FREE ENGLISH MIDEA M1-S3.68K (01) PDF USER GUIDE
FREE ENGLISH MIDEA M1-S3.68K (01) PDF USER MANUAL
FREE ENGLISH MIDEA M1-S3.68K (01) PDF OWNER GUIDE
FREE ENGLISH MIDEA M1-S3.68K (01) PDF OWNER MANUAL
FREE ENGLISH MIDEA M1-S3.68K (01) PDF REFERENCE GUIDE
FREE ENGLISH MIDEA M1-S3.68K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH MIDEA M1-S3.68K (01) PDF REFERENCE MANUAL
FREE ENGLISH MIDEA M1-S3.68K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH MIDEA M1-S3.68K (01) PDF OPERATING INSTRUCTIONS
CLICK HERE TO DOWNLOAD MIDEA M1-S3.68K (01) PDF MANUAL
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What do the safety symbols in the manual mean?
| Symbol | Description |
|---|---|
| DANGER | Non-observance will result in death or serious injury. Follow the warnings in order to prevent death or serious injury! |
| WARNING | Non-observance will result in death or serious injury. Follow the warnings in order to prevent serious injury! |
| CAUTION | Non-observance may result in minor injury. Follow the warnings in order to prevent injury! |
| ATTENTION | Non-observance may result in property damage! Follow the warnings in order to prevent damage to or destruction of the product. |
| NOTE | Provides tips essential to the optimal operation of the product. |
What are the key safety instructions for this product?
Qualified Personnel:
For safety reasons, this inverter may only be installed by a qualified electrician who:
• has received training on occupational safety, as well as the installation and commissioning of electrical systems.
• is familiar with the local laws, standards and regulations of the grid operator.
Installation Requirements:
Install the inverter according to the information contained in the manual. Mount the inverter to a suitable object with a sufficient load-bearing capacity (e.g. walls, PV frames etc.) and ensure that the inverter is upright. Ensure sufficient ventilation for air circulation to cool the inverter.
Electrical Connection:
• Before establishing the electrical connection, cover the PV modules using opaque material or disconnect the PV generator from the inverter. Solar radiation will cause dangerous voltage to be generated by the PV generator!
• All installations and electrical connections may only be carried out by trained electricians!
• Obtain authorization from the local power grid operator before connecting the inverter to the public power grid.
Operation:
• Before carrying out any repair work, first switch off the AC circuit breaker between the inverter and power grid, and then the DC switch.
• After switching off the AC circuit breaker and the DC switch, wait a minimum of 5 minutes before starting any maintenance or repair work.
• Contact with the electrical grid or the device’s terminals may result in an electric shock or fire.
• While the inverter is being operated, several internal components will become very hot. Please wear protective gloves and keep children away.
Repair and Maintenance:
Should any repairs be required, please contact a local authorized service center. The internal components of the inverter must NOT be opened without the relevant authorization.
What do the safety symbols on the inverter itself indicate?
| Symbol | Description |
|---|---|
| Symbol with a clock and “5min” | Residual voltage is present in the inverter! Before opening the inverter, you should wait five minutes to ensure that the capacitor has been fully discharged. |
| Lightning bolt in a triangle | Caution! Danger through electric shock. |
| Hand over a hot surface symbol | Caution! Hot surface. |
| Exclamation mark in a triangle | Disconnect the inverter from all the external power sources before maintenance! |
| CE mark | The product is compliant with EU guidelines. |
| Crossed-out wheelie bin | Do not dispose of the inverter together with household waste. |
| Book with ‘i’ symbol | Please read the manual before installing the inverter. |
| Grounding symbol | Grounding point. |
| “Do not disconnect under load!” symbol | Do not remove the DC input connector or AC output connector when the inverter is running. |
What are the main components of the hybrid inverter?
| NO. | Name | Description |
|---|---|---|
| 1 | Hanger Plate | To hang the inverter on the wall-mounting bracket. |
| 2 | Led Indicator Label | To explain the current working state of the inverter. |
| 3 | DC Switch | To safely disconnect the DC circuit whenever necessary. |
| 4 | Indicator | To indicate the current working state of the inverter. |
| 5 | Nameplate | To identify the product, including device model, S/N, important specifications, etc. |
| 6 | Grounding terminal | To connect system to earth. |
| 7 | Electrical connection area | PV terminals, battery terminal, AC terminal, additional grounding terminal and communication terminals. |
How do I interpret the LED indicators on the inverter?
