | V/f 1: [Pt] = setting value, [vL], [vLv], [vb], [tHrA] V/f 2: [Pt] = “0”, [F170], [F171], [F172], [F182] |
| 5 | PID control OFF | PID control permitted | PID control prohibited | a | – |
| 6 | Acc/Dec switching 1*3 | AD mode 1 | AD mode 2 | b | AD mode 1: [ACC], [dEC] AD mode 2: [F500], [F501] |
| 7 | DC braking | OFF | Forced DC braking | b | – |
| 8 | Jog run | OFF | Jog run | b | – |
| 9 | Forward/Reverse | Forward run | Reverse run | b | – |
| 10 | Run/Stop | Stop | Run | b | – |
| 11 | Coast stop*4 | Standby | Coast stop | b | – |
| 12 | Emergency off | OFF | Emergency off | a | Always enable, [E] trip |
| 13 | Fault reset | OFF | Reset | a | Trip reset |
| 14 | Frequency priority | OFF | Enabled | – | Enabled regardless of the setting of [FMOd] |
| 15 | Command priority | OFF | Enabled | – | Enabled regardless of the setting of [CMOd] |
*1 When set “12 [Sr0]” to FMOd, preset speed operation frequency 0 is selected.
*2 The V/f switching ORs with Bit 10 of [FA38].
*3 The Acc/Dec switching ORs with Bit 8 of [FA38].
*4 When set “2 [Embedded Ethernet]” to CMOd, the Bit 11 (Coast stop) of [FA36] is ON at startup. If you want to start the operation by [FA36], please turn OFF the Bit 11.
What are the details for setting the [FA38: Communication command 2 from embedded ethernet] bits on the TOSHIBA TOSVERT VF-AS3?
The details for the bits in [FA38: Communication command 2 from embedded ethernet] on the TOSHIBA TOSVERT VF-AS3 are:
| Bit | Function | 0 | 1 | Operating condition | Note |
|---|---|---|---|---|---|
| 0 | Control switching | Speed control | Torque control | b | – |
| 1 | Electric power quantity reset | OFF | Reset | a | Electric power quantity (FE76, FE77) reset |
| 2 | (Reserved) | – | – | – | – |
| 3 | Braking request (BC) | Normal | Forcibly braked | b | – |
| 4 | Preliminary excitation | Normal | Enabled | b | – |
| 5 | (Reserved) | – | – | – | – |
| 6 | Braking answer (BA) | Brake applied | Brake released | b | – |
| 7 | Quick deceleration 2 | Normal | Enabled | b | – |
| 8 | Acc/dec switching 1*1 | 00: AD mode 1 01: AD mode 2 10: AD mode 3 11: AD mode 4 |
b | Select Acc/Dec mode 1 – 4 by combination of two bits. AD mode 1: [ACC], [dEC] AD mode 2: [F500], [F501] AD mode 3: [F510], [F511] AD mode 4: [F514], [F515] |
|
| 9 | Acc/dec switching 2 | 00: V/f 1 01: V/f 2 10: V/f 3 11: V/f 4 |
b | Select V/f pattern 1 – 4 by combination of two bits V/f 1: [Pt] = setting value, [vL], [vLv], [vb], [tHrA] V/f 2: [Pt] = “0”, [F170], [F171], [F172], [F182] V/f 3: [Pt] = “0”, [F174], [F175], [F176], [F183] V/f 4: [Pt] = “0”, [F178], [F179], [F180], [F184] |
|
| 10 | V/f switching 1*2 | b | |||
| 11 | V/f switching 2 | b | |||
| 12 | OC stall level switching and Torque limit switching 1 | 00: Torque limit 1 / OC stall 1 01: Torque limit 2 / OC stall 2 10: Torque limit 3 / OC stall 1 11: Torque limit 4 / OC stall 2 |
b | OC stall 1: [F601] OC stall 2: [F185] Select torque limit 1 – 4 by combination of two bits Torque limit 1: [F441], [F443] Torque limit 2: [F444], [F445] Torque limit 3: [F446], [F447] Torque limit 4: [F448], [F449] |
|
| 13 | Torque limit switching 2 | ||||
| 14 | Speed gain switching | Gain 1 | Gain 2 | b | Gain 1: [F460], [F461], [F462] Gain 2: [F463], [F464], [F465] |
| 15 | (Reserved) | – | – | – | – |
*1 The Acc/Dec switching ORs with Bit 6 of [FA36]. When changing Acc/Dec in four types, set Bit 6 of [FA36] to “0” and use [FA38].
*2 The V/f switching ORs with Bit 4 of [FA36]. When changing V/f in four types, set Bit 4 of [FA36] to “0” and use [FA38].
How is the frequency command set via embedded ethernet on the TOSHIBA TOSVERT VF-AS3?
The frequency command on the TOSHIBA TOSVERT VF-AS3 is set up by 0.01Hz unit and the hexadecimal number. For example, when “Frequency command” is set up to “80Hz”, since the minimum unit is 0.01Hz, 80Hz=80÷0.01 = 8000 (Dec.) = 0x1F40 (Hex.).
This frequency command value is enabled only when the frequency command via embedded ethernet is enabled. To make frequency commands via embedded ethernet enabled, set [FMOd: Frequency command select 1] to “20”: Embedded Ethernet” or set the “Command priority” option (bit 14 of [FA36]).
How is the torque command set via embedded ethernet on the TOSHIBA TOSVERT VF-AS3?
The torque reference on the TOSHIBA TOSVERT VF-AS3 is set up by 0.01% unit and the hexadecimal number. For example, when “torque command” is set up to “50%”, since the minimum unit is 0.01%, 50%=50÷0.01=5000 (Dec.) =0x1388 (Hex.).
How are terminal output data controlled using the [FA50: Terminal output data] on the TOSHIBA TOSVERT VF-AS3?
By setting up the data of the bit 0 – 6 of [FA50] from communication on the TOSHIBA TOSVERT VF-AS3, setting data (OFF or ON) can be outputted to the output terminal. Please select the functional number 92 – 105 as the selection of the output terminal function [F130 to F134], [F159 to F163] before using it.
| bit | Output TB function name | 0 | 1 |
|---|---|---|---|
| 0 | Designated data output 1 (Output terminal No.: 92, 93) | OFF | ON |
| 1 | Designated data output 2 (Output terminal No.: 94, 95) | OFF | ON |
| 2 | Designated data output 3 (Output terminal No.: 96, 97) | OFF | ON |
| 3 | Designated data output 4 (Output terminal No.: 98, 99) | OFF | ON |
| 4 | Designated data output 5 (Output terminal No.: 100, 101) | OFF | ON |
| 5 | Designated data output 6 (Output terminal No.: 102, 103) | OFF | ON |
| 6 | Designated data output 7 (Output terminal No.: 104, 105) | OFF | ON |
| 7-15 | (Reserved) | – | – |
Note: Set 0 to reserved bit.
