Free English TOSHIBA TOSVERT VF-AS3 (04) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD TOSHIBA TOSVERT VF-AS3 (04) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What precautions should be taken when installing and wiring the DeviceNet option for the TOSHIBA TOSVERT VF-AS3?
Mandatory actions for installing and wiring the option include:
- Shut off power when installing and wiring this option.
- Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit. If steps above are not properly performed, this can result in electric shock or product failure.
- Use an emergency stop device and an additional safety device in your system to prevent serious accident due to the option malfunctions. Usage without any emergency stop device or any additional safety device can result in accident or injury.
- Use an additional safety device with your system to prevent a serious accident due to the network malfunctions. Usage without an additional safety device may cause an accident.
- Make sure that the operation signals are STOP before resetting drive’s fault. The motor may suddenly start and that may result in injuries.
- Do not pull on any cable itself. Doing so could result in damage or malfunction.
What are prohibited actions related to the DeviceNet option for the TOSHIBA TOSVERT VF-AS3?
Prohibited actions include:
- Do not connect to any communication device other than the one supported. It may cause an accident.
- Do not touch the sharp edges of the inverter or option. Doing so could result in injury.
- Do not use application of writing into inverter parameters more than 100,000 times. The Life of EEPROM is approximately 100,000 times. Frequent writing to the EEPROM of inverter will cause a memory corruption.
- Insert an electromagnetic contactor between the inverter and the power supply so that the machine can be stopped without fail from an external controller in case of an emergency.
- Check DeviceNet state (using below attribute) when the option is deactivated by an unusual event such as an operating error, power outage, failure, etc. (Identity Object Instance Attributes 8 (State) – The communication error occurs when Fault (4, 5) or this value cannot be read.) Deactivated option may cause an accident, if the DeviceNet state is not checked.
What are the notes on use for the DeviceNet option on the TOSHIBA TOSVERT VF-AS3?
Notes on use:
- Please install away from the place where temperature and humidity change rapidly.
- Keep a distance of 20cm or more between the drive ‘s power cable and the data transmission cable. Or the drive might malfunction because of noise.
- If the control power is turned off due to momentary power failure etc., communication can not be performed temporarily.
What are the mounting and removing instructions for the DeviceNet option on the TOSHIBA TOSVERT VF-AS3?
The mounting/removing of the option must be performed without supplying power. Turn off all input power, wait at least 15 minutes, and confirm that the charge lamp of the inverter is no longer lit. The inverter and option can become damaged. Do not use a tool for the mounting/removing of the option. The inverter and option can become damaged.
For how to mount and remove the option for VF-AS3, refer to [Mounting/removing insert type options] of E6582062.
How is the DeviceNet baud rate setup for the TOSHIBA TOSVERT VF-AS3 DeviceNet option (DEV003Z)?
The DeviceNet baud rate setup is controlled by the inverter parameter (200. as shown in the table:
| Parameter | Function | Adjustment range | Default setting |
|---|---|---|---|
| (200 | DEV003Z MAC ID | 0 to 63 | 63 |
| (201 | DEV003Z Communication baud rate | 0: AUTO * 1: 125kbps 2: 250kbps 3: 500kbps |
0 |
| (202 | DeviceNet Baud rate monitor | 1: 125kbps 2: 250kbps 3: 500kbps |
– |
Note: DeviceNet baud rate is 500kbps and with a few slaves in the network, auto baud rate function might not work.
How is the inverter operation at the communications loss action (Network wire breaks) for the TOSHIBA TOSVERT VF-AS3 configured using parameter (101?
The inverter operation at the communications loss action is set by parameter (101 as follows:
| Parameter (101) | Inverter operation at the communications loss action (Network wire breaks) |
|---|---|
| 0 | Stop and Communication release ** (follows (70d and F708 setting) |
| 1 | Operation continue |
| 2 | Deceleration stop |
| 3 | Coast stop |
| 4 | Emergency stop (Err.8) |
| 5 | Preset speed operation command (Operating at the preset speed operation frequency set with (102) |
Caution: Please note that the inverter keeps driving when the communication is lost if 1 (None) is set to the parameter (101 (Inverter operation at the communications loss action).
How can a TOSHIBA TOSVERT VF-AS3 be switched between Local and Remote modes using the terminal block?