| INDICATOR | COLOR | STATUS | EXPLANATION |
|---|---|---|---|
| DC | Green | Steady on | PV power available |
| Yellow | Steady on | PV power not available/ too low | |
| Red | Steady on | Fault | |
| – | Off | System is power-off | |
| AC | Green | Steady on | Inverter is operating |
| Green | Blinking at long intervals (on for 1s and then off for 1s) | Inverter in standby in grid-tied mode | |
| Yellow | Steady on | Inverter is operating in off-grid mode | |
| Yellow | Blinking at long intervals (on for 1s and then off for 1s) | Inverter in standby in off-grid mode | |
| Red | Steady on | Fault | |
| – | Off | System is power-off | |
| COM | Green | Blinking at long intervals (on for 0.2s and then off for 0.2s) | Wireless waiting for connection |
| Green | Blinking at long intervals (on for 1s and then off for 1s) | Establishing wireless connection | |
| Green | Steady on | Wireless connected | |
| Yellow | Steady on | Bluetooth connected | |
| – | Off | No wireless/bluetooth connected |
What are the different working modes of the hybrid inverter?
Mode1: Maximize Self-consumption
This mode is suitable for areas with high electricity tariff. When the PV power is sufficient, priority is given to the local load, and the excess electricity goes to energy storage, and if there is still energy left, it is sold to the grid. When the PV power is insufficient/there is no PV power, the battery is discharged for the local load, and when the battery discharge power and photovoltaic power can not meet the load demand, the insufficient power will be purchased from the grid.
Mode2: Maximize Feed-in
This mode is suitable for areas with high feed-in tariff. When the PV power is greater than the inverter capacity, the excess electricity will be stored by energy storage. When PV power is less than the inverter capacity, the excess electricity will be sold to the grid.
Mode3: Backup power
This mode is suitable for areas where grid outages occur frequently or to prevent grid outages. Reserved Backup SOC setting value can be adjusted. When battery SOC is less than the reserved SOC value, the battery can only be charged, until SOC reaches the reserved value, the battery will be stopped charging. When SOC is larger than the SOC setting value, the battery will behave as Self-use mode.
Mode4: Charge and discharge schedule
This mode is suitable for areas with peaks and valleys in electricity prices. Battery charging period and discharging period can be set. During the charging period, the battery can only be charged, while in the discharging period, the battery can only be discharged. The rest of the period, the battery will behave as Self-use mode.
Mode5: Peak shaving
This function is to avoid exceeding the peak kW limit from the grid, by dynamically overriding the max kW limit on the battery. Users can set the peak kW value.
NOTE:
• If there is no power from PV, The inverter will take power from the grid first, so it is normal that you will find 20-50W power from the grid when the inverter is on standby mode.
• The battery discharges to provide energy to loads. If the battery is empty or there is not enough power from the battery system, the grid shall supply power to backup loads and normal loads.
• If the smart meter is abnormal or not equipped, the inverter will run normally, however, the battery can be charged but not allowed to discharge. In this case the feed-in limitation setting will be inactive.
What are the guidelines for using the back-up function?
1. For hybrid inverters, if there is no available power from batteries or PV modules in backup mode, the backup power supply will be automatically terminated.
2. Normally, the Back-Up switching time is less than 3 s. However, external factors may cause the system to fail on Back-Up mode. Follow these instructions:
• Do not connect loads that are dependent on a stable energy supply for a reliable operation.
• Do not connect loads whose total capacity is greater than the maximum Back-Up capacity.
• Do not connect loads that may cause very high start-up current surges, such as nonfrequency conversion air conditioning, vacuum cleaner, or half-wave loads like a hair dryer or hammer drill. Refer to the recommended loads table.
• Due to the condition of the battery itself, battery current might be limited by factors like temperature and weather.
• BACK-UP is not recommended if the PV system is not configured with batteries.
• When single overload protection occurs, the inverter can restart automatically; however, the restarting time will be extended if it happens several times.
• When the grid is disconnected, the off-grid function of the inverter will close automatically if the load capacity exceeds the inverter’s rated power. To enable it, turn off the large loads and ensure the load power is less than the rated power of the inverter.
Declaration for Back-Up Overload Protection:
The inverter will restart in case of overload protection. The time required for restarting will increase (5 min at most) if overload protection repeats. Try to reduce Back-Up load power within the maximum limitation or remove the loads which may cause very high start-up current surges.
