FREE ENGLISH MIDEA M1-S4K (01) PDF USER GUIDE
FREE ENGLISH MIDEA M1-S4K (01) PDF USER MANUAL
FREE ENGLISH MIDEA M1-S4K (01) PDF OWNER GUIDE
FREE ENGLISH MIDEA M1-S4K (01) PDF OWNER MANUAL
FREE ENGLISH MIDEA M1-S4K (01) PDF REFERENCE GUIDE
FREE ENGLISH MIDEA M1-S4K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH MIDEA M1-S4K (01) PDF REFERENCE MANUAL
FREE ENGLISH MIDEA M1-S4K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH MIDEA M1-S4K (01) PDF OPERATING INSTRUCTIONS
CLICK HERE TO DOWNLOAD MIDEA M1-S4K (01) PDF MANUAL
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What do the safety symbols in the manual mean?
The manual uses symbols to ensure the safety of persons and property. The meanings are as follows:
DANGER: Non-observance will result in death or serious injury. Follow the warnings to prevent death or serious injury.
WARNING: Non-observance will result in death or serious injury. Follow the warnings to prevent serious injury.
CAUTION: Non-observance may result in minor injury. Follow the warnings to prevent injury.
ATTENTION: Non-observance may result in property damage. Follow the warnings to prevent damage to or destruction of the product.
NOTE: Provides tips essential to the optimal operation of the product.
The following symbols may also be found on the inverter:
| Symbol | Description |
|---|---|
| 5min | Residual voltage is present in the inverter. Before opening the inverter, you should wait five minutes to ensure that the capacitor has been fully discharged. |
| Lightning bolt | Caution! Danger through electric shock. |
| SSS | Caution! Hot surface. |
| Exclamation mark in triangle | Disconnect the inverter from all external power sources before maintenance. |
| CE | The product is compliant with EU guidelines. |
| Crossed-out wheelie bin | Do not dispose of the inverter together with household waste. |
| Open book with ‘i’ | Please read the manual before installing the inverter. |
| Grounding symbol | Grounding point. |
| Do not disconnect under load! | Do not remove the DC input connector or AC output connector when the inverter is running. |
What are the basic safety instructions for this inverter?
Qualified Personnel:
This inverter may only be installed by a qualified electrician who:
• has received training on occupational safety, as well as the installation and commissioning of electrical systems.
• is familiar with the local laws, standards and regulations of the grid operator.
Installation Requirements:
• Mount the inverter to a suitable object with sufficient load-bearing capacity (e.g., walls, PV frames) and ensure the inverter is upright.
• Ensure sufficient space for an emergency exit and sufficient ventilation for cooling.
Electrical Connection:
• DANGER: Before establishing the electrical connection, cover the PV modules using opaque material or disconnect the PV generator. Solar radiation will cause dangerous voltage.
• All installations and electrical connections may only be carried out by trained electricians.
• Obtain authorization from the local power grid operator before connecting the inverter to the public power grid.
Operation:
• DANGER: Before carrying out any repair work, first switch off the AC circuit breaker between the inverter and power grid, and then the DC switch.
• After switching off the AC circuit breaker and the DC switch, wait a minimum of 5 minutes before starting any maintenance or repair work.
• CAUTION: While the inverter is operating, several internal components will become very hot. Wear protective gloves and keep children away.
Repair and Maintenance:
• Unauthorized repairs are not permitted. If repairs are required, contact a local authorized service center.
• The internal components of the inverter must NOT be opened without relevant authorization.
What are the main parts of the inverter?
| NO. | Name | Description |
|---|---|---|
| 1 | Hanger Plate | To hang the inverter on the wall-mounting bracket. |
| 2 | Led Indicator Label | To explain the current working state of the inverter. |
| 3 | DC Switch | To safely disconnect the DC circuit whenever necessary. |
| 4 | Indicator | To indicate the current working state of the inverter. |
| 5 | Nameplate | To identify the product, including device model, S/N, important specifications, etc. |
| 6 | Grounding terminal | To connect system to earth. |
| 7 | Electrical connection area | PV terminals, battery terminal, AC terminal, additional grounding terminal and communication terminals. |
What do the LED indicators on the inverter mean?
| INDICATOR | COLOR | STATUS | EXPLANATION |
|---|---|---|---|
| DC | Green | Steady on | PV power available |
| Yellow | Steady on | PV power not available/ too low | |
| Red | Steady on | Fault | |
| – | Off | System is power-off | |
| AC | Green | Steady on | Inverter is operating |
| Green | Blinking at long intervals (on for 1s and then off for 1s) | Inverter in standby in grid-tied mode | |
| Yellow | Steady on | Inverter is operating in off-grid mode | |
| Yellow | Blinking at long intervals (on for 1s and then off for 1s) | Inverter in standby in off-grid mode | |
| Red | Steady on | Fault | |
| – | Off | System is power-off | |
| COM | Green | Blinking at long intervals (on for 0.2s and then off for 0.2s) | Wireless waiting for connection |
| Green | Blinking at long intervals (on for 1s and then off for 1s) | Establishing wireless connection | |
| Green | Steady on | Wireless connected | |
| Yellow | Steady on | Bluetooth connected | |
| – | Off | No wireless/bluetooth connected |
How does the hybrid inverter work in different modes?
