FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF DOCUMENT.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF USER GUIDE.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF USER MANUAL.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF OWNER GUIDE.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF OWNER MANUAL.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF REFERENCE GUIDE.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF REFERENCE MANUAL.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH MITSUBISHI ELECTRIC AE-200E (01) PDF OPERATING INSTRUCTIONS.
CLICK HERE TO DOWNLOAD MITSUBISHI ELECTRIC AE-200E (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What is the AE-200 Update Tool for the MITSUBISHI ELECTRIC AE-200E?
The Update Tool is a dedicated software tool that can update the software of all MITSUBISHI ELECTRIC AE-200E, AE-50, and EW-50 controllers that are connected in the air conditioning control system at once. It can update a maximum of 50 controllers simultaneously.
What are the PC requirements for using the Update Tool with the MITSUBISHI ELECTRIC AE-200E?
| Item | Requirements |
|---|---|
| CPU | 1 GHz or better (at least 2 GHz recommended) |
| Memory | 2 GB or better |
| Screen resolution | 1024 x 768 or better |
| OS | Microsoft® Windows® 11 (64bit) Microsoft® Windows® 10 (64bit) Microsoft® Windows® 8.1 (64bit) Must meet the minimum requirements of the OS |
| Internal LAN port or LAN card | 100 BASE-TX or better |
| Pointing device | Mouse, etc. |
Note:
.NET Framework 4.8 is required. When installing the Update Tool, the page will jump to the download site if .NET Framework 4.8 or later is not installed. The use of the latest version of the OS is recommended. The software has been verified to work on the Pro edition of the listed operating systems.
Are there any system configuration requirements when connecting the MITSUBISHI ELECTRIC AE-200E for an update?
Yes, when connecting the MITSUBISHI ELECTRIC AE-200E via a LAN for the update, you must be sure to use the “LAN1” port on the controller.
What are the system restrictions and important considerations before updating the MITSUBISHI ELECTRIC AE-200E?
Before updating your MITSUBISHI ELECTRIC AE-200E, please consider the following restrictions:
• The AE-200 Update Tool is exclusively for AE-200/AE-50/EW-50 models. Do not use it for other products.
• The software cannot be downgraded to an earlier version.
• A maximum of 50 controllers can be updated at the same time.
• Communication between the MITSUBISHI ELECTRIC AE-200E and the air conditioning units will stop during the update. An error may appear on local remote controllers, but the unit will continue its operation. Note that Mr. Slim indoor units or systems without local remote controllers may stop abnormally.
• Up to 60 minutes of energy management and billing function data will not be recorded during the update.
• For AE-50/EW-50 units, if the Pulse Input (PI) function is used, pulses will not be counted during the update.
Important Considerations:
• Record the operation status of the air conditioning units before the update. After the update, check the status and manually operate units as necessary.
• Scheduled operations, billing, Peak Cut control, and energy management will be disabled during the update. Check these settings beforehand and update at a time that does not affect these functions.
• If the following functions are in use, avoid updating during the prohibited time periods:
| Function in use | Time period in which the update is prohibited |
|---|---|
| Electricity charge apportioning function (with Charge Calculation Tool) | AM 5:00 – 5:10 |
| Electricity charge apportioning function (with TG-2000A) | AM 4:05 – 4:35 |
| Malfunction log backup (with TG-2000A) | AM 0:05 – 0:15 |
| Peak Cut data backup (with TG-2000A) | AM 2:00 – 2:10 |
| Measurement trend data backup (with PI controller, AI controller, or TG-2000A) | AM 1:05 – 1:15 |
How do I install the AE-200 Update Tool for the MITSUBISHI ELECTRIC AE-200E?
Before beginning, ensure that .NET Framework version 4.8 is installed on your PC. You can check this in the Control Panel under “Program and Features”.
1. Double-click the downloaded “AE-200 UpdateTool_V***.msi” file.
2. If a “Security Warning” message appears, click [Run].
3. When the “Setup Wizard” screen appears, click [Next].
4. On the “License Agreement” screen, read the terms, select [I Agree], and click [Next].
5. On the “Select Installation Folder” screen, choose the destination folder. To allow all PC users to access the tool, ensure the [Everyone] checkbox is selected. Click [Next].
6. On the “Confirm Installation” screen, click [Next] to begin the installation.
7. The tool will be installed. Please wait for the process to complete.
8. Once installation is complete, click [Close] to exit the wizard.
How do I set the PC’s IP address to communicate with the MITSUBISHI ELECTRIC AE-200E?