What types of loads are recommended for backup power?
| Type | Load Power |
|---|---|
| Dust collector | 1.3kW |
| Water heater/Kettle /Iron /Oven /Toaster /Geothermal blanket / Rice cooker | 3 kW |
| Microwave oven | 1.5kW |
| Refrigerator | 1kW |
| TV / Computer | 1Kw |
| Bath heater | 2.5kW |
| Fluorescent / LED lights | 1.3kW |
| Electric fan / Ceiling fan | 2kW |
| Conditioner(frequency conversionmodulation) | 1.5P |
Note: The data is based on tests with batteries (-20 ~ 55 ℃, 5~100% SOC). For actual application, refer to the maximum output capacity of the battery used.
How does the battery management system operate?
The maximum allowable charge/discharge current is limited by the smaller value among: Temperature, the maximum power of the inverter, and the maximum/recommended charge/discharge current from the battery manufacturer. The inverter cannot respond to discharge/charge command when operating off-grid.
| Range | Battery management behavior |
|---|---|
| A (0% to ~15% SOC) | In this range, the battery is no longer discharged, even in battery-backup operation. SoCL can be set from 0 to 15% in APP. |
| B | When operating off grid, the system reports the low SoC state. |
| C | When starting up in off-grid condition, the system does not output AC power, so as to charge the battery by all PV power. |
| D (20% to 90% SOC) | When operating grid-connected, the system charges / discharges the battery for PV power economy. SoCback can be set from 20 to 90% in APP. |
| E | When operating grid-connected, the system charges / discharges the battery for PV power economy. |
| F | When operating off-grid, the system charges / discharges the battery to support the system and obtain PV power economy. |
| G (90% to 100% SOC) | The battery can be discharged to support the system or for PV power economy, while it cannot be charged. The inverter cannot respond to charge command in this range. SoCH can be set from 90 to 100% in APP. |
How do I unpack and inspect the inverter upon delivery?
The product is thoroughly tested and strictly inspected before delivery. Nonetheless, damage may still occur during shipping. For this reason, please conduct a thorough inspection after receiving the product.
• Check the packing case for any visible damage.
• Check the scope of delivery for completeness according to the packing list.
• Check the inner contents for damage after unpacking.
Contact After-sales service provider or the transport company in case of any damage or incompleteness, and provide photos to facilitate services. Do not dispose of the original packing case. It is recommended to store the device in the original packing case when the product is decommissioned.
What are the storage requirements for the inverter?
The following requirements should be met if the M1 series inverter is not put into use directly:
• Do not unpack the M1 series inverter.
• Keep the storage temperature at -40°C to +70°C and the humidity at 5%- 95% RH.
• The M1 series inverter should be stored in a clean and dry place and be protected from dust and water vapor corrosion.
• A maximum of 6 units can be stacked. To avoid personal injury or device damage, stack M1 series inverter with caution to prevent them from falling over.
• Periodic inspections are required during the storage. Replace the packing materials if necessary.
• If the M1 series inverter has been long-term stored, inspections and tests should be conducted by qualified personnel before it is put into use.
What tools are required for installation?
| No. | Tool | Function |
|---|---|---|
| 01 | Hammer drill (Recommended drill diameter: 8mm) | Used to drill holes in the wall |
| 02 | Screwdriver | Wiring |
| 03 | Phillips screwdriver | Used to remove and install the screws of the AC terminal |
| 04 | Removal tool | Used to remove the PV battery terminal |
| 05 | Wire stripper | Used to strip the wire |
| 06 | 6mm Allen key | Used to turn the screw to connect the rear panel to the inverter |
| 07 | Crimping tool | Used to crimp power cables |
| 08 | Multimeter | Used to check the Grounding |
| 09 | Marker | Used for marking |
| 10 | Measuring tape | Used to measure distances |
| 11 | Spirit level | Used to align the wall bracket |
| 12 | ESD gloves | For the installer |
| 13 | Safety goggles | For the installer |
| 14 | Anti-dust respiratory mask | For the installer |
What are the environmental and mounting requirements for installation?
Basic Requirements:
• The Hybrid Inverter is protected to IP65 and can be installed indoors or out doors.
• Do not install the Hybrid Inverter in a place where personnel are easy to come into contact with its enclosure and heat sinks, because these parts are extremely hot during operation.
• Do not install the Hybrid Inverter in areas with flammable or explosive materials.
• Do not install the Hybrid Inverter at a place within children’s reach.
• Do not install the Hybrid Inverter outdoors in salt areas because it will be corroded there and may cause fire. A salt area refers to the region within 500 meters from the coast or prone to sea breeze.
• The Hybrid Inverter must be installed in a well-ventilated environment to ensure good heat dissipation.
• Recommended: Install the Hybrid Inverter in a sheltered place or a place with an awning.
Mounting Requirements:
• The mounting structure where the Hybrid Inverter is installed must be fireproof.