The Hybrid Inverter can work in standby, operating, or shutdown mode.
| Working mode | Description |
|---|---|
| Standby | The Hybrid Inverter enters Standby mode when the external environment does not meet the operating requirements. In Standby mode:
• The Hybrid Inverter continuously performs status check and enters the Operating mode once the operating requirements are met. • The Hybrid Inverter enters Shutdown mode after detecting a shutdown command or a fault after startup. |
| Operating | In Operating mode:
• The Hybrid Inverter converts DC power from PV strings into AC power and feeds the power to the power grid. • The Hybrid Inverter tracks the maximum power point to maximize the PV string output. • If Hybrid Inverter detects a fault or a shutdown command, it enters the Shutdown mode. • The Hybrid Inverter enters Standby mode after detecting that the PV string output power is not suitable for connecting to the power grid for generating power. |
| Shutdown |
• In Standby or Operating mode, the Hybrid Inverter enters Shutdown mode after detecting a fault or shutdown command. • In Shutdown mode, the Hybrid Inverter enters Standby mode after detecting a startup command or that the fault is rectified. |
What are the different energy storage system (PV ESS) working modes?
Mode1: Maximize Self-consumption
This mode is suitable for areas with high electricity tariff. When the PV power is sufficient, priority is given to the local load, and the excess electricity goes to energy storage, and if there is still energy left, it is sold to the grid. When the PV power is insufficient/there is no PV power, the battery is discharged for the local load, and when the battery discharge power and photovoltaic power can not meet the load demand, the insufficient power will be purchased from the grid.
Mode2: Maximize Feed-in
This mode is suitable for areas with high feed-in tariff. When the PV power is greater than the inverter capacity, the excess electricity will be stored by energy storage. When PV power is less than the inverter capacity, the excess electricity will be sold to the grid.
Mode3: Backup power
This mode is suitable for areas where grid outages occur frequently or to prevent grid outages. Reserved Backup SOC setting value can be adjusted, when battery SOC is less than reserved SOC value, battery can only be charged, until SOC reaches reserved value, the battery will be stopped charging; when SOC is larger than SOC setting value, battery will behave as Self-use mode.
Mode4: Charge and discharge schedule
This mode is suitable for areas with peaks and valleys in electricity prices Battery charging period and discharging period can be set, during charging period, battery can only be charged, while in discharging period, battery can only be discharged, the rest of the period, battery will behave as Self-use mode.
Mode5: Peak shaving
This function is to avoid exceeding peak kW limit from grid, by dynamically overriding the max kW limit on the battery. Users can set the peak kW value.
What are the guidelines for the back-up function?
1. For hybrid inverters, the electrical installation typically includes connection of the inverter to both PV modules and batteries. If there is no available power from batteries or PV modules in backup mode, the backup power supply will be automatically terminated.
2. Normally, the Back-Up switching time is less than 3 s. However, some external factors may cause the system to fail on Back-Up mode. Therefore, the users must be aware of conditions and follow the instructions as below:
• Do not connect loads that are dependent on a stable energy supply for a reliable operation.
• Do not connect the loads whose total capacity is greater than the maximum Back-Up capacity.
• Do not connect the loads that may cause very high start-up current surges, such as nonfrequency conversion air conditioning, vacuum cleaner or half-wave loads such as hair dryer, heat gun, hammer drill.
• Due to the condition of the battery itself, battery current might be limited by some factors, including but not limited to the temperature and weather.
• BACK-UP is not recommended if the PV system is not configured with batteries.
• When single overload protection occurs, the inverter can restart automatically; however, the restarting time will be extended if it happens several times.
• When the grid is disconnected, the off-grid function of the inverter will be closed automatically if the load capacity exceeds the inverter’s rated power; to enable it, turn off the large loads and ensure the load power is less than the rated power of the inverter.
Declaration for Back-Up Overload Protection: The inverter will restart in case of overload protection. The time required for restarting will increase (5 min at most) if overload protection repeats. Try to reduce Back-Up load power within maximum limitation or remove the loads which may cause very high start-up current surges.