What does the bit setting in [FD01: Inverter status 1] represent on the TOSHIBA TOSVERT VF-AS3 monitor parameters?
The bit setting in [FD01: Inverter status 1] on the TOSHIBA TOSVERT VF-AS3 monitor parameters is:
| bit | Function | 0 | 1 | Note |
|---|---|---|---|---|
| 0 | Failure FL | No output | Under in progress | – |
| 1 | Failure | Not tripped | Tripped | Trip status includes [rtry] and the trip retention status is also regarded as tripped statuses. |
| 2 | Alarm | No alarm | Alarm issued | – |
| 3 | Under voltage ([MOFF]) | Normal | Under voltage | – |
| 4 | V/f switching status | V/f 1 | V/f 2 | V/f 1: [Pt] = setting value, [vL], [vLv], [vb], [tHrA] V/f 2: [Pt] = “0”, [F170], [F171], [F172], [F182] |
| 5 | PID control OFF | PID control permitted | PID control prohibited | – |
| 6 | Acc/Dec switching status | AD mode 1 | AD mode 2 | AD mode 1: [ACC], [dEC] AD mode 2: [F500], [F501] |
| 7 | DC braking | OFF | Forced DC braking | – |
| 8 | Jog run | OFF | Jog run | – |
| 9 | Forward / reverse run | Forward run | Reverse run | – |
| 10 | Run/stop | Stop | Run | – |
| 11 | Coast stop (ST = OFF) | ST=ON | ST=OFF | – |
| 12 | Emergency stop | No emergency stop status | Emergency stop status | – |
| 13 | Standby ST=ON | Start-up process | Standby | Standby: Initialization completed, not failure stop status, not alarm stop status ([MOFF], [COFF], [StOP], [LStP]), ST =ON and RUN=ON |
| 14 | Standby | Start-up process | Standby | Standby: Initialization completed, not failure stop status and not alarm stop status ([MOFF], [COFF], [StOP], [LStP]) |
| 15 | HAND/AUTO (LOC/REM) | AUTO (REM) | HAND (LOC) | Enabled with [F750] = “2” HAND: Panel operation is enabled AUTO: Operation method selected [CMOd] and [FMOd] are enabled. Enabled with [F732] = “0” LOC: Panel operation is enabled REM: Operation method selected [CMOd] and [FMOd] are enabled. |
How is the output frequency read into units and by hexadecimal number from [FD00: Output frequency] on the TOSHIBA TOSVERT VF-AS3?
The current output frequency on the TOSHIBA TOSVERT VF-AS3 is read into 0.01Hz of units and by the hexadecimal number. For example, when the output frequency is “80Hz”, 0x1F40 (hexadecimal number) are read. Since the minimum unit is 0.01Hz, 0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz).
Also about the following parameters, these are the same as this:
– [FD16: Speed feedback frequency] …………………………………… Unit: 0.01Hz
– [FD22: PID feedback value]……………………………………………… Unit: 0.01Hz
– [FD29: Input power] ………………………………………………………… Unit: 0.01kW
– [FD30: Output power] ……………………………………………………… Unit: 0.01kW
How is the output current read into units and by hexadecimal number from [FD03: Output current] on the TOSHIBA TOSVERT VF-AS3?
The output current on the TOSHIBA TOSVERT VF-AS3 is read into 0.01% of units and by the hexadecimal number. For example, when the output current is 2.4A with the rated current 4.8A, 0x1388 (50.00%) is read out. Since the minimum unit is 0.01%, 0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%).
Also about the following parameters, these are the same as this:
– [FD04: Input voltage (DC detection)] …………………………………. Unit: 0.01% (V)
– [FD05: Output voltage]…………………………………………………….. Unit: 0.01% (V)
– [FD18: Torque] ……………………………………………………………….. Unit: 0.01% (Nm)*
* When the motor information are set to the parameter ([F405 to F415]), torque monitor value “100%” is same as the rated torque of a motor in general.
How are analog input values monitored from [FE35, FE36, FE37: Monitoring of the analog input RR, RX, II] on the TOSHIBA TOSVERT VF-AS3?
[FE35: Terminal RR input value], [FE36: Terminal RX input value], and [FE37: Terminal II input value] on the TOSHIBA TOSVERT VF-AS3 can be used as A/D converter.
[FE35] and [FE37] are capable of reading the data from external devices in a range of 0.01 to 100.00% (unsigned data: 0x0000 to 0x2710).
[FE36] is capable of reading the data from external devices in a range of -100.00 to 100.00% (signed data: 0xD8F0 to 0x2710).
If analog input mode is selected with the frequency setting mode selection parameter, however, keep in mind that any data entered via an analog terminal is regarded as a frequency command.
How is the cumulative run time read from [FE14: Cumulative run time for monitor] on the TOSHIBA TOSVERT VF-AS3?
The operated cumulative time on the TOSHIBA TOSVERT VF-AS3 is read by the hexadecimal number from [FE14: Cumulative run time for monitor]. For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read. 0x12 (Hex.) = 18 (Dec., hour).
What is the value range for the output value of FM terminal or AM terminal read from [FE40: FM output monitor] and [FE41: AM output monitor] on the TOSHIBA TOSVERT VF-AS3?
The output value of FM terminal or AM terminal read from [FE40: FM output monitor] and [FE41: AM output monitor] on the TOSHIBA TOSVERT VF-AS3 is set to 0 to 10000 (0x2710).
Note)
The FM output value monitor cannot be used when the parameter [F681] = “0”. Set [F681] to 1 or 2 before using.
The AM output value monitor cannot be used when the parameter [F686] = “0”. Set [F686] to 1 or 2 before using.
What are the input terminal status indications in [FD06: Input terminal status] on the TOSHIBA TOSVERT VF-AS3?