• Do not install the Hybrid Inverter on flammable building materials.
• The Hybrid Inverter is heavy. Ensure that the installation surface is solid enough to bear the weight load.
• In residential areas, do not install the Hybrid Inverter on drywalls or walls made of similar materials which have a weak sound insulation performance because the noise generated by the Hybrid Inverter is noticeable.
What are the space and angle requirements for mounting the inverter?
Angle Requirements:
Install the inverter vertically. Never install the inverter horizontally, or at forward/backward tilted (max 15° forward), side tilted, or upside down.
Space Requirements:
Reserve enough space around the inverter to ensure sufficient space for installation and heat dissipation.
• Clearance above: ≥ 300mm
• Clearance below: ≥ 500mm
• Clearance on left side: ≥ 200mm
• Clearance on right side: ≥ 200mm
How do I install the inverter on the wall?
Step 1. Place the wall-mounting bracket to a proper position on the wall. Use the spirit level on the bracket to ensure it is level (bubble in the middle). Mark the hole positions with a marker and drill the holes (Ø8, Depth 45-50mm).
Step 2. Insert the expansion bolts into the holes and fix the mounting bracket to the wall. Tighten the bolts to 5±0.2Nm.
Step 3. Lift the inverter and slide it down along the wall mounting bracket to make sure they match perfectly. Use two M4*10 screw sets to lock both the left and right sides of the inverter to the bracket. Tighten to 1.2±0.2Nm.
What are the electrical connection safety instructions?
DANGER – Electrical voltage at the DC connections:
• Ensure that the DC switch is OFF before establishing the electrical connection. The reason is that the electrical charge remains in the capacitor after the DC switch has been switched off. Therefore, at least 5 minutes must lapse before the capacitor has been electrically discharged.
DANGER – Electrical voltage:
• PV modules generate electrical energy when exposed to sunlight, and this may present an electrical shock hazard. Therefore, cover the PV modules with an opaque sheet before connecting to the DC input power cable.
DANGER – Electrical voltage at the DC connections:
• Wear rubber gloves and protective clothing (safety goggles and boots) when working on high voltage/high current systems such as inverter and battery systems.
ATTENTION – Qualification:
• The installation and maintenance of the inverter must be carried out by an electrician.
NOTE:
• The open-circuit voltage of the modules connected in series must be lower than or equal to 600 V.
• The connected PV modules must be compliant with IEC 61730 class A.
What are the functions of the electrical terminals on the inverter?
| No. | Name | Description |
|---|---|---|
| 1 | PV input terminal (PV1+/PV1-) | MC4 terminals for PV 1 input. |
| 2 | PV input terminal (PV2+/PV2-) | MC4 terminals for PV 2 input. |
| 3 | BAT input terminal (BAT+/BAT-) | Connectors for the battery power cables. |
| 4 | Communications port (BMS) | Communication connection for Battery BMS. |
| 5 | Communications port (RJ45) | Communication port Reserved. |
| 6 | Wireless button | Used to enable WiFi distribution network mode or OTA. |
| 7 | Communications port (COM) | Communication connection for smart energy meter, DI/DO RSD, etc. |
| 8 | AC-Backup output port | AC terminal for Backup loads. |
| 9 | AC-Grid output port | AC terminal to connect to the grid. |
| 10 | Ventilation valve | / |
| 11 | Wireless Communications | Communication accessory port to be connected to WiNet-S communication module. |
What are the cable requirements for electrical connections?
| NO. | Cable | Type | Cable Diameter | Cross-section |
|---|---|---|---|---|
| 1 | PV cable | Complying with 600V and 16A standard | 6-9mm | 4-6 mm² |
| 2 | AC-Backup cable | Outdoor 3-core copper wire cable | 10-21mm | 4-6 mm² |
| 3 | AC-Grid cable | Outdoor 3-core copper wire cable | 12-25.8mm | 6-16 mm² |
| 4 | BAT Power cable | Complying with 600V and 35A standard | 5.5-8mm | 6 mm² |
| 5 | Communication cable | CAT 5E outdoor shielded network cable | 4.8-6mm | 0.08-0.2 mm² |
| 6 | Grounding cable | Single-core copper wire cable | The same as PE wire in AC cable | |
ATTENTIONS:
• If local standards have other requirements for cables, set the cable specification according to the local standard.
• The factors that affect cable selection include rated current, cable type, routing mode, ambient temperature, and maximum expected line loss.
• The cabling distance between the battery and the inverter should be less than 10m, and within 5m is recommended.
How do I connect the ground cable?
