FREE ENGLISH MIDEA M1-S3K (01) PDF USER GUIDE
FREE ENGLISH MIDEA M1-S3K (01) PDF USER MANUAL
FREE ENGLISH MIDEA M1-S3K (01) PDF OWNER GUIDE
FREE ENGLISH MIDEA M1-S3K (01) PDF OWNER MANUAL
FREE ENGLISH MIDEA M1-S3K (01) PDF REFERENCE GUIDE
FREE ENGLISH MIDEA M1-S3K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH MIDEA M1-S3K (01) PDF REFERENCE MANUAL
FREE ENGLISH MIDEA M1-S3K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH MIDEA M1-S3K (01) PDF OPERATING INSTRUCTIONS
CLICK HERE TO DOWNLOAD MIDEA M1-S3K (01) PDF MANUAL
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the meanings of the safety symbols used in the manual?
The manual uses symbols to ensure the safety of persons and property. Please read through the following symbol explanations carefully in order to prevent injury or property damage.
DANGER
Non-observance will result in death or serious injury. Follow the warnings in order to prevent death or serious injury!
WARNING
Non-observance will result in death or serious injury. Follow the warnings in order to prevent serious injury!
CAUTION
Non-observance may result in minor injury. Follow the warnings in order to prevent injury!
ATTENTION
Non-observance may result in property damage! Follow the warnings in order to prevent damage to or destruction of the product.
NOTE
Provides tips essential to the optimal operation of the product.
What are the requirements for qualified personnel installing the inverter?
Personnel tasked with the operation and maintenance of the device must have the qualifications, competence and experience required to perform the described tasks, while also being capable of fully understanding all instructions contained within the manual. For safety reasons, this inverter may only be installed by a qualified electrician who:
has received training on occupational safety, as well as the installation and commissioning of electrical systems.
is familiar with the local laws, standards and regulations of the grid operator.
What are the safety precautions for electrical connection?
Observe all applicable electrical regulations when working with the Solar inverter.
DANGER: Dangerous DC voltage
Before establishing the electrical connection, cover the PV modules using opaque material or disconnect the PV generator from the inverter. Solar radiation will cause dangerous voltage to be generated by the PV generator!
DANGER: Danger through electric shock!
All installations and electrical connections may only be carried out by trained electricians!
IMPORTANT: Authorization for grid feed-in
Obtain authorization from the local power grid operator before connecting the inverter to the public power grid.
NOTE: Voiding of guarantee
Do not open the inverter or remove any of the labels. Otherwise, the guarantee will be void.
What are the safety precautions for operating the inverter?
DANGER: Dangerous voltage!
Before carrying out any repair work, first switch off the AC circuit breaker between the inverter and power grid, and then the DC switch.
After switching off the AC circuit breaker and the DC switch, wait a minimum of 5 minutes before starting any maintenance or repair work.
Electric shock
Contact with the electrical grid or the device’s terminals may result in an electric shock or fire!
Do not touch the terminal or the conductor which is connected to the electrical grid.
Follow all instructions and observe all safety documents that refer to the grid connection.
CAUTION: Burning due to hot housing
While the inverter is being operated, several internal components will become very hot.
Please wear protective gloves!
Keep children away from the device!
What should I know about unauthorized repairs and maintenance?
Following the elimination of any faults, the inverter should be fully functional once more. Should any repairs be required, please contact a local authorized service center.
The internal components of the inverter must NOT be opened without the relevant authorization.
The hardware and software after-sale service can be received from the authorized dealer. Software updates service will be available for warranty years from the manufacture date via the OTA(Over-The-Air) download technology.
What do the safety symbols on the inverter mean?
| symbols | Description |
|---|---|
| Symbol showing a hand inside a triangle with a timer icon labeled “5min”. | Residual voltage is present in the inverter! Before opening the inverter, you should wait five minutes to ensure that the capacitor has been fully discharged. |
| Symbol of a lightning bolt inside a triangle. | Caution! Danger through electric shock. |
| Symbol of three wavy vertical lines inside a triangle. | Caution! Hot surface. |
| Symbol of an exclamation mark inside a triangle. | Disconnect the inverter from all the external power sources before maintenance! |
| CE Mark. | The product is compliant with EU guidelines. |
| Symbol of a crossed-out wheeled bin. | Do not dispose of the inverter together with household waste. |
| Symbol of an open book with an ‘i’ for information. | Please read the manual before installing the inverter. |
| Symbol of a grounding point. | Grounding point. |
| Symbol of a triangle with “Do not disconnect under load!”. | Do not remove the DC input connector or AC output connector when the inverter is running. |
What are the main components of the hybrid inverter?