The input terminal status indications in [FD06: Input terminal status] on the TOSHIBA TOSVERT VF-AS3 are:
| bit | TB Name | Function (Parameter) | 0 | 1 |
|---|---|---|---|---|
| 0 | F | [F111: Input terminal function selection 1] | OFF | ON |
| 1 | R | [F112: Input terminal function selection 2] | ||
| 2 | RES | [F113: Input terminal function selection 3] | ||
| 3 | S1 | [F114: Input terminal function selection 4] | ||
| 4 | S2 | [F115: Input terminal function selection 5] | ||
| 5 | S | [F116: Input terminal function selection 6] | ||
| 6 | S4*1 | [F117: Input terminal function selection 7] | ||
| 7 | S5*2 | [F118: Input terminal function selection 8] | ||
| 8 | DI11*3 | [F119: Input terminal function selection 9] | ||
| 9 | DI12*3 | [F120: Input terminal function selection 10] | ||
| 10 | DI13*3 | [F121: Input terminal function selection 11] | ||
| 11 | DI14*3 | [F122: Input terminal function selection 12] | ||
| 12 | DI15*3 | [F123: Input terminal function selection 13] | ||
| 13 | DI16*3 | [F124: Input terminal function selection 14] | ||
| 14 to 15 | (Undefined) | – | – | – |
*1 This value is valid only when [F146: S4 terminal input selection] = “0: Digital input” is selected.
*2 This value is valid only when [F147: S5 terminal input selection] = “0: Digital input” is selected.
*3 DI11 to DI16 are expansion terminals.
What are the output terminal status indications in [FD07: Output terminal status] on the TOSHIBA TOSVERT VF-AS3?
The output terminal status indications in [FD07: Output terminal status] on the TOSHIBA TOSVERT VF-AS3 are:
| bit | TB Name | Function (Parameter) | 0 | 1 |
|---|---|---|---|---|
| 0 | FP | [F130: Terminal FP function 1] | OFF | ON |
| 1 | (Undefined) | – | – | |
| 2 | FL | [F132: Terminal FL function] | OFF | ON |
| 3 | R1 | [F133: Terminal R1 function 1] | OFF | ON |
| 4 | R2 | [F134: Terminal R2 function] | OFF | ON |
| 5 | DQ11 | [F159: Terminal DQ11 function] | OFF | ON |
| 6 | DQ12 | [F160: Terminal DQ12 function] | OFF | ON |
| 7 | R4 | [F161: Terminal R4 function] | OFF | ON |
| 8 | R5 | [F162: Terminal R5 function] | OFF | ON |
| 9 | R6 | [F163: Terminal R6 function] | OFF | ON |
| 10 | R4(B) | [A201: Terminal R4 (B) function] | OFF | ON |
| 11 | R5(B) | [A202: Terminal R5 (B) function] | OFF | ON |
| 12 | R6(B) | [A203: Terminal R6 (B) function] | OFF | ON |
| 13 to 15 | (Undefined) | – | – |
Note: The bit described “Undefined” is unstable. Do not use the bit for the judgment.
How is the Modbus TCP “03 (0x03) Read Holding Registers” function request and response format defined for the TOSHIBA TOSVERT VF-AS3?
The Modbus TCP “03 (0x03) Read Holding Registers” function request and response format for the TOSHIBA TOSVERT VF-AS3 is:
Request Format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x03 |
| 1 | Communication No. of Starting Parameter Hi |
| 2 | Communication No. of Starting Parameter Lo |
| 3 | Number of Parameters Hi (0) |
| 4 | Number of Parameters Lo (1 – 125) |
Response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x03 |
| 1 | Byte Count (B = 2 × Number of Points) |
| 2 | First Parameter Data Hi |
| 3 | First Parameter Data Lo |
| … | ………………………. |
| B | Last Parameter Data Hi |
| B+1 | Last Parameter Data Lo |
Exception response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x83 |
| 1 | Exception Code 1: Illegal Function 2: Illegal Data Address 3: Illegal Data Value |
Memo • If the communication number that doesn’t exist is read, device returns 0x8000.
How is the Modbus TCP “06 (0x06) Write Single Register” function request and response format defined for the TOSHIBA TOSVERT VF-AS3?
The Modbus TCP “06 (0x06) Write Single Register” function request and response format for the TOSHIBA TOSVERT VF-AS3 is:
Request format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x06 |
| 1 | Communication No. of Parameter Hi |
| 2 | Communication No. of Parameter Lo |
| 3 | Write Data Hi |
| 4 | Write Data Lo |
Response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x06 |
| 1 | Communication No. of Parameter Hi |
| 2 | Communication No. of Parameter Lo |
| 3 | Write Data Hi |
| 4 | Write Data Lo |
Exception response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x86 |
| 1 | Exception Code 1: Illegal Function 2: Illegal Data Address 3: Illegal Data Value 4: Slave Device Failure |
Memo • When you use this Modbus request, the value is written to the EEPROM. Frequent writing to the EEPROM of inverter will cause a memory corruption.
How is the Modbus TCP “16 (0x10) Write Multiple Registers” function request and response format defined for the TOSHIBA TOSVERT VF-AS3?
The Modbus TCP “16 (0x10) Write Multiple Registers” function request and response format for the TOSHIBA TOSVERT VF-AS3 is:
Request format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x10 |
| 1 | Communication No. of Starting Parameter Hi |
| 2 | Communication No. of Starting Parameter Lo |
| 3 | Number of Parameters Hi (0) |
| 4 | Number of Parameters Lo (1 – 123) |
| 5 | Byte Count (B = 2 × Number of Registers) |
| 6 | First Parameter Data Hi |
| 7 | First Parameter Data Lo |
| … | ………………………. |
| B+4 | Last Parameter Data Hi |
| B+5 | Last Parameter Data Lo |
Response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x10 |
| 1 | Communication No. of Starting Parameter Hi |
| 2 | Communication No. of Starting Parameter Lo |
| 3 | Number of Parameters Hi (0) |
| 4 | Number of Parameters Lo (1 – 123) |
Exception response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x90 |
| 1 | Exception Code 01: Illegal Function 02: Illegal Data Address 03: Illegal Data Value 04: Slave Device Failure |
Memo • When you use this Modbus request, the value is written to the EEPROM. Frequent writing to the EEPROM of inverter will cause a memory corruption.
How is the Modbus TCP “23 (0x17) Read/Write Multiple Registers” function request and response format defined for the TOSHIBA TOSVERT VF-AS3, used for I/O Scanning?