Connect the inverter to the equipotential bonding bar by using the protective earth cable (PE) for grounding.
ATTENTION: As the inverter is transformerless, the plus and minus poles of the PV generator must NOT be earthed. Otherwise, the inverter will malfunction.
1. Strip 6 mm of insulation from the 4 mm² ground cable. The exposed length should be 8-10 mm.
2. Crimp a ring terminal onto the stripped end of the cable. Place heat-shrink tubing over the connection.
3. Use a crimping tool to secure the terminal.
4. Connect the ground cable’s ring terminal to the grounding point on the side of the inverter using an M4 screw. Tighten to 1.2±0.2Nm.
How do I perform the AC output connection?
The AC power cables connect the inverter to the critical loads (AC-BACKUP port) and the AC power distributor or power grid (AC-GRID port). The blue connector is for the grid, and the black connector is for backup. The installation process is the same for both.
1. Strip the outer jacket of the AC cable (30-50 mm). Strip the insulation from the L, N, and PE wires.
2. Insert the wires into the corresponding terminals of the connector housing (L-Brown, N-Blue, PE-Yellow-Green) and tighten the screws to 1.2±0.2Nm.
3. Assemble the connector housing and screw the cable gland tight.
4. Connect the assembled AC connector to the corresponding port (AC-GRID or AC-BACKUP) on the inverter by turning it clockwise until it clicks and locks into place.
To remove: Turn the AC connector anticlockwise.
NOTE: When you use the meter connection function, make sure that the AC terminal cable corresponds to the meter cable one by one (L, N and PE cables).
How do I install the DC (PV and Battery) connectors?
NOTE: The connection steps for the battery and PV are the same, but the terminal specifications and colors are different. The battery terminal is blue, and the PV terminal is black.
Installing the PV/Battery Connectors:
1. Strip 7 mm of insulation from the red (+) and black (-) 4 mm² cables.
2. Insert the stripped ends into the metal pins of the DC connector.
3. Use a crimping tool to crimp the pins onto the wires.
4. Insert the crimped red (+) and black (-) wires into the corresponding positive and negative plastic connector housings until they click into place.
5. Tighten the end caps onto the connector housings.
Installing the PV/Battery Connector to the Inverter:
1. Rotate the DC switch on the inverter to the “OFF” position.
2. Check the cable connection of the PV string for polarity correctness and ensure the open circuit voltage does not exceed the inverter input limit of 600V.
3. Connect the PV and/or Battery connectors to the corresponding terminals on the inverter (PV1+/-, PV2+/-, BAT+/-) until there is an audible click.
NOTE: Insert the protective caps into any unused DC connections. Before removing any DC connector, ensure the DC switch has been set to OFF.
How do I connect the BMS RJ45 communication cable?
The Enable cable and RJ45 cable are for communication between the inverter and a Li-ion battery.
Step 1 (optional, if not using a pre-made cable):
• Thread the communication cable (Ø4.8-6mm) through the waterproof component.
• Strip the insulation layer of the cable with an Ethernet wire stripper.
• Insert the stripped communication cable wires into the RJ45 plug in the correct order and crimp it with a crimper.
• Before installing the connector, tighten the waterproof cover.
Step 2:
• Find the BMS terminal under the inverter.
• Insert the RJ45 plug into the BMS terminal, ensuring it is inserted correctly.
• Tighten the waterproof screw cap.
How do I connect the Smart Meter with CT?
The Smart Meter can be installed in an AC combiner box or other places inaccessible to children. The Current Transformer (CT) is usually installed on the L wire between the house loads and the power grid.
Follow the electrical diagram provided in the manual to connect the smart meter and CT. The meter terminals are defined as follows:
| NO. | Definition | Function |
|---|---|---|
| 1 | L-S1 | To detect the CT current and direction |
| 2 | L-S2 | |
| 3 | N | Power supplied from grid |
| 4 | L | |
| 8 | GND | Ground connection |
| 9 | B- | Communicate with hybrid inverter |
| 10 | A+ |
How do I set the Smart Meter parameters?
The energy meter is preconfigured. To change or check settings, use the button on the meter:
• Set ID: Long-press to enter setting mode. Tap to cycle through values. Long-press to confirm.
• Set Baud rate: From the ID screen, tap to move to the Baud rate setting. Long-press to enter setting mode. Tap to cycle through values. Long-press to confirm.
• Set primary current: From the Baud rate screen, tap to move to the primary current setting. Long-press to enter setting mode. Tap to cycle through values. Long-press to confirm.
The screen will stop flickering when the setting is successfully saved.
How do I connect the Wireless Module?