To communicate with the MITSUBISHI ELECTRIC AE-200E, your PC’s IP address must be on the same network. For example, if the controller’s IP address is 192.168.11.1, your PC’s IP address could be 192.168.11.150. Consult your system administrator for the correct addresses if you are on an existing LAN.
Follow these steps to set the IP address:
1. Open the Control Panel on your PC.
2. Click [Network and Sharing Center], then [Change adapter settings].
3. Double-click the [Ethernet] icon. In the “Ethernet Status” window that appears, click [Properties].
4. In the “Ethernet Properties” window, select [Internet Protocol Version 4 (TCP/IPv4)] and click [Properties].
5. In the properties window, check the radio button for [Use the following IP address].
6. Enter the correct IP address for your PC (e.g., 192.168.11.150).
7. Enter the subnet mask (e.g., 255.255.255.0, unless specified otherwise).
8. Enter the gateway address if necessary.
9. Click [OK] or [Close] on all open windows to save the changes.
Important: Always consult the system administrator to decide the IP, subnet mask, and gateway addresses, and make a note of the original settings before changing them.
What version of .NET Framework is required for the MITSUBISHI ELECTRIC AE-200E Update Tool?
If .NET Framework 4.8 is not already installed, you must download and install it. If your system is not connected to the Internet, you will need to download the offline installer beforehand.
What is the general workflow for using the Update Tool with the MITSUBISHI ELECTRIC AE-200E?
The update process follows these general steps:
1. Start the Update Tool to view the Main screen.
2. Input the IP addresses of the MITSUBISHI ELECTRIC AE-200E controllers to be updated.
3. Click “Acquire data” to check the current version and status of the controllers.
4. Select the appropriate update file for the controllers.
5. Click “Update”. An authentication screen will appear.
6. Enter the ID and password for the controllers and click “OK” to begin the update.
7. Monitor the status column to confirm that the update completes successfully.
Can you describe the main screen of the MITSUBISHI ELECTRIC AE-200E Update Tool?
The main screen of the Update Tool is organized into several key areas:
| Function | Description |
|---|---|
| Menu bar | Contains operations to load IP addresses from a TXT file, save entered IP addresses, exit the tool, and check the version information. |
| Update file selection | Area to select the update file for the centralized controller. |
| IP address setting | The area where you enter the IP addresses of the controllers to be updated. |
| Centralized controller system information | Displays the system information (Model name, Version, Serial No.) of a given controller after data acquisition. |
| Centralized controller status | Displays the status regarding the update of a given controller. |
| [Acquire data] button | Click to acquire the system information of the controllers whose IP addresses are entered. |
| [Update] button | Click to start the update process for the controllers whose IP addresses are entered. |
Note: Up to 50 centralized controllers can be updated at the same time.
What operations are available in the menu bar of the MITSUBISHI ELECTRIC AE-200E Update Tool?
The menu bar contains two menus: File and Help.
File Menu:
• Open TXT file: Click [File] > [Open] to load a TXT file containing the destination IP addresses.
• Save TXT file: Click [File] > [Save] to save the IP addresses that are entered in the tool to a file on your PC.
• Exit Update Tool: Click [File] > [Exit] to close the application.
Help Menu:
• Version information: Click [Help] > [About] to display the current version of the Update Tool software.
How do I input the IP addresses of the MITSUBISHI ELECTRIC AE-200E controllers directly into the Update Tool?
To input IP addresses directly, simply click into the “Destination IP address” column for each row and type the IP address of the MITSUBISHI ELECTRIC AE-200E controller you wish to update.
Important:
• Enter the IP address using one-byte characters in the format [XXX.XXX.XXX.XXX], where XXX is an integer between 0 and 255. (Example: 192.168.1.1)
• Do not enter any other characters, including tabs and spaces.
How can I load multiple IP addresses for MITSUBISHI ELECTRIC AE-200E controllers from a TXT file?
You can load up to 50 IP addresses from a standard TXT file.
1. Using a text editor like Notepad, create a file and enter one IP address per line for each MITSUBISHI ELECTRIC AE-200E controller. Save the file.