The Modbus TCP “23 (0x17) Read/Write Multiple Registers” function request and response format for the TOSHIBA TOSVERT VF-AS3, used for the IO Scanning service, is:
Request format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x17 |
| 1 | Read Starting Register Hi(0) |
| 2 | Read Starting Register Lo(0) |
| 3 | Number of Read Registers Hi (0) |
| 4 | Number of Read Registers Lo (2 – 9) |
| 5 | Write Starting Register Hi (0) |
| 6 | Write Starting Register Lo (0) |
| 7 | Number of Write Registers Hi (0) |
| 8 | Number of Write Registers Lo (2 – 9) |
| 9 | Byte Count (B = 2 × Number of Write Registers) |
| 10 | First Write Register Data Hi |
| 11 | First Write Register Data Lo |
| … | ………………………. |
| B+8 | Last Write Register Data Hi |
| B+9 | Last Write Register Data Lo |
Response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x17 |
| 1 | Byte Count (B = 2 × Number of Points) |
| 2 | First Read Register Data Hi |
| 3 | First Read Register Data Lo |
| … | ………………………. |
| B | Last Read Register Data Hi |
| B+1 | Last Read Register Data Lo |
Exception response format:
| Byte | Meaning |
|---|---|
| 0 | Function Code = 0x97 |
| 1 | Exception Code 01 (Illegal Function) 02 (Illegal Data Address) 03 (Illegal Data Value) 04 (Slave Device Failure) |
Memo
If the communication number that doesn’t exist is read, device returns 0x8000.
When you use this Modbus request with I/O scanning service, the value is written to RAM.
Please set the “00” for Read Starting Address and Write Starting Address.
What is the outline of the IO scanning service for the TOSHIBA TOSVERT VF-AS3?
The IO Scanning service on the TOSHIBA TOSVERT VF-AS3 is used to exchange I/O data between a controller (PLC) and the inverter. It is usually performed by implicit services, thus avoiding the need to program the controller (PLC).
The IO Scanning service operates if it has been enabled in the PLC with function code 0x17.
When you use the I/O scanning service, set the “255” (0xFF) to the Unit ID.
Time out detection time of IO scanning service can be changed by parameter [C666: Emb Eth. I/O scan timeout detection time].
How are word registers set up for I/O scan services using Modbus function code 0x17 on the TOSHIBA TOSVERT VF-AS3?
Up to ten of the Read/Write register data will be exchanged by the I/O scan services using Modbus function code 0x17 on the TOSHIBA TOSVERT VF-AS3. By parameter setting of [C641] – [C650], [C651] – [C660], you can assign command / monitor parameters for each register. Since the No. 0 of register is in the reservation data, please use the register No. 1 to No. 10.
| Register No. | Output variables (written by IO Scanner) | Input variables (read by IO Scanner) |
|---|---|---|
| 0 | Reserved | Reserved |
| 1 | Scanner write word 1 (selected by [C641]) | Scanner read word 1 (selected by [C651]) |
| 2 | Scanner write word 2 (selected by [C642]) | Scanner read word 2 (selected by [C652]) |
| 3 | Scanner write word 3 (selected by [C643]) | Scanner read word 3 (selected by [C653]) |
| 4 | Scanner write word 4 (selected by [C644]) | Scanner read word 4 (selected by [C654]) |
| 5 | Scanner write word 5 (selected by [C645]) | Scanner read word 5 (selected by [C655]) |
| 6 | Scanner write word 6 (selected by [C646]) | Scanner read word 6 (selected by [C656]) |
| 7 | Scanner write word 7 (selected by [C647]) | Scanner read word 7 (selected by [C657]) |
| 8 | Scanner write word 8 (selected by [C648]) | Scanner read word 8 (selected by [C658]) |
| 9 | Scanner write word 9 (selected by [C649]) | Scanner read word 9 (selected by [C659]) |
| 10 | Scanner write word 10 (selected by [C650]) | Scanner read word 10 (selected by [C660]) |
| 11-31 | Reserved | Reserved |
What error codes are returned by the inverter for the Modbus function code 43 (0x2B) Read Device identification on the TOSHIBA TOSVERT VF-AS3?
If the following errors occur, the reply command from the inverter is returned by adding 80H to the command received by the inverter for the Modbus function code 43 (0x2B) Read Device identification on the TOSHIBA TOSVERT VF-AS3. The error codes are as follows:
| Error code | Name | Description |
|---|---|---|
| 01 | Command error | No command exists. The MEI type is not 14 (0x0E) with the model information reading by Modbus function code 0x2B. |
| 02 | Communication number error | No communication number exists. Writing was performed to the exclusive reading parameter. Illegal Object ID with the model information reading by Modbus function code 0x2B. |
| 03 | Data error | Data range error. The communication format has an error. When the reading equipment code is set to 4 or more in model information reading command. |
| 04 | Execution impossible | Writing to parameter that is impossible to be written while running. Writhing to parameter for which TYP is being executed. Writing to [F738: Password setting] when [F738] is set. |
What are the common data type prevalent in the EtherNet/IP object specifications for the TOSHIBA TOSVERT VF-AS3?
The prevalent data types in the EtherNet/IP object specifications for the TOSHIBA TOSVERT VF-AS3 are:
BOOL ………………………Boolean 0(False) or 1(TRUE)
SINT………………………..Signed Short Integer -128 to 127
INT ………………………….Integer -32768 to 32767
DINT………………………..Double Integer -2^31 to 2^31-1
USINT ……………………..Unsigned Short Integer 0 to 255
UINT………………………..Unsigned Integer 0 to 65535
UDINT ……………………..Unsigned Double Integer 0 to 2^32-1
STRING …………………..character string (1 byte per character)
SHORT_STRING………character string (1 byte per character, 1 byte length indicator)
BYTE……………………….Bit string – 8-bits
WORD……………………..Bit string – 16-bits
DWORD …………………..Bit string – 32-bits
EPATH……………………..CIP path segments
What is the structure of Instance 20: CIP basic speed control output mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 20 mapping for CIP basic speed control output on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | – | – | – | – | Fault reset*1 | – | Run Fwd |
| 1 | – | – | – | – | – | – | – | – |
| 2 | Drive Speed Reference min⁻¹ (Low byte) *2 | |||||||
| 3 | Drive Speed Reference min⁻¹ (High byte) *2 | |||||||
*1 Fault reset works only 1 time when 0 -> 1.