1. Remove the protective cap from the USB interface (labeled WiNet-S or similar).
2. Install the Wireless stick into the USB port.
3. Tighten the connecting nut to secure the module.
What is the pin definition for the communication ports?
Multi-COM Port Definition
| PIN | Definition | Function |
|---|---|---|
| P1 RJ45 | RS485+(A2)/RS485-(B2) | Communicate with smart meters |
| P2 RJ45 | RS485+(A2)/RS485-(B2) | Communicate with heat pump |
| 1 | DO1+ | Dry contacts of load control |
| 2 | DO1- | |
| 3 | DO2 | Dry contacts of load control |
| 4 | DO3 | |
| 5 | DO_COM | |
| 6 | DRM1/5 | Demand response modes (DRED For Australia and New Zealand, RCR For Germany and some other European countries) |
| 7 | DRM2/6 | |
| 8 | DRM3/7 | |
| 9 | DRM4/8 | |
| 10 | COM | 12V power supply |
| 11 | COM_LOAD/0 | Demand response modes |
| 12 | ES | For WSD(wired shut down)/NS protection |
| 13 | Grid on | For grid operator |
| 14 | COM | 12V power supply |
| 15 | RS485B1 | Communicate with inverter |
| 16 | RS485A1 | |
| 17 | RS485B1 | |
| 18 | RS485A1 | |
| 19 | RS485B3 | Communicate with upper computer |
| 20 | RS485A3 | |
| 21 | / | Reserved |
| 22 | / | Reserved |
What is the pre-power-on checklist for commissioning?
Before powering on, check that the DC and AC voltages are within the permissible range of the inverter.
| No. | Item | Acceptance Criterion |
|---|---|---|
| 1 | Inverter installation | The Inverter is installed correctly and securely. |
| 2 | Battery installation (optional) | The Energy Storage Unit is installed correctly and securely. |
| 3 | Wireless module | The Wireless module is installed correctly and securely. |
| 4 | Cable routing | The cables are routed properly as required by the customer. |
| 5 | Cable ties | Cable ties are secured evenly and no burr exists. |
| 6 | Reliable grounding | The PE cable is connected correctly and securely. |
| 7 | Switch | DC switches and all the switches connecting to the Inverter are OFF. |
| 8 | Cable connection | The AC output power cable, DC input power cables, battery cable, and signal cable are connected correctly and securely. |
| 9 | Unused terminals and ports | Unused terminals and ports are locked by watertight caps. |
| 10 | Installation environment | The installation space is proper, and the installation environment is clean and tidy. |
How do I power on the system?
1. If a battery is connected, turn on the battery switch.
2. Turn on the AC switch between the inverter and the power grid.
3. Turn on the DC switch (if any) between the PV string and the inverter.
4. Turn on the DC switch at the bottom of the inverter.
5. Wait for about 1 minute and observe the LED indicators on the inverter to check its running status.
How do I power off the system?
If the inverter needs to be shut down for electrical inspection, please follow these steps:
1. Turn off the AC switch between the inverter and the power grid.
2. Turn off the DC switch at the bottom of the inverter.
3. If there is a DC switch between the inverter and PV string, turn off the DC switch.
4. Turn off the DC switch at the battery (Optional).
5. Wait for 5 minutes before checking the inverter.
What routine maintenance is required?
Inverters do not generally require daily or routine maintenance. Before carrying out cleaning, ensure that the DC switch and AC circuit breaker between the inverter and power grid have been switched off. Wait at least 5 minutes before carrying out cleaning.
Cleaning the inverter:
Clean the inverter using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, or cleaning agents.
Cleaning the heat sink:
To help guarantee correct long-term operation of the inverter, make sure there is sufficient space for ventilation around the heat sink. Check the heat sink for blockages (dust, snow etc.) and remove them if present. Please clean the heat sink using an air blower and a dry, soft cloth or a soft bristle brush. Do not clean the heat sink with water, corrosive chemicals, or cleaning agents.
How do I troubleshoot common problems?
First, check the warnings, error messages, or error codes displayed on the screen of the app. If no error information is displayed, check whether the following requirements have been fulfilled:
• Has the inverter been set up in a clean, dry, well-ventilated area?
• Is the DC switch set to ON?
• Are the cables sufficiently dimensioned and short enough?
• Are the input connections, output connections and the wiring all in good condition?
• Are the configuration settings for the relevant installation correct?
• Are the communication cables correctly connected and undamaged?
