Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Document. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF User Guide. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF User Manual. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Owner Guide. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Owner Manual. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Reference Guide. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Instruction Guide. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Reference Manual. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Instruction Manual. Free English MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF Operating Instructions.


CLICK HERE TO DOWNLOAD MITSUBISHI ELECTRIC FX3G-1DA-BD (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What safety precautions should I be aware of when using the MITSUBISHI ELECTRIC FX3G-1DA-BD?

The safety precautions for the MITSUBISHI ELECTRIC FX3G-1DA-BD are classified into two categories:

AWARNING: Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

ACAUTION: Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.

Depending on the circumstances, procedures indicated by ACAUTION may also cause severe injury. It is important to follow all precautions for personal safety.


What items are included with the MITSUBISHI ELECTRIC FX3G-1DA-BD?

Product Included items
Analog output expansion board FX3G-1DA-BD

• M3×8 tapping screws for installation: 2 pcs.

• Side cover

• Installation Manual (This manual)


What are the external parts of the MITSUBISHI ELECTRIC FX3G-1DA-BD?

The external parts of the MITSUBISHI ELECTRIC FX3G-1DA-BD are:

[1] Terminal block mounting screws

[2] POW LED: Lit while power is properly supplied from main unit

[3] Mounting holes (2-ø3.2)

[4] Connector cover

[5] Main unit connector

[6] Terminal block to connect analog output

[7] Memory cassette/Display module connector


What precautions should be taken for installation of the MITSUBISHI ELECTRIC FX3G-1DA-BD?

AWARNING

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product.

ACAUTION

• Use the product within the generic environment specifications described in the PLC main unit manual (Hardware Edition).

• Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.

• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.

• Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions.

• Connect expansion board securely to their designated connectors. Loose connections may cause malfunctions.


What are the wiring precautions for the MITSUBISHI ELECTRIC FX3G-1DA-BD?

AWARNING

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product.

ACAUTION

• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.

• Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise:

1) Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main circuit, high-voltage line, or load line. As a guideline, lay the control line at least 100 mm (3.94″) or more away from the main circuit, high-voltage line, or load line.

2) Ground the shield of the analog input/output cable at one point on the signal receiving side. However, do not use common grounding with heavy electrical systems.

• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions:

– The disposal size of the cable end should follow the dimensions described in the manual.

– Tightening torque should follow the specifications in the manual.

– Twist the end of strand wire and make sure that there are no loose wires.

– Do not solder-plate the electric wire ends.

– Do not connect more than the specified number of wires or electric wires of unspecified size.

– Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.

• Make sure to properly wire to the terminal blocks in accordance with the following precautions:

– Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6 mm (0.24″) or less). Make sure that the screwdriver does not touch the partition part of the terminal block.


What are the applicable cable and terminal tightening torque specifications for the MITSUBISHI ELECTRIC FX3G-1DA-BD?

For the terminal block (European type):

1) Wire size

Wiring to the analog device should use 20-22 AWG wire.

2) Applicable cable

Type Wire size
Single-wire 0.3 mm² to 0.5 mm² (AWG22 to 20)
2-wire 2 pieces of 0.3 mm² (AWG22)

3) Termination of cable end

Strip the coating of strand wire and twist the cable core before connecting it, or strip the coating of single wire before connecting it. An alternative connection is to use a ferrule with insulating sleeve.

<Reference>

Manufacturer Model Caulking tool
Phoenix Contact Co., Ltd. AI 0.5-8WH CRIMPFOX 6 (or CRIMPFOX 6T-F)

When using a ferrule with insulation sleeve, choose a wire with proper cable sheath referring to the specified outside dimensions, or otherwise, the wire cannot be inserted easily. The tightening torque must be 0.22 to 0.25 N·m. Do not tighten terminal screws with a torque outside this range.

4) Tool

For tightening the terminal, use a commercially available small screwdriver having a straight form that is not widened toward the end. If the diameter of the screwdriver grip is too small, the tightening torque will not be able to be achieved. Use the following recommended screwdriver or an appropriate replacement (grip diameter: approximately 25 mm (0.98″)).

<Reference>

Manufacturer Model
Phoenix Contact Co., Ltd. SZS 0.4×2.5

How should I wire the analog output for the MITSUBISHI ELECTRIC FX3G-1DA-BD?

For a voltage output, connect to the V+ and VI- terminals. For a current output, also connect to the V+ and VI- terminals. Follow these guidelines:

• Use 2-core shielded twisted pair cable for the analog output lines.

• Separate the analog output lines from other power lines or inductive lines.

• The grounding resistance should be 100 Ω or less.


What are the grounding requirements for the MITSUBISHI ELECTRIC FX3G-1DA-BD?

Grounding should be performed as stated below:

• The grounding resistance should be 100 Ω or less.

• Independent grounding should be performed for best results. When independent grounding is not performed, perform “shared grounding”. Common grounding is not allowed.