| NO. | Name | Description |
|---|---|---|
| 1 | Hanger Plate | To hang the inverter on the wall-mounting bracket. |
| 2 | Led Indicator Label | To explain the current working state of the inverter. |
| 3 | DC Switch | To safely disconnect the DC circuit whenever necessary. |
| 4 | Indicator | To indicate the current working state of the inverter. |
| 5 | Nameplate | To identify the product, including device model, S/N, important specifications, etc. |
| 6 | Grounding terminal | To connect system to earth. |
| 7 | Electrical connection area | PV terminals, battery terminal, AC terminal, additional grounding terminal and communication terminals. |
What do the LED indicators on the inverter mean?
| INDICATOR | COLOR | STATUS | EXPLANATION |
|---|---|---|---|
| DC | Green | Steady on | PV power available |
| Yellow | Steady on | PV power not available/ too low | |
| Red | Steady on | Fault | |
| – | Off | System is power-off | |
| AC | Green | Steady on | Inverter is operating |
| Green | Blinking at long intervals (on for 1s and then off for 1s) | Inverter in standby in grid-tied mode | |
| Yellow | Steady on | Inverter is operating in off-grid mode | |
| Yellow | Blinking at long intervals (on for 1s and then off for 1s) | Inverter in standby in off-grid mode | |
| Red | Steady on | Fault | |
| – | Off | System is power-off | |
| COM | Green | Blinking at long intervals (on for 0.2s and then off for 0.2s) | Wireless waiting for connection |
| Green | Blinking at long intervals (on for 1s and then off for 1s) | Establishing wireless connection | |
| Green | Steady on | Wireless connected | |
| Yellow | Steady on | Bluetooth connected | |
| – | Off | No wireless/bluetooth connected |
What are the working modes of the hybrid inverter?
| Working mode | Description |
|---|---|
| Standby | The Hybrid Inverter enters Standby mode when the external environment does not meet the operating requirements. In Standby mode: The Hybrid Inverter continuously performs status check and enters the Operating mode once the operating requirements are met. The Hybrid Inverter enters Shutdown mode after detecting a shutdown command or a fault after startup. |
| Operating | In Operating mode: The Hybrid Inverter converts DC power from PV strings into AC power and feeds the power to the power grid. The Hybrid Inverter tracks the maximum power point to maximize the PV string output. If Hybrid Inverter detects a fault or a shutdown command, it enters the Shutdown mode. The Hybrid Inverter enters Standby mode after detecting that the PV string output power is not suitable for connecting to the power grid for generating power. |
| Shutdown | In Standby or Operating mode, the Hybrid Inverter enters Shutdown mode after detecting a fault or shutdown command. In Shutdown mode, the Hybrid Inverter enters Standby mode after detecting a startup command or that the fault is rectified. |
What should I know before setting up a PV Energy Storage System (PV ESS)?
Only 2 or 3 battery packs can be connected to one battery cluster. please configuring as required.
Under any connection, either grid-connection or off-grid application, please be sure that the potential voltage between N and PE line is not higher than 30V, otherwise, inverter will stop generating power.
The system is not suitable for supplying life-sustaining medical devices. It cannot guarantee backup power in all circumstances. The PV generator must be earthed in accordance with the requirements of the local power grid operator!
What is the declaration for the Back-Up function and overload protection?
Declaration for Back-Up Function
1. For hybrid inverters, the electrical installation typically includes connection of the inverter to both PV modules and batteries. If there is no available power from batteries or PV modules in backup mode, the backup power supply will be automatically terminated. The inverters shall hold no liability for any consequences arising from failing to observe this instruction.
2. Normally, the Back-Up switching time is less than 3 s. However, some external factors may cause the system to fail on Back-Up mode. Therefore, the users must be aware of conditions and follow the instructions as below:
Do not connect loads that are dependent on a stable energy supply for a reliable operation.
Do not connect the loads whose total capacity is greater than the maximum Back-Up capacity.
Do not connect the loads that may cause very high start-up current surges, such as nonfrequency conversion air conditioning, vacuum cleaner or half-wave loads such as hair dryer, heat gun, hammer drill.