What do the error codes mean and how can I resolve them?
| Alarm ID | Alarm Name | Possible Cause | Troubleshooting |
|---|---|---|---|
| 1001 | String reverse connection | The PV string polarity is reversed. | Check whether the PV string is reversely connected. If so, wait until the string current decreases to below 0.5 A. Then, turn off the DC switch and correct the polarity. |
| 1002 | Abnormal residual current | The input-to-ground insulation impedance has decreased during operation. | If accidental, it may recover automatically. If it persists, check if the impedance between the PV string and ground is too low. |
| 1003 | Low insulation resistance | 1. A short circuit exists between the PV array and the ground. 2. The PV array is in a moist environment. | 1. Check impedance between PV array output and ground. Rectify any short circuit or insufficient insulation. 2. Check PE cable connection. 3. Adjust insulation resistance protection threshold via APP if needed in moist environments. |
| 1004 | Cabinet over temperature | 1. Poor ventilation. 2. Ambient temperature too high. 3. Inverter not operating properly. | 1. Check ventilation and ambient temperature. Improve if needed. 2. If conditions are normal, contact your dealer or technical support. |
| 1005 | Grid loss | 1. Power grid outage. 2. AC circuit is disconnected or AC switch is off. | 1. Alarm clears automatically when grid recovers. 2. Check AC circuit and switch. |
| 1006 | Power Module Communication failure | The battery communication is abnormal. | Check that the communications cable is correctly installed, and that the communication parameters are the same as the inverter RS485 configurations. |
| 1007 | BMS Communication failure | The battery communication is abnormal. | |
| 1008 | Meter Communication failure | The meter communication is abnormal. | |
| 1009 | Equipment fault | An unrecoverable fault occurs on a circuit inside the inverter. | Turn off AC and DC switches, wait 5 minutes, then turn them on. If alarm persists, contact your dealer or technical support. |
| 1010 | Grid overvoltage | The grid voltage exceeds the upper threshold. | 1. If occasional, the grid may be temporarily abnormal. 2. If persistent, check if grid voltage is in range. If not, contact power operator. If yes, modify protection thresholds via APP (with operator consent). |
| 1011 | Grid undervoltage | The grid voltage is below the lower threshold. | |
| 1012 | Grid over frequency | The actual power grid frequency is higher than requirements. | 1. If occasional, the grid may be temporarily abnormal. 2. If persistent, check if grid frequency is in range. If not, contact power operator. If yes, modify protection thresholds via APP (with operator consent). |
| 1013 | Grid under frequency | The actual power grid frequency is lower than requirements. | |
| 1014 | AC-grid output overcurrent | Grid voltage drops dramatically or is short-circuited. | Inverter monitors and recovers automatically. If persistent, check for output short circuit. If fault persists, contact dealer/support. |
| 1015 | AC-backup output overcurrent | The backup load power exceeds the upper threshold. | 1. Try to reduce the load power. 2. If it doesn’t work, contact your dealer or technical support. |
| 2001 | Power module over temperature | 1. Poor ventilation. 2. Ambient temperature too high. 3. Battery power control module is abnormal. | 1. Check ventilation and ambient temperature. 2. Improve ventilation if poor or temperature is high. 3. If conditions are normal, contact your dealer or technical support. |
| 2002 | Low battery DC input bus voltage | 1. DC bus voltage of battery is low. 2. Battery DC switch is OFF. 3. Battery cables not correctly connected. | Check battery charge, DC switch status, and cable connections. |
| 2003 | Battery expansion module undervoltage | The voltage of a battery expansion module is low. | If sunlight is sufficient or AC reverse charging is allowed, the battery expansion modules can be charged when the inverter is running. |
| 2004 | Power module reversely connected | Positive and negative terminals are reversely connected. | 1. Turn off all switches for 5 mins. 2. Check cable connections. 3. Turn on switches in sequence. 4. If alarm persists, contact support. |
| 2005 | Abnormal BMS communication | The power module fails to communicate with the battery expansion modules. | 1. Turn off battery DC switch. 2. Check power and communication cables to battery modules. 3. Turn on battery DC switch. 4. If alarm persists, contact support. |
| 2006 | Equipment fault | An unrecoverable fault occurs on a circuit inside the device. | Turn off the DC switch, wait 5 minutes, then turn on. If alarm persists, contact support. |
| 2007 | Black start-up failed | 1. Battery level is less than 10%. 2. Energy storage DC switch is not turned on. | 1. Turn off PV and AC switches for 1 minute. 2. Turn on PV and AC switches and start black again. |
| 2008 | Battery reversal connection | Battery reversal connection. | Check if the battery is reversely connected to the power module. If so, turn off the DC switch and correct the battery polarity. |
| 3001 | Battery Pack Undervoltage | 1. Voltage of battery pack is too low. 2. Stored for a long time. 3. Idle for a long time. | 1. Connect to the power grid and charge batteries. 2. If alarm persists after charging, contact support. |
| 3002 | Battery module over temperature | 1. Poor ventilation. 2. Ambient temperature too high. 3. Battery power control module is abnormal. | 1. Check ventilation and temperature. 2. Improve ventilation if needed. 3. If conditions are normal, contact support. |
| 3003 | Battery module low temperature | 1. Ambient temperature is too low. 2. A battery expansion module is abnormal. | 1. Check if ambient temperature is below threshold. 2. Improve the installation environment. 3. If alarm persists after temperature normalizes, contact support. |
How do I handle the inverter for removal, packing, or disposal?