The switching between Local and Remote modes can be controlled via the terminal block function as shown in the example for VF-AS3:
- F terminal: RUN command
- R terminal: DeviceNet /Local (Terminal in this example) switching
- RR terminal: Operation frequency command
- (70d (command mode selection) = 0 (terminal board)
- F708 (frequency setting mode selection 1) = 1 (RR)
- F112 (input terminal selection 2 (R)) = 48 (DeviceNet/Local control)
- R-P24 terminal open: VF-AS3 is controlled as slave device of DeviceNet.
- R-P24 terminal closed:
- F-P24 terminal short to RUN
- F-P24 terminal open to STOP
- Output frequency is set up by the RR signal input.
What are the definitions for the bits in the Output Instance 20 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 20/70?
The Output Instance 20 Layout (DeviceNet Standard, parameter (203 = 0) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | Fault reset | Run reverse | Run forward | |||||
| 1 | Inverter Reference Speed min-1 (Low byte) * | |||||||
| 2 | Inverter Reference Speed min-1 (High byte) * | |||||||
| 3 | ||||||||
What are the definitions for the bits in the Input Instance 70 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 20/70?
The Input Instance 70 Layout (DeviceNet Standard, parameter (203 = 0) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | Running Forward | Faulted/ tripped | ||||||
| 1 | ||||||||
| 2 | Inverter Actual Speed min-1 (Low byte) | |||||||
| 3 | Inverter Actual Speed min-1 (High byte) | |||||||
What are the definitions for the bits in the Output Instance 21 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 21/71?
The Output Instance 21 Layout (DeviceNet Standard, parameter (203 = 1) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | Net Ref * | Net Ctrl * | Fault reset | Run reverse | Run forward | |||
| 1 | ||||||||
| 2 | Inverter Reference Speed min-1 (Low byte) ** | |||||||
| 3 | Inverter Reference Speed min-1 (High byte) ** | |||||||
What are the definitions for the bits in the Input Instance 71 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 21/71?
The Input Instance 71 Layout (DeviceNet Standard, parameter (203 = 1) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | At reference *** | Ref from Net *** | Ctrl from Net *** | Ready | Running Reverse | Running Forward | Warning | Faulted/ tripped |
| 1 | Error | |||||||
| 2 | Inverter Actual Speed min-1 (Low byte) | |||||||
| 3 | Inverter Actual Speed min-1 (High byte) | |||||||
How are the bits 5 and 6 of Instance 21 byte 0 defined for the TOSHIBA TOSVERT VF-AS3 when using Instance 21/71?
Bit 5 (Net Ctrl) and Bit 6 (Net Ref) of Instance 21 byte 0 are defined as follows:
- Bit 5 (Net Ctrl): When “1” is set, bits 0 (Run forward) and 1 (Run reverse) of byte 0 are enabled. When “0” is set, Run/Stop is according to setup of the inverter parameter (708.
- Bit 6 (Net Ref): When “1” is set, Inverter Reference Speed is according to the value of bytes 2 and 3. When “0” is set, Inverter Reference Speed is according to setup of the inverter parameter F708.
How are bits 5, 6, and 7 of Instance 71 byte 0 defined for the TOSHIBA TOSVERT VF-AS3 when using Instance 21/71?
Bits 5, 6, and 7 of Instance 71 byte 0 are defined as follows:
- Bit 5 (Ctrl from Net): When RUN/STOP command from DeviceNet is enabled, “1” is set.
- Bit 6 (Ref from Net): When frequency command from DeviceNet is enabled, “1” is set.
- Bit 7 (At reference): When output frequency becomes the same as frequency command, “1” is set.
What are the definitions for the bits in the Output Instance 100 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 100/150 (Toshiba Specific, parameter (203 = 2)?
The Output Instance 100 Layout (Toshiba Specific, parameter (203 = 2) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 | |
|---|---|---|---|---|---|---|---|---|---|
| 0 | DC braking | ACC1/ACC2 | PID control off | THR1,VF1/THR2,VF2 | Preset speed stop | Preset Speed4 | Preset Speed3 | Preset Speed2 | Preset Speed1 |
| 1 | Command link * | Frequency link * | Fault trip | Emergency command | Coast stop command | Run/Stop | Forward/Reverse | Jog run | |
| 2 | Inverter Reference Speed Hz (Low byte) ** | ||||||||
| 3 | Inverter Reference Speed Hz (High byte) ** | ||||||||
What are the definitions for the bits in the Input Instance 150 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 100/150 (Toshiba Specific, parameter (203 = 2)?