*2 Drive Speed Reference is set up number of rotations by the hexadecimal number. For example, when “Frequency reference” is set up to 1800 min-1: 1800 = 0x0708
What is the structure of Instance 70: CIP basic speed control input mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 70 mapping for CIP basic speed control input on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | – | – | – | – | Running Fwd | – | Faulted |
| 1 | – | – | – | – | – | – | – | – |
| 2 | Drive Actual Speed min⁻¹ (Low byte) | |||||||
| 3 | Drive Actual Speed min⁻¹ (High byte) | |||||||
| 4 | Drive Actual Torque Nm (Low byte) | |||||||
| 5 | Drive Actual Torque Nm (High byte) | |||||||
How do I set Instance 20/70 to Stop on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP?
To set Instance 20/70 to Stop on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP:
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 20 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0x0000 |
| 3, 2 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| Input Instance 70 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0x0000 |
| 3, 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0x0000 |
How do I set Forward running 1800 min⁻¹ for Instance 20/70 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP?
To set Forward running 1800 min⁻¹ for Instance 20/70 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP:
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 20 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0x0001 |
| 3, 2 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0x0708 | |
| Input Instance 70 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0x0004 |
| 3, 2 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0x0708 |
How do I perform a Fault reset for Instance 20/70 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP?
To perform a Fault reset for Instance 20/70 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP (Fault reset):
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 20 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0x0004 |
| 3, 2 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – |
*1 Fault reset works only 1 time when 0 -> 1.
What is the structure of Instance 21: CIP extended speed control output mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 21 mapping for CIP extended speed control output on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | NetRef*1 | NetCtrl*1 | – | – | Fault reset | Run Rev | Run Fwd |
| 1 | – | – | – | – | – | – | – | – |
| 2 | Drive Reference Speed min⁻¹ (Low byte) | |||||||
| 3 | Drive Reference Speed min⁻¹ (High byte) | |||||||
| 4 | Drive Reference Torque Nm (Low byte) | |||||||
| 5 | Drive Reference Torque Nm (High byte) | |||||||
*1 Bit 5 and 6 of the instance 21 byte 0 are defined as follows:
Bit 5 (Net Ctrl) ……………………………. When “1” is set, Run/Stop is according to bits 0 (Run forward) and 1 (Run reverse) of byte 0. When “0” is set, Run/Stop is according to setup of the parameter [CMOd].
Bit 6 (Net Ref) ……………………………. When “1” is set, Drive Reference Speed is according to bytes 2 and 3. When “0” is set, Drive Reference Speed is according to setup of the parameter [FMOd].
What is the structure of Instance 71: CIP extended speed control input mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 71 mapping for CIP extended speed control input on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | At Reference *2 | Ref From Net*2 | Ctrl From Net*2 | Ready | Running Rev | Running Fwd | Warning | Faulted |
| 1 | Drive Status*3 | |||||||
| 2 | Drive Actual Speed min⁻¹ (Low byte) | |||||||
| 3 | Drive Actual Speed min⁻¹ (High byte) | |||||||
*2 Bit 5, 6, and 7 of the instance 71 byte 0 are defined as follows.
Bit 5 (Ctrl from Net) …………………….. When RUN/STOP command from EtherNet/IP is enabled, “1” is set.
Bit 6 (Ref from Net) …………………….. When Drive Reference Speed from EtherNet/IP is enabled, “1” is set.
Bit 7 (At reference)……………………… When Drive Actual Speed becomes the same as frequency command, “1” is set.
*3 Drive Status is same as the Control Supervisor class State attribute (refer to section 4. 6. 2).
How do I set Instance 21/71 to Stop on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP?
To set Instance 21/71 to Stop on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP:
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 21 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0x0000 |
| 3, 2 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| Input Instance 71 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0 | 0 | 0 | 0x0310 |
| 3, 2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0x0000 |
How do I set Forward running 1800 [min⁻¹] with network control and network reference for Instance 21/71 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP?
To set Forward running 1800 [min⁻¹] with network control and network reference for Instance 21/71 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP:
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 21 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0 | 0 | 1 | 0x0061 |
| 3, 2 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0x0708 | |
| Input Instance 71 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 1 | 1 | 1 | 1 | 0 | 1 | 0 | 0 | 0x04F4 |
| 3, 2 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0x0708 |
How do I perform a Fault reset for Instance 21/71 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP?
To perform a Fault reset for Instance 21/71 on the TOSHIBA TOSVERT VF-AS3 using EtherNet/IP (Fault reset*1):
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 21 | 1, 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0x0004 |
| 3, 2 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – |
*1 Fault reset works only 1 time when 0 -> 1.
What is the structure of Instance 22: CIP basic speed and torque control output mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 22 mapping for CIP basic speed and torque control output on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | – | – | – | – | Fault reset*1 | – | Run Fwd |
| 1 | – | – | – | – | – | – | – | – |
| 2 | Drive Speed Reference min⁻¹ (Low byte)*2 | |||||||
| 3 | Drive Speed Reference min⁻¹ (High byte)*2 | |||||||
| 4 | Drive Reference Torque Nm (Low byte) | |||||||
| 5 | Drive Reference Torque Nm (High byte) | |||||||
*1 Fault reset works only 1 time when 0 -> 1.
*2 Drive Speed Reference is set up number of rotations by the hexadecimal number. For example, when “Frequency reference” is set up to 1800 min-1: 1800 = 0x0708
What is the structure of Instance 23: CIP extended speed and torque control output mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 23 mapping for CIP extended speed and torque control output on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | Net Ref*1 | Net Ctrl*1 | – | – | Fault reset | Run Rev | Run Fwd |
| 1 | – | – | – | – | – | – | – | – |
| 2 | Drive Reference Speed min⁻¹ (Low byte) | |||||||
| 3 | Drive Reference Speed min⁻¹ (High byte) | |||||||
| 4 | Drive Reference Torque Nm (Low byte) | |||||||
| 5 | Drive Reference Torque Nm (High byte) | |||||||
*1 Bit 5 and 6 of the instance 21 byte 0 are defined as follows.
Bit 5 (Net Ctrl) ……………………………. When “1” is set, Run/Stop is according to bits 0 (Run forward) and 1 (Run reverse) of byte 0. When “0” is set, Run/Stop is according to setup of the parameter [CMOd].
Bit 6 (Net Ref) ……………………………. When “1” is set, Drive Reference Speed is according to bytes 2 and 3. When “0” is set, Drive Reference Speed is according to setup of the parameter [FMOd].