Removing the inverter:
Before removing the inverter, power off the AC and DC (batteries).
1. Disconnect all cables from the inverter, including RS485 communications cables, DC input power cables, AC output power cables, and PGND cables.
2. Remove the inverter from the mounting bracket.
3. Remove the mounting bracket.
Packing the inverter:
• If the original packing materials are available, put the inverter inside them and then seal them by using adhesive tape.
• If the original packing materials are not available, put the inverter inside a suitable cardboard box and seal it properly.
Disposing of the inverter:
If the inverter service life expires, dispose of it according to the local disposal rules for electrical equipment waste. This product complies with the EU WEEE Directive and should not be disposed of with other household wastes. Used devices must be returned to an official collection point for recycling.
What are the technical specifications of the M1-S(3-6)K series inverters?
| Model | M1-S3K | M1-S3.68K | M1-S4K | M1-S4.6K | M1-S5K | M1-S6K |
|---|---|---|---|---|---|---|
| DC Input (PV) | ||||||
| Max. PV array power (Wp) | 6000 | 7400 | 8000 | 9200 | 10000 | 12000 |
| Max. PV input power (Wp) | 4500 | 5500 | 6000 | 6900 | 7500 | 10000 |
| Max. input voltage (V) | 600 | |||||
| MPPT operating voltage range (V) | 60~550 | |||||
| Start-up voltage (V) | 75 | |||||
| Rated input voltage (V) | 360 | |||||
| Max. input current (input PV1 /input PV2) | 16/16 | |||||
| Max. short-circuit current | 20/20 | |||||
| No. of MPP trackers / Strings per MPP tracker | 2 | |||||
| Battery connection | ||||||
| Battery type | Li-ion | |||||
| Voltage range (V) | 85-460 | |||||
| Max. charge current (A) | 30 | |||||
| Max. discharging current (A) | 30 | |||||
| Max. charge power (W) | 4500 | 5500 | 6000 | 6000 | 6000 | 6000 |
| Max. discharge power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| AC Output Data (on-grid) | ||||||
| Nominal AC output power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| Max. AC output apparent power (VA) | 3300 | 3680 | 4400 | 5000 | 5500 | 6000 |
| Nominal Output Current(A) | 13.0 | 16.0 | 17.4 | 20.0 | 21.7 | 26.1 |
| Max. AC output current (A) | 15.0 | 16.0 | 20.0 | 23.0 | 25.0 | 27.3 |
| Max. AC input apparent power (VA) | 6300 | 7360 | 8400 | 9600 | 10000 | 10000 |
| Max. AC input current (VA) | 27.4 | 32.0 | 36.5 | 41.7 | 43.5 | 43.5 |
| Nominal AC voltage (V) | 220Vac / 230Vac/ 240Vac,L/N/PE | |||||
| Nominal AC Grid Frequency (Hz) | 50/60 | |||||
| Adjustable power factor | 0.8 leading … 0.8 lagging | |||||
| Max. total harmonic distortion | ≤3% | |||||
| AC Output Data (back-up) | ||||||
| Nominal output power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| Max. continous current (A) | 13.0 | 16.0 | 17.4 | 20.0 | 21.7 | 26.1 |
| Nominal voltage (V) | 230Vac,L/N/PE | |||||
| Frequency (Hz) | 50/60 | |||||
| General Data | ||||||
| Operating temperature range (°C) | -25°C to + 60°C(Derating above 45°C @ Rated output power) | |||||
| Weight (kg) | 24.5 | |||||
| Max. operating altitude (m) | 4000 | |||||
| Dimension(W/H/D) (mm) | 485/450/187 | |||||
| Degree of protection | IP66 | |||||
CLICK HERE TO DOWNLOAD MIDEA M1-S3.68K (01) PDF MANUAL