The Input Instance 150 Layout (Toshiba Specific, parameter (203 = 2) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | DC braking | ACC1/ACC2 | PID control off | THR1,VF1/THR2,VF2 | Under voltage (NOFF) | ALARM (FC91) | Failure | Failure FL |
| 1 | HAND/AUTO **** | Standby ST=ON | Emergency stop | Coast stop (ST off) | Run/Stop | Forward/Reverse | Jog run | |
| 2 | Inverter Actual Speed Hz (Low byte) | |||||||
| 3 | Inverter Actual Speed Hz (High byte) | |||||||
How are Bit 7 and Bit 6 of the instance 100 byte 1 defined for the TOSHIBA TOSVERT VF-AS3 when using Instance 100/150?
Bit 7 (Command link) and Bit 6 (Frequency link) of the instance 100 byte 1 are defined as follows:
- Bit 7 (Command link): When “0” is set, the other command does not work except bit 4 and 3 of instance 100 byte 1, Run/Stop is according to setup of the inverter parameter (N0d.
- Bit 6 (Frequency link): When “1” is set, Inverter Reference Speed is according to the value of bytes 2 and 3. When “0” is set, Inverter Reference Speed is according to setup of the inverter parameter FNO8.
How are Bit 5, 6, and 7 of the instance 151 byte 0 defined for the TOSHIBA TOSVERT VF-AS3 when using Instance 101/151?
Bits 5, 6, and 7 of the instance 151 byte 0 are defined as follows:
- Bit 5 (Ctrl from Net): When RUN/STOP command from DeviceNet is enabled, “1” is set.
- Bit 6 (Ref from Net): When frequency command from DeviceNet is enabled, “1” is set.
- Bit 7 (At reference): When output frequency becomes the same as frequency command, “1” is set.
What are the definitions for the bits in the Output Instance 106 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 106/156 (Toshiba Specific, parameter (203 = 6) for VF-AS3 only?
The Output Instance 106 Layout (Toshiba Specific, parameter (203 = 6) (Only VF-AS3) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | Net Ref * | Net Ctrl * | Fault reset | Run reverse | Run forward | |||
| 1 | Write | |||||||
| 2 | Inverter Reference Speed min-1 (Low byte) ** | |||||||
| 3 | Inverter Reference Speed min-1 (High byte) ** | |||||||
| 4 | Index (Low byte) | |||||||
| 5 | Index (High byte) | |||||||
| 6 | Data (Low byte) | |||||||
| 7 | Data (High byte) | |||||||
What are the definitions for the bits in the Input Instance 156 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 106/156 (Toshiba Specific, parameter (203 = 6) for VF-AS3 only?
The Input Instance 156 Layout (Toshiba Specific, parameter (203 = 6) (Only VF-AS3) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | At reference *** | Ref from Net *** | Ctrl from Net *** | Ready | Running Reverse | Running Forward | Warning | Faulted/ tripped |
| 1 | Error | |||||||
| 2 | Inverter Actual Speed min-1 (Low byte) | |||||||
| 3 | Inverter Actual Speed min-1 (High byte) | |||||||
| 4 | Index (Low byte) | |||||||
| 5 | Index (High byte) | |||||||
| 6 | Data (Low byte) | |||||||
| 7 | Data (High byte) | |||||||
What is the definition of Bit 5 (Net Ctrl) for Instance 106 byte 0 when using Instance 106/156 on the TOSHIBA TOSVERT VF-AS3?
For Instance 106 byte 0, Bit 5 (Net Ctrl) is defined as: When “1” is set, bits 0 (Run forward) and 1 (Run reverse) of byte 0 are enabled. When “0” is set, Run/Stop is according to setup of the inverter parameter (2008.
How can the inverter parameters be accessed using the Parameter Object (Vender Specific Profiles) for the TOSHIBA TOSVERT VF-AS3?
The inverter parameter access is provided by Class code 0x65 (Attribute ID is 3, inverter parameter number is set as Instance ID).