2. In the Update Tool, click [File] > [Open].
3. A file selection screen will appear. Locate and select the TXT file you created, and click [Open].
4. The IP addresses from the file will be loaded and displayed in the “Destination IP address” column.
Important:
• When creating the TXT file, enter the IP address using one-byte characters in the format [XXX.XXX.XXX.XXX] (Example: 192.168.1.1). Do not include any other characters like tabs or spaces.
• If a line in the TXT file only contains a line feed (is blank), it will appear as a blank line in the tool.
How do I check the current software versions of the MITSUBISHI ELECTRIC AE-200E controllers using the Update Tool?
After entering the IP addresses of the MITSUBISHI ELECTRIC AE-200E controllers:
1. Click the [Acquire data] button.
2. The tool will communicate with each controller. The “Status” column will show “Acquiring data…”.
3. Once successfully completed, the “Status” column will display “Data acquisition succeeded”, and the “Model name”, “Version”, and “Serial No.” columns will be populated with the information for each controller.
Important: Do not click the ‘X’ at the top right corner of the main screen while data is being acquired.
What do the different status messages mean during data acquisition for the MITSUBISHI ELECTRIC AE-200E?
| Display information in the “Status” column | Explanation |
|---|---|
| Acquiring data… | The controller data is being acquired. The message appears in black. |
| Data acquisition succeeded | The controller data was successfully acquired. The model name, version, and serial number will be displayed. The message appears in black. |
| Data acquisition failed | The controller data could not be acquired. The message appears in red. |
| Invalid IP address | The IP address entered is not in the correct format. The message appears in red. |
| IP addresses overlap | The same IP address has been entered more than once. The message appears in red. |
| The equipment is not applicable for update. | Data was acquired from equipment that is not a target for this tool (i.e., not an AE-200/AE-50/EW-50). The message appears in red. |
If you see “Data acquisition failed,” “Invalid IP address,” or “IP addresses overlap,” refer to the troubleshooting section.
How do I select the update file for the MITSUBISHI ELECTRIC AE-200E?
1. In the “Update file selection” section, click the [Browse…] button next to the “AE-200 update file” field.
2. A file selection screen will appear. Navigate to the location of the update file and select it. Click [Open].
3. The full path of the selected file will be displayed in the text box.
Note:
• Select the file named “AE200_FW####_****.dat” for a MITSUBISHI ELECTRIC AE-200E controller. (#### represents the software version).
• Select the file named “AE50_FW####_****.dat” for an AE-50/EW-50 controller. (#### represents the software version).
How do I perform the software update on the MITSUBISHI ELECTRIC AE-200E controllers?
After acquiring data and selecting the update file:
1. Click the [Update] button. The “Authentication information input” screen will appear.
2. For the first controller (No. 1), enter the ID and Password for its initial settings in the corresponding fields.
3. For any subsequent controllers (No. 2 and later), if they use the same ID and password as the first one, check the box next to [Same as No. 1]. Otherwise, enter their unique ID and password.
4. Click [OK]. The authentication screen will close and the update process will begin.
5. The update status for each MITSUBISHI ELECTRIC AE-200E will appear in the “Status” column of the main screen.
What do the different status messages mean during the update process for the MITSUBISHI ELECTRIC AE-200E?
The status messages appear in a specific order during the update process:
| Display information in the “Status” column | Explanation | Display order |
|---|---|---|
| Authentication succeeded | The controller authentication was successful. Appears in black. | 1 |
| Authentication failed | The controller authentication failed. Appears in red. | |
| Communication failed | Communication with the controller failed. Appears in red. | |
| Already updated | The controller software is already up to date. Appears in red. | |
| Updating… | The controller is currently being updated. Appears in black. | 2 |
| Update completed | The update has been successfully completed. Appears in black. | 3 |
| Update failed | The controller update has failed. Appears in red. |
How long does the update for the MITSUBISHI ELECTRIC AE-200E take, and are there any important warnings?
The approximate time required for the update varies with the number of controllers and the software version.
| Number of centralized controllers to be updated | Time required for update [min] | |
|---|---|---|
| Ver. 7.24 or earlier | Ver. 7.31 or later | |
| 4 | 9 | 7 |
| 10 | 15 | 10 |
| 20 | 25 | 15 |
| 40 | 45 | 25 |
| 50 | 55 | 30 |
Important Warnings:
• Do not click the ‘X’ at the top right corner of the screen, disconnect the LAN cable, or turn off power to the MITSUBISHI ELECTRIC AE-200E during the update process.
