What are the general notices regarding the PV Reverse Combiner Box?

Contents may be periodically updated or revised. SolaX reserves the right to make improvements or changes in the product(s) and the program(s) described in this manual without the prior notice.

The installation and maintenance can only be performed by qualified personnel who:

Are licensed and/or satisfy state and local jurisdiction regulations;

Have good knowledge of this manual and other related documents.

Before installing the device, carefully read, fully understand and strictly follow the detailed instruction of the installation manual and other related regulations. SolaX shall not be liable for any consequences caused by the violation of the installation, and operation regulations specified in this document.

Use insulated tools when installing the device. Individual protective tools must be worn during installation, electrical connection and maintenance.


What are the potential risks associated with the photovoltaic (PV) system?

Exposure to sunlight can result in the generation of high DC voltage by PV modules, which can lead to electric shock causing severe injuries or even death.

Never touch the positive or negative poles of the PV connecting device, and avoid touching both poles simultaneously.

Do not ground the positive or negative poles of the PV modules.

Only qualified personnel can perform the wiring of the PV modules.


What are the requirements for grounding the cable?

The grounding cable must be well connected to ground.

Incorrect connection may cause fatal electric shock!

If not connected correctly, the device may be damaged when struck by lightning!


What are the dangers of electrical shock related to the device?

Only operate the device when it is technically faultless. Otherwise, electric shock or fire may occur.

Do not open the enclosure in any case without authorization from SolaX. Unauthorized opening will void the warranty and cause lethal danger or serious injury due to electric shock.


What is the correct power-on sequence when the inverter is connected in parallel mode with a PV Reverse Combiner Box?

The inverter, which connected in parallel mode with a PV Reverse Combiner Box, should be switched on before sunrise or after sunset.

When power on the system, the correct order is: switch on the PV Reverse Combiner Box, turn the inverter DC switch to ON, then turn the switch of the PV Combiner box to ON.


What precautions should be taken regarding internal terminals?

Touching the internal terminals of the device may result in electric shock or fire!

Do not touch the terminals or conductors connected to the inverter or string.


What are the warnings regarding electrical connections?

The screws of the terminal must be tightened in place, otherwise the terminal would be heated and burned after a prolonged period.

Multi-strand copper core flame-retardant cables must be used, with the wire diameter not less than the recommended value.

The screw of the waterproof terminal must be tightened in place, otherwise it may cause water leakage.


What general cautions should be observed for the device?

Keep children away from the device.

Pay attention to the weight of the device. Personal injuries may be caused if not handled properly.

All the product labels and nameplate on the device shall be maintained clearly visible.


What types of cables and their cross-sections are required?

No. Required Cable Type Conductor Cross-section
5 Input cable Single core wire PG42 (32-38 mm²)
6 Output cable Single core wire PG9 (4-8 mm²)
7 Grounding cable Yellow and green wire PG16 (10-14 mm²)

What materials are additionally required for installation?

No. Required Materials Type Quantity
1 Input terminal* Gland (Max. 240 mm²) 2 pcs
2 Fireproof mud / 1 pc
3 Output terminal Gland (6 mm²) 20 pcs for PVR-10S:
24 pcs for PVR-12S:
36 pcs for PVR-18S:
48 pcs for PVR-24S
4 OT terminal / 1 pc

* For copper input cables, please use copper terminals, for aluminium input cables, please use aluminium-to-copper terminals.


What is included in the packing list for the PV Reverse Combiner Box?

Item Description Quantity Remark
/ PV Reverse Combiner Box 1 pc
A Key 2 pcs For locking the door
B M8x20 screw 4 pcs For mechanical installation
C Nut 4 pcs For mechanical installation
D Washer 4 pcs For mechanical installation
E Document /

What are the recommended conditions for the installation site?

The ambient temperature should be -40°C to +60°C.

The relative humidity shall be between 0-95%RH.

Install the device in a well-ventilated environment for heat dissipation. It is recommended to install an awning over the device if it is installed on a support outdoor.

Do not install the device in areas with flammable, explosive and corrosive materials or near combustibles and antennas.

For outdoor installation, precautions against direct sunlight, rain exposure and snow accumulation are recommended.

Exposure to direct sunlight raises the temperature inside the device. This temperaturerise poses no safety risks, but may impact the device performance.


How do I perform the mechanical installation of the PV Reverse Combiner Box?

1. Dimensions for mounting between the lugs on its both sides (Unit:mm): 860 mm width, 473 mm height.

2. Mark the position of the mounting hole and drill. The drill bit should be Ø10 mm, depth 20 mm, diameter 10 mm.

3. Fix M8x20 screws, lugs, washers and nuts in order and tighten it. Torque for M8 screws: 10.8-13.2 N-m.


What are the safety precautions before electrical connection?

Before electrical connection, make sure all switches and DC breaker are disconnected. Otherwise, the high voltage may cause electric shock, resulting in severe personal injuries or even death.


How do I prepare the PV Reverse Combiner Box for electrical connection?