For example, to set 5 sec. to “Acc. time” (minimum unit 0.1 sec., set value 50 = 0x0032 (Hex.), communication number “0009”): set the value 0x0032 to Class 0x65, Instance 0009, Attribute 3 to use Set Single Attribute service.
Parameter AU I cannot be accessed by using Class 0x65. Please, use Class 0x64.
For Class code 0x64:
- All parameter’s Attribute ID is 3.
- The instance ID should be set “VF-MB1 or VF-S15 parameter communication number + 0x4000”.
- In the case of the parameter from which a communication number begins in “F”, it should be set “the inverter parameter communication number – 0x8000 (same as bit 15 set to 0)”.
Examples for Class 0x64:
- In case of Basic parameter “C70d – Command mode selection”, Communication No: 0003 -> Instance ID: 4003
- In case of Extended parameter “F300 – PWM carrier frequency”, Communication No: 0300 -> Instance ID: 4300
- In case of Monitor parameter “FE03 – Output current”, Communication No: FE03 -> Instance ID: 7E03. Monitor parameter can access “Get” only.
Caution: Do not use application of writing into inverter parameters more than 100,000 times. The Life of EEPROM is approximately 100,000 times. Frequent writing to the EEPROM of inverter will cause a memory corruption.
What are the definitions for the bits in the Output Instance 102 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 102/152 (Toshiba Specific, parameter (203 = 4)?
The Output Instance 102 Layout (Toshiba Specific, parameter (203 = 4) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | C001 Command data (Low byte) | C001 Command data (High byte) | ||||||
| 1 | C002 Command data (Low byte) | C002 Command data (High byte) | ||||||
| 2 | C003 Command data (Low byte) | C003 Command data (High byte) | ||||||
| 3 | C004 Command data (Low byte) | C004 Command data (High byte) | ||||||
| 4 | C005 Command data (Low byte) | C005 Command data (High byte) | ||||||
| 5 | C006 Command data (Low byte) | C006 Command data (High byte) | ||||||
| 6-11 | ||||||||
What are the definitions for the bits in the Input Instance 152 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 102/152 (Toshiba Specific, parameter (203 = 4)?
The Input Instance 152 Layout (Toshiba Specific, parameter (203 = 4) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | C021 Monitor data (Low byte) | C021 Monitor data (High byte) | ||||||
| 1 | C022 Monitor data (Low byte) | C022 Monitor data (High byte) | ||||||
| 2 | C023 Monitor data (Low byte) | C023 Monitor data (High byte) | ||||||
| 3 | C024 Monitor data (Low byte) | C024 Monitor data (High byte) | ||||||
| 4 | C025 Monitor data (Low byte) | C025 Monitor data (High byte) | ||||||
| 5 | C026 Monitor data (Low byte) | C026 Monitor data (High byte) | ||||||
| 6-11 | ||||||||
How is Command transmitting by the output Instance 102 configured for the TOSHIBA TOSVERT VF-AS3 when using Instance 102/152?
To transmit a command using Output Instance 102:
When you want to set “0xC400″ to parameter FA06, set “1 (FA06)” to parameter C001.
Since 0 and 1 byte of the output instance 102 supports the parameter C001, if “0xC400” is set up here, “0xC400” will be set as FA06.
Example: Command transmitting by the output Instance 102.
| The drive | DEV003Z | DeviceNet Master Output Instance 102 | ||
|---|---|---|---|---|
| Parameter | Value | |||
| C001 | 1 (FA06) | |||
| C002 | ||||
| C003 | ||||
| … | ||||
The setting “0xC400” is set as the parameter FA06.
| Byte | Data |
|---|---|
| 0 | 00 |
| 1 | C4 |
| 2 | |
| 3 |
How is state monitoring configured using the input instance 152 for the TOSHIBA TOSVERT VF-AS3 when using Instance 102/152?
To monitor the output current using Input Instance 152:
Set “3 (F803)” to parameter C021.
The value of the parameter F803 specified as 0 and 1 byte of the input instance 152 with the parameter C021 is inputted.