• The following controllers will not be updated: those with no destination IP address entered, and those with a status of “The equipment is not applicable for update” or “Already updated”.
• If an “Authentication failed,” “Communication failed,” or “Update failed” status appears, refer to the troubleshooting section.
• A 7905 error message (System abnormality – Version error / Different unit model error) may appear on the MITSUBISHI ELECTRIC AE-200E if the software versions of connected controllers temporarily do not match during the update. This error will automatically reset when the software versions match.
How do I save the list of MITSUBISHI ELECTRIC AE-200E controller IP addresses?
1. In the menu bar, click [File] > [Save].
2. A “Save As” screen will appear. Enter any name for the file in the “File name” field and click [Save].
3. A confirmation window will appear stating “The destination IP addresses have been saved.” Click [OK].
What should I do if an error occurs when loading the TXT file for the MITSUBISHI ELECTRIC AE-200E update?
If you see an error message that says “File read failed. Check the data in the file.”, it means the TXT file is not created according to the specified format. You should check that the TXT file contains only valid IP addresses, one per line, with no extra characters, as specified in the instructions for creating an IP address TXT file.
What should I do if I get an error when selecting the update file for the MITSUBISHI ELECTRIC AE-200E?
If you see an error message such as “This file is not an update file for AE-200. Check the file type.”, it means a wrong file has been selected. You need to ensure you are selecting the correct update file for your MITSUBISHI ELECTRIC AE-200E, which should be named in the format “AE200_FW####_****.dat”. Then, re-select the correct file.
What should I do if I encounter “Data acquisition failed,” “Invalid IP address,” or “IP addresses overlap” for my MITSUBISHI ELECTRIC AE-200E?
• Data acquisition failed: This can happen if the IP address of the controller is different from the one entered, or if the LAN connection between the PC and the controller is not established. Check that the IP address is correct and that the LAN connection is proper, then try again.
• Invalid IP address: This means the IP address was not entered in the correct format. Check that the IP address is entered according to the specified format (XXX.XXX.XXX.XXX).
• IP addresses overlap: This means the same IP address has been entered more than once in the list. Check the IP address of the controller in error, and re-enter the correct IP address.
What troubleshooting steps should I take if an error occurs when I click the [Update] button for my MITSUBISHI ELECTRIC AE-200E?
If you encounter an error after clicking [Update], check the following:
• Data acquisition not completed: An error may state “Check that the data acquisition of all centralized controllers has succeeded.” You must successfully acquire data for all controllers before updating. Check the “Status” column and click [Acquire data] again to complete the process for any controllers that failed.
• Update file not selected: An error may state “AE-200 update file is not selected.” You must select the correct update file for the MITSUBISHI ELECTRIC AE-200E by clicking [Browse…].
• Older update file selected: An error may state “The version of the selected update file is older than the version of AE-200.” You cannot downgrade the software. Click [Browse…] and select a file with a newer version than the one currently installed.
• Mismatched update file versions: If updating both AE-200 and AE-50/EW-50 units, an error may state that the versions of the two update files do not match. You must select update files for both controller types that have matching versions.
What does the error “Communication or authentication failed” mean when updating the MITSUBISHI ELECTRIC AE-200E?
This error message appears when updating the centralized controllers and can be caused by two main issues:
1. The LAN connection with the centralized controller is cut off. Check for a proper LAN connection between the PC with the Update Tool and the MITSUBISHI ELECTRIC AE-200E controller that is in error.
2. The ID and password entered are wrong. Re-enter the correct ID and password for the initial settings of the given centralized controller.
What should I do if the update for the MITSUBISHI ELECTRIC AE-200E fails?
If the message “Update failed” appears in the “Status” column, it could be due to a LAN connection being cut off during the process or another communication failure.
To resolve this:
1. Check for a proper LAN connection between the PC running the Update Tool and the MITSUBISHI ELECTRIC AE-200E centralized controller.
2. Click the [Acquire data] button on the main screen to check if the controller’s version has been updated.
3. If it has not been properly updated, attempt the update process again.
What functions were added in Ver. 7.98 for the MITSUBISHI ELECTRIC AE-200E Update Tool?
| Version | Menu item | Added function |
|---|---|---|
| Ver. 7.98 | Windows® 11 compatible | A computer with Windows® 11 is compatible for use. |
| .NET Framework 4.8 compatible | Supports the use of .NET Framework 4.8 |