What are the recommended backup loads for the inverter in an off-grid scenario?
| Type | Load Power |
|---|---|
| Dust collector | 1.3kW |
| Water heater/Kettle /Iron /Oven /Toaster /Geothermal blanket / Rice cooker | 3 kW |
| Microwave oven | 1.5kW |
| Refrigerator | 1kW |
| TV / Computer | 1Kw |
| Bath heater | 2.5kW |
| Fluorescent / LED lights | 1.3kW |
| Electric fan / Ceiling fan | 2kW |
| Conditioner(frequency conversionmodulation) | 1.5P |
The data of the compatibility for backup of Hybrid Inverter are based on the test with batteries (-20 ~ 55 °C, 5-100% SOC). For the actual application, please refer to the maximum output capacity of the battery used.
How does the battery management system work?
The maximum allowable charge/discharge current is limited by temperature, the maximum power of the inverter, and the maximum recommended charge/discharge current from the battery manufacturer. The inverter cannot respond to discharge/charge commands when operating off-grid.
| Range | Battery management behavior |
|---|---|
| A | In this range, the battery is no longer discharged, even in battery-backup operation. SoCL can be set from 0 to 15% in APP. |
| B | When operating off grid, the system reports the low SoC state. |
| C | When starting up in off-grid condition, the system does not output AC power, so as to charge the battery by all PV power. |
| D | When operating grid-connected, the system charges / discharges the battery for PV power economy. SoCback can be set from 20 to 90% in APP. |
| E | When operating grid-connected, the system charges / discharges the battery for PV power economy. |
| F | When operating off-grid, the system charges / discharges the battery to support the system and obtain PV power economy. |
| G | The battery can be discharged to support the system or for PV power economy, while it cannot be charged. The inverter cannot respond to charge command in this range. SoCH can be set from 90 to 100% in APP. |
How do I unpack and inspect the inverter?
The product is thoroughly tested and strictly inspected before delivery. Nonetheless, damage may still occur during shipping. For this reason, please conduct a thorough inspection after receiving the product.
• Check the packing case for any visible damage.
• Check the scope of delivery for completeness according to the packing list.
• Check the inner contents for damage after unpacking.
What are the storage requirements for the inverter?
The following requirements should be met if the M1 series inverter is not put into use directly:
• Do not unpack the M1 series inverter.
• Keep the storage temperature at -40°C to +70°C and the humidity at 5%- 95% RH.
• The M1 series inverter should be stored in a clean and dry place and be protected from dust and water vapor corrosion.
• A maximum of 6 units can be stacked. To avoid personal injury or device damage, stack M1 series inverter with caution to prevent them from falling over.
• Periodic inspections are required during the storage. Replace the packing materials if necessary.
• If the M1 series inverter has been long-term stored, inspections and tests should be conducted by qualified personnel before it is put into use.
What tools are needed for installation?
| No. | Tool | Model | Function |
|---|---|---|---|
| 01 | Hammer drill | Recommended drill diameter: 8mm | Used to drill holes in the wall |
| 02 | Screwdriver | Wiring | |
| 03 | Phillips screwdriver | Used to remove and install the screws of the AC terminal | |
| 04 | Removal tool | Used to remove the PV battery terminal | |
| 05 | Wire stripper | Used to strip the wire | |
| 06 | 6mm Allen key | Used to turn the screw to connect the rear panel to the inverter | |
| 07 | Crimping tool | Used to crimp power cables | |
| 08 | Multimeter | Used to check the Grounding | |
| 09 | Marker | Used for marking | |
| 10 | Measuring tape | Used to measure distances | |
| 11 | Spirit level | Used to align the wall bracket | |
| 12 | ESD gloves | For the installer | |
| 13 | Safety goggles | For the installer | |
| 14 | Anti-dust respiratory mask | For the installer |
What are the environmental and mounting requirements for installation?
Basic Requirements:
• The Hybrid Inverter is protected to IP65 and can be installed indoors or outdoors.
• Do not install where personnel can easily come into contact with its enclosure and heat sinks, as these parts get extremely hot.
• Do not install in areas with flammable or explosive materials.
• Do not install within children’s reach.
• Do not install outdoors in salt areas (within 500 meters from the coast) as it may corrode and cause fire.
• Must be installed in a well-ventilated environment. A sheltered place or an awning is recommended.
Mounting Requirements:
• The mounting structure must be fireproof. Do not install on flammable building materials.
• The installation surface must be solid enough to bear the weight of the inverter.
• In residential areas, do not install on drywalls or walls with weak sound insulation as the noise may be noticeable.