What is the structure of Instance 72: CIP basic speed control input mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 72 mapping for CIP basic speed control input on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | – | – | – | – | Running Fwd | – | Faulted |
| 1 | – | – | – | – | – | – | – | – |
| 2 | Drive Actual Speed min⁻¹ (Low byte) | |||||||
| 3 | Drive Actual Speed min⁻¹ (High byte) | |||||||
| 4 | Drive Actual Torque Nm (Low byte) | |||||||
| 5 | Drive Actual Torque Nm (High byte) | |||||||
What is the structure of Instance 73: CIP extended speed and torque control input mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 73 mapping for CIP extended speed and torque control input on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | At Reference *2 | Ref From Net*2 | Ctrl From Net*2 | Ready | Running 2 (Rev) | Running 1 (Fwd) | Warning | Faulted |
| 1 | Drive Status*3 | |||||||
| 2 | Drive Actual Speed min⁻¹ (Low byte) | |||||||
| 3 | Drive Actual Speed min⁻¹ (High byte) | |||||||
| 4 | Drive Actual Torque Nm (Low byte) | |||||||
| 5 | Drive Actual Torque Nm (High byte) | |||||||
*2 Bit 5, 6, and 7 of the instance 71 byte 0 are defined as follows.
Bit 5 (Ctrl from Net) …………………….. When RUN/STOP command from EtherNet/IP is enabled, “1” is set.
Bit 6 (Ref from Net) …………………….. When Drive Reference Speed from EtherNet/IP is enabled, “1” is set.
Bit 7 (At reference)……………………… When Drive Actual Speed becomes the same as frequency command, “1” is set.
*3 Drive Status is same as the Control Supervisor class State attribute (refer to section 4. 6. 2).
What is the structure of Instance 100: Toshiba control output mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 100 mapping for Toshiba control output on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | DC braking | AD mode 1/ AD mode 2 | PID off | V/f switching | Preset Speed 4 | Preset Speed 3 | Preset Speed 2 | Preset Speed 1 |
| 1 | Net Ctrl*1 | Net Ref*1 | Reset trip | Emergency stop (ST) | Free run (ST) | Run/stop | Forward/ Reverse | Jog run |
| 2 | Drive Reference Speed Hz (Low byte)*2 | |||||||
| 3 | Drive Reference Speed Hz (High byte)*2 | |||||||
*1 Bit 6 and 7 of the instance 100 byte 1 are defined as follows.
Bit 7 (Net Ctrl) ……………………………. When “1” is set, all commands of byte 0 and 1 are enabled. When “0” is set, commands other than Emergency stop and Reset trip are according to setup of the parameter [CMOd].
Bit 6 (Net Ref) ……………………………. When “1” is set, Drive Reference Speed is according to bytes 2 and 3. When “0” is set, Drive Reference Speed is according to setup of the parameter [FMOd].
*2 Drive Reference Speed is set up by 0.01Hz unit and the hexadecimal number. For example, when “Frequency reference” is set up to 60Hz, since the minimum unit is 0.01Hz, 60 / 0.01 = 6000 = 0x1770
What is the structure of Instance 150: Toshiba control input mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 150 mapping for Toshiba control input on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | DC braking | AD mode | PID | V/f 2 | MOFF | ALARM | EMG | FL |
| 1 | HAND/AUTO (LOC/REM) | READY without ST/RUN | READY with ST/ RUN | Emergency stopping (ST) | Free run (ST) | Run/Stop | Forward / Reverse | Jog running |
| 2 | Drive Actual Speed Hz (Low byte) | |||||||
| 3 | Drive Actual Speed Hz (High byte) | |||||||
How do I read the parameter [CMOd] (Command mode selection, communication number is 0003) using Instance 101/151 on the TOSHIBA TOSVERT VF-AS3?
To read the parameter [CMOd] (Command mode selection, communication number is 0003) using Instance 101/151 on the TOSHIBA TOSVERT VF-AS3:
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 101 | 5, 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0x0003 | |
| 7, 6 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| Input Instance 151 ([CMOd] is 0.) | 5, 4 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0x0003 | |
| 7, 6 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0x0000 |
How do I read the parameter [F268] (Initial value of UP/DOWN frequency) using Instance 101/151 on the TOSHIBA TOSVERT VF-AS3?
To read the parameter [F268] (Initial value of UP/DOWN frequency) using Instance 101/151 on the TOSHIBA TOSVERT VF-AS3, where [F268] is 60.0Hz:
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 101 | 5, 4 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 1 | 1 | 0 | 1 | 0 | 0 | 0 | 0x0268 |
| 7, 6 | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | – | |
| Input Instance 151 ([F268] is 60.0Hz.) | 5, 4 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 1 | 1 | 0 | 1 | 0 | 0 | 0 | 0x0268 |
| 7, 6 | 0 | 0 | 0 | 1 | 0 | 1 | 1 | 1 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0x1770 |
How do I write “60 (Hz)” to the parameter [Sr1] (Preset speed 1, communication number is 0018) using Instance 101/151 on the TOSHIBA TOSVERT VF-AS3?
To write “60 (Hz)” to the parameter [Sr1] (Preset speed 1, communication number is 0018) using Instance 101/151 on the TOSHIBA TOSVERT VF-AS3:
| Instance | Byte | 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | Hex. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Output Instance 101 | 5, 4 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0 | 0 | 0 | 0x8018 |
| 7, 6 | 0 | 0 | 0 | 1 | 0 | 1 | 1 | 1 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0x1770 | |
| Input Instance 151 (OK) | 5, 4 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0 | 0 | 0 | 0x8018 |
| 7, 6 | 0 | 0 | 0 | 1 | 0 | 1 | 1 | 1 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0x1770 | |
| Input Instance 151 (NG) (Error code*1) | 5, 4 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 | 0 | 0 | 0 | 0 | 0xC018 |
| 7, 6 | 0 | 0 | 0 | 1 | 0 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0x1100 |
*1 Data of “Error code”
0x1100: Data out of range
0x1101: Bad address
0x1103: Read only address / Password protection
0x1106: Read only during running
What is the structure of Instance 102: Native transport control output mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 102 mapping for Native transport control output on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | [C641] Command data (Low byte) | |||||||
| 1 | [C641] Command data (High byte) | |||||||
| 2 | [C642] Command data (Low byte) | |||||||
| 3 | [C642] Command data (High byte) | |||||||
| 4 | [C643] Command data (Low byte) | |||||||
| 5 | [C643] Command data (High byte) | |||||||
| 6 | [C644] Command data (Low byte) | |||||||
| 7 | [C644] Command data (High byte) | |||||||
| 8 | [C645] Command data (Low byte) | |||||||
| 9 | [C645] Command data (High byte) | |||||||
| 10 | [C646] Command data (Low byte) | |||||||
| 11 | [C646] Command data (High byte) | |||||||
Refer to “Emb Eth. Scanner input select ([C641] – [C650])” for detail of Command data.