Example: State monitor by the input instance 152.
| The drive | DEV003Z | DeviceNet Master Input Instance 152 | ||
|---|---|---|---|---|
| Parameter | Value | |||
| C021 | 3 (F803) | |||
| C022 | ||||
| C023 | ||||
The value of the parameter Fd03 (ex.0x1234) outputted.
| Byte | Data |
|---|---|
| 0 | 34 |
| 1 | 12 |
| 2 | |
| 3 |
What are the definitions for the bits in the Output Instance 105 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 105/155 (Toshiba Specific, parameter (203 = 5)?
The Output Instance 105 Layout (Toshiba Specific, parameter (203 = 5) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | Function code (Read/Write command)*1 | |||||||
| 1 | ||||||||
| 2 | Index (Low byte) | |||||||
| 3 | Index (High byte) | |||||||
| 4 | Data (Low byte) | |||||||
| 5 | Data (High byte) | |||||||
| 6 | C001 Command data (Low byte) | C001 Command data (High byte) | ||||||
| 7 | C002 Command data (Low byte) | C002 Command data (High byte) | ||||||
| 8 | C003 Command data (Low byte) | C003 Command data (High byte) | ||||||
| 9 | C004 Command data (Low byte) | C004 Command data (High byte) | ||||||
| 10 | C005 Command data (Low byte) | C005 Command data (High byte) | ||||||
| 11 | C006 Command data (Low byte) | C006 Command data (High byte) | ||||||
| 12-17 | ||||||||
What are the definitions for the bits in the Input Instance 155 Layout for the TOSHIBA TOSVERT VF-AS3 when using Instance 105/155 (Toshiba Specific, parameter (203 = 5)?
The Input Instance 155 Layout (Toshiba Specific, parameter (203 = 5) is defined as follows:
| Byte | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
|---|---|---|---|---|---|---|---|---|
| 0 | Function code (Read/Write response)*2 | |||||||
| 1 | ||||||||
| 2 | Index (Low byte) | |||||||
| 3 | Index (High byte) | |||||||
| 4 | Data (Low byte) | |||||||
| 5 | Data (High byte) | |||||||
| 6 | C021 Monitor data (Low byte) | C021 Monitor data (High byte) | ||||||
| 7 | C022 Monitor data (Low byte) | C022 Monitor data (High byte) | ||||||
| 8 | C023 Monitor data (Low byte) | C023 Monitor data (High byte) | ||||||
| 9 | C024 Monitor data (Low byte) | C024 Monitor data (High byte) | ||||||
| 10 | C025 Monitor data (Low byte) | C025 Monitor data (High byte) | ||||||
| 11 | C026 Monitor data (Low byte) | C026 Monitor data (High byte) | ||||||
| 12-17 | ||||||||
What is the purpose of instances 102/152 (Byte 0 – 11) and 105/155 (Byte 6 – 17) for the TOSHIBA TOSVERT VF-AS3?
The purposes of instances 102/152 (Byte 0 – 11) and 105/155 (Byte 6 – 17) are adjustment by real time command transmission, and the monitor of an operation state by using cyclic communication of DeviceNet.
How is the Command mode selection parameter (C70d) set via communication command 1 (FA06) for the TOSHIBA TOSVERT VF-AS3 using Output Instance 102?
To set Command mode selection via communication command 1 (FA06) using Output Instance 102:
Set “1 (FA06)” to parameter C001 when you want to set the desired value for FA06. Since bytes 0 and 1 of Output Instance 102 support the parameter C001, setting “0xC400” to these bytes will set FA06 to “0xC400”.
Example of setting FA06 to 0xC400:
| Byte | Data | Hex. |
|---|---|---|
| 0 | 0000000000000000 | 0x0000 |
| 1 | 0000000000000011 | 0x0003 |
| 2 | ||
| 3 |
How are the bits for VF/f switching 1 defined in the command FA06 for the TOSHIBA TOSVERT VF-AS3?
For VF-MB1/S15:
| Bit | Function | 0 | 1 | Note |
|---|---|---|---|---|
| 4 | Motor selection (1 or 2) (THR 2 selection) | Motor 1 (THR 1) | Motor 2 (THR 2) | THR 1: PE = setting value, ul, ulu, ub, Ehr THR 2: PE = 0,F170,F171, F172,F 173 |
For VF-AS3:
| Bit | Function | 0 | 1 | Note |
|---|---|---|---|---|
| 4 | V/f switching 1 (*2) | V/f 1 | V/f 2 | V/f 1: PE = setting value, ul, ulu, ub, EH-A V/f 2: PE = “0”, F170,F171, F172,F182 |
How is the frequency command set up by FA07 for the TOSHIBA TOSVERT VF-AS3?