Angle Requirements:
Install the inverter vertically. Never install it horizontally, tilted forward/backward, side-tilted, or upside down. A tilt of less than 15 degrees is acceptable.
Space Requirements:
Reserve enough space around the inverter for installation and heat dissipation:
• Above: ≥ 300mm
• Below: ≥ 500mm
• Sides: ≥ 200mm
How do I install the inverter on the wall?
ATTENTION: Mechanical damage
• In order to prevent injuries and damage to the device, ensure that the inverter is kept balanced while it is being moved – it is very heavy.
• Do not place the inverter on its connections, as these are not designed to bear its weight. Place the inverter horizontally on the ground.
• When you place the inverter on the ground, place foamed material or paper underneath it in order to protect its housing.
Step 1. Placing the wall-mounting bracket to a proper position on the wall. Mark the positions by marker and drill the holes. (Observe the level on the bracket and adjust until the bubble is in the middle position). Drill holes with a diameter of 8mm and depth of 45-50mm.
Step 2. Placing and fixing the expansion Bolts in the holes, and Installing the mounting bracket. Tighten the bolts to 5±0.2Nm.
Step 3. Lift the inverter and slide it down along the wall mounting bracket to make sure they match perfectly. Use two screw sets (M4*10) to lock both left and right sides. Tighten the screws to 1.2±0.2Nm.
What are the electrical terminal descriptions?
| No. | Name | Description | DVC |
|---|---|---|---|
| 1 | PV input terminal (PV1+/PV1-) | MC4 terminals for PV 1 input. | DVCC |
| 2 | PV input terminal (PV2+/PV2-) | MC4 terminals for PV 2 input. | DVCC |
| 3 | BAT input terminal (BAT+/BAT-) | Connectors for the battery power cables. | DVCC |
| 4 | Communications port(BMS) | Communication connection for Battery BMS. | DVCA |
| 5 | Communications port(RJ45) | Communication port Reserved. | DVCA |
| 6 | Wireless button | Used to enable WiFi distribution network mode or OTA. | / |
| 7 | Communications port(COM) | Communication connection for smart energy meter, DI/DO RSD, etc. | DVCA |
| 8 | AC-Backup output port | AC terminal for Backup loads. | DVCC |
| 9 | AC-Grid output port | AC terminal to connect to the grid. | DVCC |
| 10 | Ventilation valve | / | / |
| 11 | Wireless Communications | Communication accessory port to be connected to WiNet-S communication module. | DVCA |
What are the required cable specifications?
| NO. | Cable | Type | Cable Diameter | Cross-section |
|---|---|---|---|---|
| 1 | PV cable | Complying with 600V and 16A standard | 6-9mm | 4-6 mm² |
| 2 | AC-Backup cable | Outdoor 3-core copper wire cable | 10-21mm | 4-6 mm² |
| 3 | AC-Grid cable | Outdoor 3-core copper wire cable | 12-25.8mm | 6-16 mm² |
| 4 | BAT Power cable | Complying with 600V and 35A standard | 5.5-8mm | 6 mm² |
| 5 | Communication cable | CAT 5E outdoor shielded network cable | 4.8-6mm | 0.08-0.2 mm² |
| 6 | Grounding cable | Single-core copper wire cable | The same as PE wire in AC cable | |
ATTENTIONS:
• If local standard have other requirements for cables, set the cable specification according to the local standard.
• The factors that affect cable selection include rated current, cable type, routing mode, ambient temperature, and maximum expected line loss.
• The cabling distance between the battery and the inverter should be less than 10m, and within 5m is recommended.
How do I connect the ground cable?
Connect the inverter to the equipotential bonding bar by using the protective earth cable (PE) for grounding.
ATTENTION: Pole Grounding not permissible!
As the inverter is transformerless, the plus and minus poles of the PV generator must NOT be earthed. Otherwise, the inverter will malfunction. In the PV system, not all live metal parts (e.g. PV module frames, PV frame, generator connection box housing, inverter housing) require Grounding.
Steps:
1. Strip 6 mm of insulation from the 4 mm² ground cable. Strip 8-10 mm from the other end to expose the wire for the terminal.
2. Place heat-shrink tubing over the cable and crimp the ground terminal onto the exposed wire.
3. Use a crimping tool to secure the terminal.
4. Attach the ground terminal to the grounding point on the inverter using an M4 screw, and tighten to 1.2±0.2Nm.
How do I perform the AC output connection?
The AC power cables connect the inverter to critical loads (via the AC-BACKUP port) and the AC power distributor or grid. The blue connector is for grid, and the black connector is for backup. The installation process is the same for both.