What is the structure of Instance 152: Native transport control input mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 152 mapping for Native transport control input on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | [C651] Monitor data (Low byte) | |||||||
| 1 | [C651] Monitor data (High byte) | |||||||
| 2 | [C652] Monitor data (Low byte) | |||||||
| 3 | [C652] Monitor data (High byte) | |||||||
| 4 | [C653] Monitor data (Low byte) | |||||||
| 5 | [C653] Monitor data (High byte) | |||||||
| 6 | [C654] Monitor data (Low byte) | |||||||
| 7 | [C654] Monitor data (High byte) | |||||||
| 8 | [C655] Monitor data (Low byte) | |||||||
| 9 | [C655] Monitor data (High byte) | |||||||
| 10 | [C656] Monitor data (Low byte) | |||||||
| 11 | [C656] Monitor data (High byte) | |||||||
Refer to “Emb Eth. Scanner output select ([C651] – [C660])” for detail of Monitor data.
Memo • Command/Monitor targets are determined by scanner address setting value at startup of Class 1 connection.
What is the structure of Instance 105: Native transport and parameter change control output mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 105 mapping for Native transport and parameter change control output on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | – | – | – | – | – | – | – |
| 1 | Function code (Read / Write) results Read: 0x00, Write: 0x80 Read error: 0x40, Write error: 0xC0 |
|||||||
| 2 | Index (Low byte) | |||||||
| 3 | Index (High byte) | |||||||
| 4 | Data (Low byte) | |||||||
| 5 | Data (High byte) | |||||||
| 6 | [C641] Command data (Low byte) | |||||||
| 7 | [C641] Command data (High byte) | |||||||
| 8 | [C642] Command data (Low byte) | |||||||
| 9 | [C642] Command data (High byte) | |||||||
| 10 | [C643] Command data (Low byte) | |||||||
| 11 | [C643] Command data (High byte) | |||||||
| 12 | [C644] Command data (Low byte) | |||||||
| 13 | [C644] Command data (High byte) | |||||||
| 14 | [C645] Command data (Low byte) | |||||||
| 15 | [C645] Command data (High byte) | |||||||
| 16 | [C646] Command data (Low byte) | |||||||
| 17 | [C646] Command data (High byte) | |||||||
Refer to “Emb Eth. Scanner input select ([C641] – [C650])” for detail of Command data.
What is the structure of Instance 155: Native transport and parameter change control input mapping for the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object?
The Instance 105 mapping for Native transport and parameter change control input on the TOSHIBA TOSVERT VF-AS3 EtherNet/IP object is:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | – | – | – | – | – | – | – | – |
| 1 | Function code (Read / Write) results Read: 0x00, Write: 0x80 Read error: 0x40, Write error: 0xC0 |
|||||||
| 2 | Index (Low byte) | |||||||
| 3 | Index (High byte) | |||||||
| 4 | Data (Low byte) | |||||||
| 5 | Data (High byte) | |||||||
| 6 | [C651] Monitor data (Low byte) | |||||||
| 7 | [C651] Monitor data (High byte) | |||||||
| 8 | [C652] Monitor data (Low byte) | |||||||
| 9 | [C652] Monitor data (High byte) | |||||||
| 10 | [C653] Monitor data (Low byte) | |||||||
| 11 | [C653] Monitor data (High byte) | |||||||
| 12 | [C654] Monitor data (Low byte) | |||||||
| 13 | [C654] Monitor data (High byte) | |||||||
| 14 | [C655] Monitor data (Low byte) | |||||||
| 15 | [C655] Monitor data (High byte) | |||||||
| 16 | [C656] Monitor data (Low byte) | |||||||
| 17 | [C656] Monitor data (High byte) | |||||||
Refer to “Emb Eth. Scanner output select ([C651] – [C660])” for detail of Monitor data.
Memo • Command/Monitor targets are determined by scanner address setting value at startup of Class 1 connection.
How can I connect to the webserver of the TOSHIBA TOSVERT VF-AS3?
The webserver of the TOSHIBA TOSVERT VF-AS3 can be accessed by standard browsers like Edge, chrome, safari and Firefox (Firefox is supported with inverter CPU1 version 116 or later).
In the following example, the Inverter has assigned the IP address 192.168.0.10: Enter the IP address of inverter after “http://” in the URL entry field of the browser to connect.
What should I enter for the first access to the TOSHIBA TOSVERT VF-AS3 web server login?
For the first access to the TOSHIBA TOSVERT VF-AS3 web server, enter “ADMIN” for the user name and the password and click the Login button. For the second access and later, enter the user name and password set in advance.
How can the password for the TOSHIBA TOSVERT VF-AS3 web server be initialized?
At the time of first access to the TOSHIBA TOSVERT VF-AS3 web server, change the password to a new one. The password can be initialized by setting [C669] = “1”, however, all the settings of the web server are also initialized then. It can be also initialized by the [tyP] function.
What must be done after accepting the instructions for use when accessing the TOSHIBA TOSVERT VF-AS3 web server?
Instructions for use are displayed. Click the [OK] button after accepting the contents for the TOSHIBA TOSVERT VF-AS3 web server.
How do I move between pages on the TOSHIBA TOSVERT VF-AS3 web server?
Each page on the TOSHIBA TOSVERT VF-AS3 web server has tabs displayed to move to another page. For example, when you want to move the Parameter page, you can move there by clicking the “Parameter” tab.
What is the function of the side menu on pages other than My Dashboard in the TOSHIBA TOSVERT VF-AS3 web server?
Each page on the TOSHIBA TOSVERT VF-AS3 web server except for My Dashboard has a side menu. When you click each menu item, the corresponding page is displayed. When you click the upper right of the side menu, it is minimized. The side menu that has been minimized is displayed again, when you click the minimized icon.
What is the function of the My Dashboard page on the TOSHIBA TOSVERT VF-AS3 web server?
The My Dashboard page on the TOSHIBA TOSVERT VF-AS3 web server is the first page displayed when you log in. You can add, delete, and move all the widgets, so you can display only information necessary for you and the setting window.