Frequency reference is set up by 0.01Hz unit and the hexadecimal number. For example, when “Frequency reference” is set up to 80Hz, since the minimum unit is 0.01Hz, 80/0.01 = 8000 = 0x1F40 (Hex.) is used.
How is the torque command set up by FA33 for the TOSHIBA TOSVERT VF-AS3?
Torque reference is set up by 0.01% unit and the hexadecimal number. For example: when “torque command” is set up to “50%”, since the minimum unit is 0.01%, 50%=50+0.01=5000=1388H is used.
How can terminal output data (FA50) be controlled via communication for the TOSHIBA TOSVERT VF-AS3?
By setting up the data of the bit 0 – 1 of terminal output data (FA50) from communication, setting data (OFF or ON) can be outputted to the output terminal. You must select the functional number 92 – 95 as the selection of the output terminal function parameter before using it.
| bit | Output TB function name | 0 | 1 |
|---|---|---|---|
| 0 | Specified data output 1 (Output terminal No.: 92, 93) | OFF | ON |
| 1 | Specified data output 2 (Output terminal No.: 94, 95) | OFF | ON |
| 2-15 | (Reserved) | – | – |
Note: Set 0 to reserved bit.
How can the output frequency (real time) be read using FA00 for the TOSHIBA TOSVERT VF-AS3?
The current output frequency is read into 0.01Hz of units and by the hexadecimal number. For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%, 0x1F40 (Hex.) = 8000 (Dec.) * 0.01 = 80.00 (Hz).
Also about the following parameters, these are the same as this:
- Fd22 (Feedback value of PID (real time)): Unit: 0.01Hz
- Fd16 (Estimated speed (real time)): Unit: 0.01Hz
- Fd29 (Input power (real time)): Unit: 0.01kW
- F630 (Output power (real time)): Unit: 0.01kW
How can the output current (real time) be read using FA03 for the TOSHIBA TOSVERT VF-AS3?
The output current is read into 0.01% of units and by the hexadecimal number. For example, when the output current of the rated current 4.8A inverter is 50% (2.4A), 0x1388 (hexadecimal number) is read out.
Since the minimum unit is 0.01%, 0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%).
Also about the following parameters, these are the same as this:
- F805 (Output voltage (real time)): Unit: 0.01% (V)
- F804 (Voltage at DC bus (real time)): Unit: 0.01% (V)
- Fd18 (Torque): Unit: 0.01% (N·m)* (100% means the rated motor torque calculated by the motor constant parameters (F405 – F417))
How can the cumulative operation time (FE14) be read for the TOSHIBA TOSVERT VF-AS3?
The operated cumulative time is read by the hexadecimal number. For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read. 0x12 (Hex.) = 18 (Dec., hour).
How can the alarm information (FC91) be interpreted for the TOSHIBA TOSVERT VF-AS3?
The alarm information (FC91) for VF-AS3 is indicated by panel display based on the bit status:
| bit | Function | 0 | 1 | Panel display |
|---|---|---|---|---|
| 0 | Overcurrent alarm | Normal | Alarming | [] flicking |
| 1 | Inverter over load alarm | Normal | Alarming | [1] flicking |
| 2 | Motor over load alarm | Normal | Alarming | [1] flicking |
| 3 | Overheat alarm | Normal | Alarming | [H] flicking |
| 4 | Overvoltage alarm | Normal | Alarming | [F] flicking |
| 6 | Inverter overheat alarm | Normal | Alarming | [] flicking |
| 7 | Undercurrent alarm | Normal | Alarming | |
| 8 | Overtorque alarm | Normal | Alarming | |
| 9 | Braking resistor overload alarm | Normal | Alarming | |
| 10 | Cumulative run time alarm | Normal | Alarming | [] flicking |
| 11 | Communication option alarm | Normal | Alarming | [] flicking |
| 12 | Serial communication alarm | Normal | Alarming | [] flicking |
| 13 | Power circuit under voltage alarm | Normal | Alarming | [00FF] flicking |
| 14 | Stop after instantaneous power off | Dec., Under stop | Dec., Under stop | [SEOP] flicking |
| 15 | During sleep | Dec., Under stop | Dec., Under stop | [50P] flicking |
What are the definitions for the function parameters C001-C006 setup values for monitoring parameters for the TOSHIBA TOSVERT VF-MB1/S15?