Connector Installation Steps:
1. Strip 30-50 mm of the outer insulation from the AC cable.
2. Insert the wires into the appropriate terminals on the connector plug. Tighten the screws to 1.2±0.2Nm.
| Connection | Cable |
|---|---|
| L | Phase 1 (brown) |
| N | Neutral conductor (blue) |
| PE | Grounding cable (yellow-green) |
3. Assemble the connector housing and screw the cable gland tight.
4. Connect the AC connector to the corresponding AC port on the inverter (AC GRID or AC BACKUP) by turning it clockwise until it clicks into place.
NOTE:
• Remove the AC connector by turning it anticlockwise.
• When you use the meter connection function, make sure that the AC terminal cable corresponds to the meter cable one by one (L, N, and PE cables).
How do I perform the DC cable connection?
NOTE: The connection steps for the battery and PV are the same, but the terminal specifications are different. The battery terminal is blue, and the PV terminal is black.
Installing the PV Connectors (on the cable):
1. Strip 7 mm of insulation from the red (+) and black (-) 4 mm² cables.
2. Crimp the metal contacts onto the stripped ends of the wires using a crimping tool.
3. Insert the crimped contacts into the corresponding positive (red) and negative (black) connector housings until they click.
4. Tighten the end caps of the connectors using an MC4 wrench.
Installing PV Connector to Inverter:
Step 1. Rotate the DC switch on the inverter to the “OFF” position.
Step 2. Check the cable connection of the PV string for correct polarity and ensure the open-circuit voltage does not exceed the inverter input limit of 600V using a multimeter.
Step 3. Connect the PV connectors to the corresponding PV1 or PV2 terminals on the inverter until there is an audible click.
Installing Battery Connector:
Follow the same process as the PV connector, but use the blue battery connectors and connect them to the BAT+ and BAT- terminals on the inverter until they click.
NOTE: Insert the protective caps into any unused DC connections. To remove connectors, ensure the DC switch is OFF and use a removal key.
How do I connect the BMS RJ45 cable?
The Enable cable and RJ45 cable are used for communication between the inverter and a Li-ion battery.
Step 1 (optional): If not using a pre-made cable, thread the communication cable (4.8-6mm diameter) through the waterproof component. Strip the insulation layer, lead out the signal cables, insert them into the RJ45 plug in the correct order, and crimp it with a crimper. Tighten the waterproof cover before installing the connector.
*Skip this step if a standard network cable with an RJ45 plug is prepared.
Step 2: Find the BMS terminal under the inverter. Insert the RJ45 plug into the BMS terminal, confirming it is inserted correctly. Then, tighten the waterproof screw cap.
How do I connect the Smart Meter?
The Smart Meter with a Current Transformer (CT) is used to measure the power flow at the point of grid interconnection. The CT is usually installed on the L wire between the house loads and the power grid.
Meter Terminal Definitions:
| NO. | Definition | Function |
|---|---|---|
| 1 | L-S1 | To detect the CT current and direction |
| 2 | L-S2 | |
| 3 | N | Power supplied from grid |
| 4 | L | |
| 5-7 | / | |
| 8 | GND | Ground connection |
| 9 | B- | Communicate with hybrid inverter |
| 10 | A+ |
Communication Terminal Definition (Inverter to Meter):
| Inverter Multi-com P1 | Function | Meter Pin | Communication Cable |
|---|---|---|---|
| RJ45 Pin 1 | RS485+ (A2) | Pin 10 | Red line |
| RJ45 Pin 2 | RS485- (B2) | Pin 9 | Black line |
How do I connect the Wireless Module?
Procedure:
1. Remove the protective cap from the USB interface on the inverter.
2. Install the Wireless stick.
3. Tighten the connecting nut.
What is the pinout for the communication ports?
Multi-COM Port Definition:
| PIN | Definition | Function |
|---|---|---|
| P1 RJ45 | RS485+(A2)/RS485-(B2) | Communicate with smart meters |
| P2 RJ45 | RS485+(A2)/RS485-(B2) | Communicate with heat pump |
| 1 | DO1+ | Dry contacts of load control |
| 2 | DO1- | |
| 3 | DO2 | Dry contacts of load control |
| 4 | DO3 | |
| 5 | DO_COM | |
| 6-9 | DRM1/5 to DRM4/8 | Demand response modes |
| 10 | COM | 12V power supply |
| 11 | COM_LOAD/0 | Demand response modes |
| 12 | ES | For WSD(wired shut down)/NS protection |
| 13 | Grid on | For grid operator |
| 14 | COM | 12V power supply |
| 15-18 | RS485B1/A1 | Communicate with inverter |
| 19-20 | RS485B3/A3 | Communicate with upper computer |
| 21-22 | / | Reserved |
RJ45 Terminal Definition (Color Code):
| No. | Color | P1 RJ45(Smart meters) | P2 RJ45(Heat pump) |
|---|---|---|---|
| 1 | White with orange stripes | RS485+(A2) | RS485+(A2) |
| 2 | Orange | RS485-(B2) | RS485-(B2) |
| 3 | White with green stripes | NC | NC |
| 4 | Blue | NC | NC |
| 5 | White with blue stripes | NC | NC |
| 6 | Green | NC | NC |
| 7 | White with brown stripes | NC | NC |
| 8 | Brown | NC | NC |
What checks should I perform before powering on the system?