• The grounding wire size should be AWG 22-20 (0.3-0.5 mm²).

• The grounding point should be close to the PLC, and all grounding wire should be as short as possible.


What precautions should be taken for startup, maintenance, disposal, and transportation of the MITSUBISHI ELECTRIC FX3G-1DA-BD?

STARTUP AND MAINTENANCE PRECAUTIONS (ACAUTION)

• Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. For repair, contact your local Mitsubishi Electric representative.

• Do not drop the product or exert strong impact to it. Doing so may cause damage.

DISPOSAL PRECAUTIONS (ACAUTION)

• Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device.

TRANSPORTATION AND STORAGE PRECAUTIONS (ACAUTION)

• The product is a precision instrument. During transportation, avoid impacts larger than those specified in the general specifications by using dedicated packaging boxes and shock-absorbing palettes. Failure to do so may cause failures in the product.

• After transportation, verify operation of the product and check for damage of the mounting part, etc.


Which PLCs are compatible with the MITSUBISHI ELECTRIC FX3G-1DA-BD?

Model name Applicability
FX3S Series PLC Ver. 1.00 or later (from first production)
FX3G Series PLC Ver. 1.10 or later

The number of connectable expansion boards varies depending on the main unit as follows:

• FX3S, FX3G-14M, FX3G-24M Main units: 1 unit

• FX3G-40M, FX3G-60M Main units: 2 units

Never stack up two or more expansion boards.


What are the guidelines for using the MITSUBISHI ELECTRIC FX3G-1DA-BD to ensure EMC compliance?

For the best performance and EMC compliance with the MITSUBISHI ELECTRIC FX3G-1DA-BD, follow these points:

• Use shielded cables. If no other EMC protection is provided, you may experience a temporary loss of accuracy between ±10% in very heavy industrial areas.

• Do not lay sensitive analog cable in the same trunking or cable conduit as high voltage cabling. Where possible, run analog cables separately.

• Use good cable shielding. When terminating the shield at Earth, ensure that no earth loops are accidentally created.

• When reading analog values, EMC accuracy can be improved by averaging the readings. This can be achieved either through functions on the analog expansion boards or through a user’s program in the PLC main unit.


What are the performance specifications of the MITSUBISHI ELECTRIC FX3G-1DA-BD?

Item Specifications
Voltage output Current output
Analog output range 0 to 10 V DC (External load resistance: 2 kΩ to 1 MΩ) 4 to 20 mA DC (External load resistance: 500 Ω or less)
Digital input Resolution 12 bits, binary
2.5 mV (10 V/4000)
11 bits, binary
8 μA (16 mA/2000)
Total accuracy • ±0.5 % (±50 mV) for full scale of 10 V (when ambient temperature is 25 °C ±5 °C)
• ±1.0 % (±100 mV) for full scale of 10 V (when ambient temperature is 0 °C to 55 °C)
• Shipment adjustment is carried out by external load resistance 2 kΩ
• If external load resistance becomes larger than 2 kΩ, the output voltage will increase slightly.
• When the load is 1 MΩ, the output voltage becomes about 2 % higher than the correct value.
• ±0.5 % (±80 μA) for full scale of 16 mA (when ambient temperature is 25 °C ±5 °C)
• ±1.0 % (±160 μA) for full scale of 16 mA (when ambient temperature is 0 °C to 55 °C)
D/A conversion time 60 μs
(The data will be updated at every scan time of the PLC.)
Output characteristics 0 to 4000 are adjusted to 0 to 10 V when the external load resistance is 2 kΩ. 0 to 2000 are adjusted to 4 to 20 mA when the external load resistance is 250 Ω.
Caution: An area of dead band is located in the region of 0 V. Therefore the output analog value may not represent the digital value accurately.
Insulation method No insulation between the PLC.
Occupied points 0 point (This number is not related to the maximum number of input/output points of the PLC.)

What are the special devices for the MITSUBISHI ELECTRIC FX3G-1DA-BD?

Device number Description R: Read / W: Write
FX3G FX3S
Board A Board B
Special auxiliary relay M8260 M8260 M8270 Switches the output mode
OFF: Voltage output ON: Current output
R/W
M8264 M8264 M8274 Output Holding Function Cancellation Setting
OFF: Holds the analog data output just before stop of the PLC.
ON: Output the offset data at stop of the PLC.
R/W
D8260 D8260 D8270 Output setting data R/W
Special data register D8268 D8268 D8278 Error status
b0: Output data setting error
b1: Unused
b2: Unused
b3: Unused
b4: EEPROM error
b15 to b5: Unused
R/W
D8269 D8269 D8279 Model code = 4 R

Are there any special considerations for the use of the MITSUBISHI ELECTRIC FX3G-1DA-BD?

Yes. This product has been manufactured as a general-purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.

• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi Electric.

• This product has been manufactured under strict quality control. However when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.