The C001-C006 setup values for monitoring parameters for VF-MB1/S15 are:
| C001-C006 setup value | Function |
|---|---|
| 0: No action | |
| 1: FA06 (Communication command 1) | |
| 2: FA23 (Communication command 2) | |
| 3: FA07 (Frequency command, 0.01Hz) | |
| 5: FAS0 (Terminal output data) | |
| 6: FAS1 (FM analog output) | |
| 8: F601 (Stall prevention level, %) | |
| 13: ACC (Acceleration time 1, 0.1s)*1 | |
| 14: DEC (Deceleration time 1, 0.1s)*1 | |
| 15: UL (Upper limit, 0.01Hz) | |
| 16: (Torque boost value 1, 0.1%) | |
| 17: (Base frequency voltage 1, 0.1V) |
What are the definitions for the function parameters C021-C026 setup values for monitoring parameters for the TOSHIBA TOSVERT VF-MB1/S15?
The C021-C026 setup values for monitoring parameters for VF-MB1/S15 are:
| C021-C026 setup value | Function |
|---|---|
| 0: No action | |
| 1: F801 (Status information 1) | |
| 2: F800 (Output frequency, 0.01Hz) | |
| 3: F803 (Output current, 0.01%) | |
| 4: F805 (Output voltage, 0.01%) | |
| 5: FC91 (Alarm information) | |
| 6: F822 (PID feedback value, 0.01Hz) | |
| 7: F806 (Input terminal information) | |
| 8: F807 (Output terminal information) | |
| 9: FE36 (VIB input value, 0.01%) | |
| 10: FE35 (VIA input value, 0.01%) | |
| 11: FE37 (VIC input value, 0.01%) | |
| 12: F804 (Input voltage (DC detection), 0.01%) | |
| 13: Fd16 (Estimated speed, 0.01Hz) | |
| 14: Fd18 (Torque, 0.01%) | |
| 20: F829 (Input power, 0.01kW) | |
| 21: F830 (Output power, 0.01kW) | |
| 22: FE14 (Cumulative operation time, 1=1hour) | |
| 23: FE40 (FM terminal output monitor, 0.01%) | |
| 25: F820 (Torque current, 0.01%) | |
| 26: F823 (Motor overload factor, 0.01%) | |
| 27: F824 (Inverter overload factor, 0.01%) | |
| 28: F625 (PBR cumulative load factor, 1%) | |
| 29: F826 (Motor load factor, 1%) | |
| 30: F827 (Inverter load factor, 1%) | |
| 31: FE56 (Pulse train input value, pps) | |
| 32: FE70 (Rated current, 0.1A) | |
| 33: FE75 (Integral input power, 0.1kWh × 10^F749)*2 | |
| 34: FE77 (Integral output power, 0.1kWh × 10^F749)*2 | |
| 35: F883 (IGBT temperature, degree C) |
What are the definitions for the function parameters C001-C006 setup values for monitoring parameters for the TOSHIBA TOSVERT VF-AS3?
The C001-C006 setup values for monitoring parameters for VF-AS3 are:
| C001-C006 setup value | Function |
|---|---|
| 0: No action | |
| 1: FA06 (Communication command 1) | |
| 2: FA23 (Communication command 2) | |
| 3: FA07 (Frequency command, 0.01Hz) | |
| 4: FA33 (Torque command 0.01%) | |
| 5: FAS0 (Terminal output data) | |
| 6: FA51 (Analog output(FM) data from comm.) | |
| 7: FA52 (Analog output(AM) data from comm.) | |
| 8: F601 (Stall prevention level, %) | |
| 9:F441 (Power running torque limit 1 level,0.01%) | |
| 10: F443 (Regenerative braking torque limit 1 level, 0.01%) | |
| 11: F450 (Speed loop proportional gain) | |
| 12:F461 (Speed loop stabilization coefficient) | |
| 13: ACC (Acceleration time 1, 0.1s) (*1) | |
| 14: DEC (Deceleration time 1, 0.1s) (*1) | |
| 15: UL (Upper limit, 0.01Hz) | |
| 16: (Torque boost value 1, 0.01%) | |
| 17: (Base frequency voltage 1, 0.1V) |
What are the definitions for the function parameters C021-C026 setup values for monitoring parameters for the TOSHIBA TOSVERT VF-AS3?