Ensure that the DC and AC voltages are within the permissible range of the inverter. Perform the following checks:
| No. | Item | Acceptance Criterion |
|---|---|---|
| 1 | Inverter installation | The Inverter is installed correctly and securely. |
| 2 | Battery installation (optional) | The Energy Storage Unit is installed correctly and securely. |
| 3 | Wireless module | The Wireless module is installed correctly and securely. |
| 4 | Cable routing | The cables are routed properly as required by the customer. |
| 5 | Cable ties | Cable ties are secured evenly and no burr exists. |
| 6 | Reliable grounding | The PE cable is connected correctly and securely. |
| 7 | Switch | DC switches and all the switches connecting to the Inverter are OFF. |
| 8 | Cable connection | The AC output power cable, DC input power cables, battery cable, and signal cable are connected correctly and securely |
| 9 | Unused terminals and ports | Unused terminals and ports are locked by watertight caps. |
| 10 | Installation environment | The installation space is proper, and the installation environment is clean and tidy. |
What is the system power-on procedure?
1. If a battery is connected, turn on the battery switch.
2. Turn on the AC switch between the inverter and the power grid.
3. Turn on the DC switch (if any) between the PV string and the inverter.
4. Turn on the DC switch at the bottom of the inverter.
5. Wait for about 1 minute and observe the LED indicators on the inverter to check its running status.
How do I power-off the system for maintenance?
If the inverter needs to be shut down for electrical inspection, please follow the following steps:
1. Turn off the AC switch between the inverter and the power grid.
2. Turn off the DC switch at the bottom of the inverter.
3. If there is a DC switch between the inverter and PV string, turn off the DC switch.
4. Turn off the DC switch at the battery (Optional).
5. Wait for 5 minutes before checking the inverter.
How do I perform routine maintenance?
Inverters do not generally require daily or routine maintenance. Before carrying out cleaning, ensure that the DC switch and AC circuit breaker between the inverter and power grid have been switched off. Wait at least 5 minutes before carrying out cleaning.
Cleaning the inverter: Clean the inverter using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, cleaning agents etc.
Cleaning the heat sink: To help guarantee correct long-term operation, make sure there is sufficient space for ventilation around the heat sink. Check the heat sink for blockages (dust, snow etc.) and remove them if present. Please clean the heat sink using an air blower and a dry, soft cloth or a soft bristle brush. Do not clean the heat sink with water, corrosive chemicals, cleaning agents etc.
How do I troubleshoot problems with the inverter?
To carry out troubleshooting, proceed as follows:
• Check the warnings, error messages or error codes displayed on the screen of the app.
If no error information is displayed on the screen, check whether the following requirements have been fulfilled:
• Has the inverter been set up in a clean, dry, well-ventilated area?
• Is the DC switch set to ON?
• Are the cables sufficiently dimensioned and short enough?
• Are the input connections, output connections and the wiring all in good condition?
• Are the configuration settings for the relevant installation correct?
• Are the the communication cables correctly connected and undamaged?