To add a widget, click the “Add Widget” tab at the upper right of the screen to display the widget menu. Select a widget to be added, drag and drop it.
You can edit a widget from buttons displayed on the title bar.
The Ethernet communication may stop when editing My Dashboard. Therefore, do not edit the My Dashboard when inverter is running.
If widget can’t be added to My Dashboard, reduce the number of widgets.
What caution should be observed when editing the My Dashboard on the TOSHIBA TOSVERT VF-AS3 web server?
Do not edit the My Dashboard when inverter is running on the TOSHIBA TOSVERT VF-AS3. If you change My Dashboard, this will stop the Ethernet communication and cause the unexpected movement.
How can a chart widget be added to the My Dashboard on the TOSHIBA TOSVERT VF-AS3 web server?
To add a chart, drag and drop the “Chart” icon and add the chart widget into the page on the TOSHIBA TOSVERT VF-AS3 web server. You can move each widget by dragging the title bar.
How can a widget be deleted from the My Dashboard on the TOSHIBA TOSVERT VF-AS3 web server?
You can delete a widget that has been once added with the deletion button with X mark at the upper right of the widget on the TOSHIBA TOSVERT VF-AS3 web server.
What functions are available on the Tool button in the widget title bar of the TOSHIBA TOSVERT VF-AS3 web server?
The Tool button in the widget title bar on the TOSHIBA TOSVERT VF-AS3 web server allows you to change the setting of the widget. With the Data Viewer widget, you can select a monitor table to be displayed.
What is the function of the Jump button in the widget title bar on the TOSHIBA TOSVERT VF-AS3 web server?
The Jump button in the widget title bar on the TOSHIBA TOSVERT VF-AS3 web server allows you to move to the page corresponding to the table displayed in the widget. For example, you can move from the IO Status widget of Data Viewer to IO Status of the Display page.
How can a new monitor table be created in the Display page of the TOSHIBA TOSVERT VF-AS3 web server?
To create a new monitor table on the Display page of the TOSHIBA TOSVERT VF-AS3 web server, click “+ Create New Table” of the side menu to move to the table creation screen. Here, you can select up to ten parameters to be displayed on the monitor to create a new table.
You can filter parameters with the character string entered in the Filter entry field when you select parameters. If you already know the title of the parameter you want to add, you can add it directly to the table by entering the title in the Parameter entry field and clicking the green + mark.
An X button is displayed on the right of the table/chart newly created. You can delete tables except for the preset one by clicking this X button.
How can a new chart be created in the Display page of the TOSHIBA TOSVERT VF-AS3 web server?
When you click “+ Create New Chart” of the side menu on the Display page of the TOSHIBA TOSVERT VF-AS3 web server, you can create a new chart in a similar way to creating a table. When creating a chart, you can separately select the update cycle (s), number of plots, and whether auto scale should be applied or not.
An X button is displayed on the right of the table/chart newly created. You can delete charts except for the preset one by clicking this X button.
How can TCP/IP settings, theme, and password be changed in the Setup page of the TOSHIBA TOSVERT VF-AS3 web server?
In the Setup page on the TOSHIBA TOSVERT VF-AS3 web server, you can change the TCP/IP settings, theme, and password and manage the account.
How can IP settings and the device name be set/checked in the TCP/IP menu of the Setup page on the TOSHIBA TOSVERT VF-AS3 web server?
In the TCP/IP menu of the Setup page on the TOSHIBA TOSVERT VF-AS3 web server, you can set the IP settings and the device name and check the MAC address. Change of the device name is reflected immediately, but the IP settings are enabled after reset.
How can SNTP settings be configured in the Time menu of the Setup page on the TOSHIBA TOSVERT VF-AS3 web server?
In the Time menu of the Setup page on the TOSHIBA TOSVERT VF-AS3 web server, you can set the SNTP settings. SNTP is disabled by default.
Note: When the operation panel is not mounted on the inverter, SNTP function does not work.
How can the web page design be copied using the Web Design Transfer menu on the TOSHIBA TOSVERT VF-AS3 web server?
In the Web Design Transfer menu on the TOSHIBA TOSVERT VF-AS3 web server, you can Copy the web page design. My dashboard of the logged in account, monitor viewer table, chart viewer and inverter parameter table will be copied.
When you click the “Copy from Device to PC”, Web server design data will be downloaded to PC with the file name “WebDesign.dat”.
After logging in to the account of the device you want to copy the My dashboard, click “Copy from PC to Device” and upload “WebDesign.dat” to the device, the Web server design data will be reflected on the device.
Note) Please refresh the page after copying to correctly reflect changes.
How can user accounts be managed in the User Access menu of the Setup page on the TOSHIBA TOSVERT VF-AS3 web server?
You can manage the account in the User Access menu on the TOSHIBA TOSVERT VF-AS3 web server. You can create account for up to 10 by selecting whether the administrator privileges and the write permission are given. You can create the account according to the applications. For example, account for monitoring, account for make adjustment, etc.
How is a new user account created on the TOSHIBA TOSVERT VF-AS3 web server?
When you click the plus button on the top of the screen on the TOSHIBA TOSVERT VF-AS3 web server, you can move to the account creation screen. When you enter the user name, password, and privileges and permission to be given and click the “Create” button, a new account is created.
What happens when a user logs in with an account that does not have the administrator privileges on the TOSHIBA TOSVERT VF-AS3 web server?
When a user logs in with an account that does not have the administrator privileges on the TOSHIBA TOSVERT VF-AS3 web server, the tab to access the Setup page is not displayed so that change of the user account can be prevented.
What happens when a user tries to change a parameter with an account that does not have the write permission on the TOSHIBA TOSVERT VF-AS3 web server?
When the user tries to change a parameter with account that does not have the write permission on the TOSHIBA TOSVERT VF-AS3 web server, the frame is displayed in gray and becomes unchangeable so that writing from an account for monitoring can be prevented.
What actions can an administrator perform on user accounts in the User Access section of the TOSHIBA TOSVERT VF-AS3 web server?
From an account that has the administrator privileges on the TOSHIBA TOSVERT VF-AS3 web server, the user can block an account by clicking the delete button and can change the password forcibly by clicking the reset button.
How can the base color of the page theme be changed in the Themes menu of the TOSHIBA TOSVERT VF-AS3 web server?
In the Themes menu on the TOSHIBA TOSVERT VF-AS3 web server, you can select the base color of the page between blue and red. When you click the name of the theme, the base color is changed.