The C021-C026 setup values for monitoring parameters for VF-AS3 are:
| C021-C026 setup value | Function |
|---|---|
| 0: No action | |
| 1: F801 (Status information 1) | |
| 2: F800 (Output frequency, 0.01Hz) | |
| 3: F803 (Output current, 0.01%) | |
| 4: F805 (Output voltage, 0.01%) | |
| 5: FC91 (Inverter alarm) | |
| 6: F822 (PID feedback value, 0.01Hz) | |
| 7: F806 (Input terminal status) | |
| 8: F807(Output terminal status) | |
| 9: FE35 (RR input, 0.01%) | |
| 10: FE36 (RX input, 0.01%) | |
| 11: FE37(II input, 0.01%) | |
| 12: F804 (Input voltage (DC detection), 0.01%) | |
| 13: Fd16 (Estimated speed (real-time value), 0.01Hz) | |
| 14: Fd18 (Torque, 0.01%) | |
| 20: F829 (Input power, 0.01kW) | |
| 21: F830 (Output power, 0.01kW) | |
| 22: FE14 (Cumulative operation time, 1hour) | |
| 23: FE40 (FM terminal output monitor, 0.01%) | |
| 24: FE41 (AM terminal output monitor, 0.01%) | |
| 25: F820 (Torque current, 0.01%) | |
| 26:F823 (Motor overload factor, 0.01%) | |
| 27: F824 (Inverter overload factor, 0.01%) | |
| 28: F625 (PBR overload factor, %) | |
| 29: F826 (Motor load factor, %) | |
| 30: F827 (Inverter load factor, %) | |
| 31: FE56 (Pulse train input, pps) | |
| 32: FE70 (Inverter rated current, 0.1A) | |
| 33: FE76 (Input Watt-hour, 0.1kWh × 10^F749) | |
| 34:FE77 (Output Watt-hour, 0.1kWh × 10^F749) | |
| 35: F883 (IGBT temperature, degree C) |
How are the bits for Acc/Dec switching 1 defined in FA06 for the TOSHIBA TOSVERT VF-MB1/S15?
For VF-MB1/S15, the Acc/Dec switching 1 bits in FA06 are defined as follows:
| Bit | Function | 0 | 1 | Note |
|---|---|---|---|---|
| 8 | Acceleration/deceleration pattern selection 1 (AD2 selection) | Acceleration /deceleration pattern 1 (AD1) | Acceleration /deceleration pattern 2 (AD2) | AD1: ACC, DEC AD2: F500, F501 |
How are the bits for Acc/Dec switching 1 defined in FA06 for the TOSHIBA TOSVERT VF-AS3?
For VF-AS3, the Acc/Dec switching 1 bits in FA06 are defined as follows:
| Bit | Function | 0 | 1 | Note |
|---|---|---|---|---|
| 8 | Acc/dec switching 1 (*1) | AD mode 1 | AD mode 2 | Select acceleration/deceleration 1-4 by combination of two bits. AD mode 1: ACC,DEC AD mode 2: F500,F501 AD mode 3: F510,F511 AD mode 4: F5 14,F515 |
How are the bits for OC stall level switching and Torque limit switching 1 defined in FA23 for the TOSHIBA TOSVERT VF-AS3?
For VF-AS3, OC stall level switching and Torque limit switching 1 bits in FA23 are defined as follows:
| Bit | Function | 0 | 1 | Note |
|---|---|---|---|---|
| 12 | OC stall level switching and Torque limit switching 1 | 00: Torque limit 1 / OC stall 1 01: Torque limit 2 / OC stall 2 10: Torque limit 3 / OC stall 1 11: Torque limit 4 / OC stall 2 |
Select torque limit 1 – 4 by combination of bits |
CLICK HERE TO DOWNLOAD TOSHIBA TOSVERT VF-AS3 (04) PDF DOCUMENT