Error List:
| Alarm ID | Alarm Name | Possible Cause | Trouble shooting |
|---|---|---|---|
| 1001 | String reverse connection | The PV string polarity is reversed. | Check whether the PV string is reversely connected to the inverter. If so, wait until the PV string current decreases to below 0.5 A. Then, turn off the DC switch and correct the PV string polarity. |
| 1002 | Abnormal residual current | The input-to-ground insulation impedance has decreased during the inverter operation. | 1. If the alarm occurs accidentally, the external power cable may be abnormal temporarily. The inverter automatically recovers after the fault is rectified. 2. If the alarm persists or lasts a long time, check whether the impedance between the PV string and ground is too low. |
| 1003 | Low insulation resistance | 1. A short circuit exists between the PV array and the ground. 2. The PV array is in a moist environment and the circuit is not well. | 1. Check the impedance between the PV array output and the ground. If a short circuit occurs or the insulation is insufficient, rectify the fault. 2. Check whether the PE cable of the inverter is correctly connected. 3. If you have confirmed that the impedance is lower than the specified protection threshold in a cloudy or rainy environment, log in to the APP and set the Insulation resistance protection threshold. |
| 1004 | Cabinet over temperature | 1.The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds the upper threshold. 3. The inverter is not operating properly. | 1.Check the ventilation and ambient temperature at the inverter installation position. 2. If the ventilation is poor or the ambient temperature exceeds the upper threshold, improve the ventilation and heat dissipation. |
| 1005 | Grid loss | 1. Power grid outage occurs. 2.The AC circuit is disconnected or the AC switch is off. | 1. The alarm is cleared automatically after the power grid recovers. 2. Check whether the AC circuit is disconnected or the AC switch is off. |
| 1006 | Power Module Communication failure | The battery communication is abnormal | Check that the communications cable is correctly installed, and that the communication parameters are the same as the inverter RS485 configurations. |
| 1007 | BMS Communication failure | The battery communication is abnormal | |
| 1008 | Meter Communication failure | The meter communication is abnormal | |
| 1009 | Equipment fault | An unrecoverable fault occurs on a circuit inside the inverter. | Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the alarm persists, replace the monitoring board. |
| 1010 | Grid overvoltage | The grid voltage exceeds the upper threshold or the high voltage duration has lasted for more than the value specified by high voltage ride-through (HVRT). | 1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal. 2. If the alarm persists, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. If yes, modify the grid over/undervoltage protection threshold through the APP with the consent of the local power operator. 3. Check whether the peak voltage of the power grid is too high/low. |
| 1011 | Grid undervoltage | The grid voltage is below the lower threshold or the low-voltage duration has lasted for more than the value specified by low voltage ride-through (LVRT). | |
| 1012 | Grid over frequency | Power grid exception: The actual power grid frequency is higher than the requirements for the local power grid code. | 1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers. 2. If the alarm persists, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator. If yes, modify the grid frequency protection threshold. |
| 1013 | Grid under frequency | Power grid exception: The actual power grid frequency is lower than the requirements for the local power grid code. | |
| 1014 | AC-grid output overcurrent | The power grid voltage drops dramatically or the power grid is short circuited. As a result, the inverter transient output current exceeds the upper threshold, and protection is triggered. | 1. The inverter monitors its external operating conditions in real time and automatically recovers after the fault is rectified. 2. If the alarm persists and affects the energy yield of the power plant, check whether the output is short circuited. |
| 1015 | AC-backup output overcurrent | The backup load power exceeds the upper threshold. | 1.Try to reduce the load power. |
| 2001 | Power module over temperature | 1. The installation position of the battery power control module is not well ventilated. 2. The ambient temperature is excessively high. 3. The battery power control module is abnormal. | 1. Check the ventilation and whether the ambient temperature of the power control module exceeds the upper threshold. 2. If the ventilation is poor or the ambient temperature is excessively high, improve the ventilation and heat dissipation. |
| 2002 | Low battery DC input bus voltage | 1. The DC bus voltage of the battery is low. 2. The battery DC switch is OFF. 3. The battery cables are not correctly connected. | Check battery voltage, ensure the battery DC switch is on, and verify battery cable connections. |
| 2003 | Battery expansion module undervoltage | The voltage of a battery expansion module is low. | If the sunlight is sufficient or AC reverse charging is allowed, the battery expansion modules can be charged when the inverter is running. |
| 2004 | Power module reversely connected | The positive and negative terminals are reversely connected when the power module connects to the inverter. | 1. Turn off the inverter AC output switch, inverter DC input switch, and battery DC switch, and wait for 5 minutes. 2. Check the cable connections to the power control module. 3. After checking connections, turn on switches in sequence: battery DC, AC output, inverter DC input. |
| 2005 | Abnormal BMS communication | The power module fails to communicate with the battery expansion modules. | 1. Turn off the battery DC switch. 2. Check that the power cables and communications cables are correctly connected. 3. After checking cables, turn on the battery DC switch. |
| 2006 | Equipment fault | An unrecoverable fault occurs on a circuit inside the device. | Turn off the DC switch, and then turn it on after 5 minutes. If the alarm persists, replace the monitoring board. |
| 2007 | Black start-up failed | 1. The battery level is less than 10%. 2. The energy storage DC switch is not turned on. | 1. Turn off the PV switch and AC output switch, and wait for 1 minute for the device to turn off all LED lights. 2, turn on the PV switch and AC output switch, and start black again. |
| 2008 | Battery reversal connection | Battery reversal connection | Check whether the battery is reversely connected to the power module. If so, turn off the DC switch and correct the battery polarity. |
| 3001 | Battery Pack Undervoltage | 1. The voltage of the battery pack or its cell is too low. 2. The battery pack has been stored for a long period of time. 3. The battery pack has been idle for a long time after grid connection. | 1. Connect to the power grid and charge batteries in a timely manner. 2. If the alarm persists after the battery has been charged for one hour, contact support. |
| 3002 | Battery module over temperature | 1. The battery installation position is not well ventilated. 2. The ambient temperature is excessively high. 3. The battery power control module is abnormal. | 1. Check the ventilation and whether the ambient temperature of the battery expansion modules exceeds the upper threshold. 2. If the ventilation is poor or the ambient temperature is excessively high, improve the ventilation and heat dissipation. |
| 3003 | Battery module low temperature | 1. The ambient temperature is excessively low. 2. A battery expansion module is abnormal. | 1. Check whether the ambient temperature in the installation positions of the battery expansion modules is lower than the lower threshold. 2. If the ambient temperature is excessively low, improve the installation environment. |
How do I handle the inverter for removal, packing, and disposal?