1. Use keys to open the PV Reverse Combiner Box.

2. Remove the PC Cover. Torque for M5 screws: 0.8 N-m.


How do I connect the input cable to the PV Reverse Combiner Box?

1. Strip the cable (35 mm), sleeve the terminal onto the cable.

2. Crimp the cable to the Input terminal.

3. Dismantle the input cable gland.

4. Dismantle the M12 screw. Torque for M12 screws: 25 N-m.

5. Insert the cable to the input cable gland in order. Pre-assemble the input cable gland and do not tighten it.

6. Insert the cable and input cable gland to the device and tighten the M12 screw. Torque for M12 screws: 25 N-m.

7. Adjust the cable, and tighten the input cable gland. If the seal is not secure, it is recommended to add some fireproof mud inside the input cable gland.

During connection, pay attention to the polarity, and do not reverse it.


How do I connect the output cable to the PV Reverse Combiner Box?

1. Strip the cable (15 mm), sleeve the terminal onto the cable.

2. Crimp the cable to the output terminal.

3. Dismantle the output cable gland. Torque for output cable gland: 1-2 N-m.

4. Insert the cable to the output cable gland in order. Pre-assemble the output cable gland and do not tighten it.

5. Insert the cable to the output cable gland and tighten the cable. Torque for M5 screws: 3 N-m.

6. Adjust the cable, and tighten the output cable gland. The wiring procedure here takes PVR-24S as an example. Torque for output cable gland: 1-2 N-m.

During connection, pay attention to the polarity, and do not reverse it.


How do I make the grounding connection?

The ground wire should have a bare length of B. The stripped insulation for the terminal should be A=B+(2~3 mm). The cable should be 10-14 mm².

Crimp the terminal onto the cable.

Apply heat-shrink tubing (C=A+2 cm) over the crimped terminal and cable.

Dismantle the grounding cable gland. Torque for grounding cable gland: 4-6 N-m.

Insert the cable to the grounding cable gland. Pre-assemble the input cable gland and do not tighten it.

Insert the cable and grounding cable gland to the device. Tighten the terminal (M5, 3 N-m), adjust the cable, and tighten the output cable gland (4-6 N-m).


What preparations are needed after electrical connection before powering on?

1. Install the PC cover. Torque for M5 screws: 0.8 N-m.

2. Use the keys to lock the door. (Power on the system before locking the door for the first-time use).


What are the steps to power on the system?

During operation, please wear protective equipment and make sure that all cables has connected to the inverter.

Step 1: Use keys to open the door.

Step 2: Ensure that all switches are disconnected before proceeding.

Step 3: Check that the positive and negative terminals of the PV Reverse Combiner Box are not reversed.

Step 4: Use a multimeter to measure the voltage on the output side of the PV Reverse Combiner Box, ensure that the voltage of each circuit is basically equal and there is no negative voltage (wrong polarity will cause damage to the box and inverter!).

Step 5: Turn the inverter DC switch to ON, then turn the switch of the PV Combiner box to ON.

Step 6: Lock the door and pull out the key.


What are the steps to power off the system?

Step 1: Use keys to open the door.

Step 2: Disconnect the switch on the input side of the PV Reverse Combiner Box (if any). (Do not disconnect the DC switch of the inverter first, it is possible to cause damage to the PV Reverse Combiner Box and the inverter!)

Step 3: Turn the switch of the PV Combiner box to OFF. Then turn the inverter DC switch to OFF.

Step 4: Lock the door and pull out the key.


What are the guidelines for replacing a fuse?

Once the fuse has blown, it cannot be restored and must be replaced immediately.

The fuse replacement must be of the same grade as the original one!

Do not check or replace the fuse with load! Installation and removal of the fuse must be proceeded with no load to avoid arc damage and personal injury.


How do I replace a fuse?

Step 1: Pull out the fuse cover.

Step 2: Replace the fuse.

Step 3: Close the fuse cover tightly.


What are the DC input & AC output specifications for the PV Reverse Combiner Box?

Model PVR-10S PVR-12S PVR-18S PVR-24S
Max. PV string voltage [V] 1100 1100 1100 1100
Number of DC inputs 1 1 1 1
Number of DC outputs 10 12 18 24
Max. input current [A] 150 180 264 264
Max. input short circuit current [A] 200 240 300 350
Nominal output current per string [A] 15 15 15 15
Input terminal type Gland (Max. 240 mm²)
Output terminal type Gland (6 mm²)

What are the protection specifications for the PV Reverse Combiner Box?

Model PVR-10S PVR-12S PVR-18S PVR-24S
Ingress protection IP65
Environment temperature -40°C ~ +60 °C
Relative humidity [%] 0~95%
Anti-corrosion C5

What are the system data specifications for the PV Reverse Combiner Box?

Model PVR-10S PVR-12S PVR-18S PVR-24S
Dimensions (W x H x D) [mm] 820 x 520 x 170 (Bracket not included)
Weight [kg] <30
Certification IEC 61439-1, IEC 61439-2

CLICK HERE TO DOWNLOAD SOLAX POWER PVR-10S (01) PDF MANUAL