Removing the inverter:
Before removing the inverter, power off the AC and DC (batteries).
1. Disconnect all cables from the inverter, including RS485 communications cables, DC input power cables, AC output power cables, and PGND cables.
2. Remove the inverter from the mounting bracket.
3. Remove the mounting bracket.
Packing the inverter:
• If the original packing materials are available, put the inverter inside them and then seal them by using adhesive tape.
• If the original packing materials are not available, put the inverter inside a suitable cardboard box and seal it properly.
Disposing of the inverter:
If the inverter service life expires, dispose of it according to the local disposal rules for electrical equipment waste.
What are the technical specifications of the M1-S(3-6)K series inverters?
| Model | M1-S3K | M1-S3.68K | M1-S4K | M1-S4.6K | M1-S5K | M1-S6K |
|---|---|---|---|---|---|---|
| DC Input (PV) | ||||||
| Max. PV array power (Wp) | 6000 | 7400 | 8000 | 9200 | 10000 | 12000 |
| Max. PV input power (Wp) | 4500 | 5500 | 6000 | 6900 | 7500 | 10000 |
| Max. input voltage (V) | 600 | |||||
| MPPT operating voltage range (V) | 60~550 | |||||
| Start-up voltage (V) | 75 | |||||
| Rated input voltage (V) | 360 | |||||
| Max. input current (input PV1 /input PV2) | 16/16 | |||||
| Max. short-circuit current | 20/20 | |||||
| No. of MPP trackers / Strings per MPP tracker | 2 | |||||
| Battery connection | ||||||
| Battery type | Li-ion | |||||
| Voltage range (V) | 85-460 | |||||
| Max. charge current (A) | 30 | |||||
| Max. discharging current (A) | 30 | |||||
| Max. charge power (W) | 4500 | 5500 | 6000 | 6000 | 6000 | 6000 |
| max. discharge power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| AC Output Data (on-grid) | ||||||
| Nominal AC output power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| Max. AC output apparent power (VA) | 3300 | 3680 | 4400 | 5000 | 5500 | 6000 |
| Nominal Output Current(A) | 13.0 | 16.0 | 17.4 | 20.0 | 21.7 | 26.1 |
| Max. AC output current (A) | 15.0 | 16.0 | 20.0 | 23.0 | 25.0 | 27.3 |
| Max. AC input apparent power (VA) | 6300 | 7360 | 8400 | 9600 | 10000 | 10000 |
| Max. AC input current (VA) | 27.4 | 32.0 | 36.5 | 41.7 | 43.5 | 43.5 |
| Nominal AC voltage (V) | 220Vac/230Vac/ 240Vac,L/N/PE | |||||
| Nominal AC Grid Frequency (Hz) | 50/60 | |||||
| Adjustable power factor | 0.8 leading … 0.8 lagging | |||||
| Max. total harmonic distortion | ≤3% | |||||
| AC Output Data (back-up) | ||||||
| Nominal output power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| Max. continuous current (A) | 13.0 | 16.0 | 17.4 | 20.0 | 21.7 | 26.1 |
| Nominal voltage (V) | 230Vac,L/N/PE | |||||
| Frequency (Hz) | 50/60 | |||||
| General Data | ||||||
| Operating temperature range (°C) | -25°C to + 60°C(Derating above 45°C @ Rated output power) | |||||
| Weight (kg) | 24.5 | |||||
| Max. operating altitude (m) | 4000 | |||||
| Dimension(W/H/D) (mm) | 485/450/187 | |||||
| Degree of protection | IP66 | |||||
CLICK HERE TO DOWNLOAD MIDEA M1-S4K (01) PDF MANUAL