Due to the condition of the battery itself, battery current might be limited by some factors, including but not limited to the temperature and weather.
BACK-UP is not recommended if the PV system is not configured with batteries. Otherwise, the risk in system power usage is beyond the equipment manufacturer’s warranty scope.
When single overload protection occurs, the inverter can restart automatically; however, the restarting time will be extended if it happens several times.
When the grid is disconnected, the off-grid function of the inverter will be closed automatically if the load capacity exceeds the inverter’s rated power; to enable it, turn off the large loads and ensure the load power is less than the rated power of the inverter.
Declaration for Back-Up Overload Protection
The inverter will restart in case of overload protection. The time required for restarting will increase (5 min at most) if overload protection repeats. Try to reduce Back-Up load power within maximum limitation or remove the loads which may cause very high start-up current surges.
What are the recommended backup loads and their power consumption?
| Type | Load Power |
|---|---|
| Dust collector | 1.3kW |
| Water heater/Kettle /Iron /Oven /Toaster /Geothermal blanket / Rice cooker | 3 kW |
| Microwave oven | 1.5kW |
| Refrigerator | 1kW |
| TV / Computer | 1Kw |
| Bath heater | 2.5kW |
| Fluorescent / LED lights | 1.3kW |
| Electric fan / Ceiling fan | 2kW |
| Conditioner(frequency conversionmodulation) | 1.5P |
The data of the compatibility for backup of Hybrid Inverter are based on the test with batteries (-20 ~ 55 ℃, 5~100% SOC). For the actual application, please refer to the maximum output capacity of the battery used.
What are the different working modes for the PV Energy Storage System?
Mode1: Maximize Self-consumption
This mode is suitable for areas with high electricity tariff. When the PV power is sufficient, priority is given to the local load, and the excess electricity goes to energy storage, and if there is still energy left, it is sold to the grid. When the PV power is insufficient/there is no PV power, the battery is discharged for the local load, and when the battery discharge power and photovoltaic power can not meet the load demand, the insufficient power will be purchased from the grid.
Mode2: Maximize Feed-in
This mode is suitable for areas with high feed-in tariff. When the PV power is greater than the inverter capacity, the excess electricity will be stored by energy storage. When PV power is less than the inverter capacity, the excess electricity will be sold to the grid.
Mode3: Backup power
This mode is suitable for areas where grid outages occur frequently or to prevent grid outages. Reserved Backup SOC setting value can be adjusted, when battery SOC is less than reserved SOC value, battery can only be charged, until SOC reaches reserved value, the battery will be stopped charging; when SOC is larger than SOC setting value, battery will behave as Self-use mode.
Mode4: Charge and discharge schedule
This mode is suitable for areas with peaks and valleys in electricity prices Battery charging period and discharging period can be set, during charging period, battery can only be charged, while in discharging period, battery can only be discharged, the rest of the period, battery will behave as Self-use mode.
Mode5: Peak shaving
This function is to avoid exceeding peak kW limit from grid, by dynamically overriding the max kW limit on the battery. Users can set the peak kW value.
NOTE
If there is no power from PV, The inverter will take power from grid firstly.so it is normal that you will find 20-50W power from grid when the inverter is on standby mode.
The battery discharges to provide energy to loads. If the battery is empty or there is not enough power from the battery system, the grid shall supply power to backup loads and normal loads.
If the smart meter is abnormal or not equipped, the inverter will run normally, however, the battery can be charged but not allowed to discharge. In this case the feed-in limitation setting will be inactive.
When does the inverter derate its power?
Power deration is a way to protect the inverter from overload or potential faults. In addition, the deration function can also be activated following the requirements of the utility grid. Situations requiring inverter power deration are:
over-temperature (including ambient temperature and module temperature)
high input voltage
grid under-voltage
grid over-frequency
power factor (when values out of the rated values)
high altitude
How does the inverter manage the battery charge and discharge?
The maximum allowable charge/discharge current is limited to the smaller value among: Temperature, the maximum power of inverter, and the maximum / recommended charge/discharge current from the battery manufacturer. The inverter cannot respond to discharge/charge command when operating off-grid.
| Range | Battery management behavior |
|---|---|
| A | In this range, the battery is no longer discharged, even in battery-backup operation. SoCL can be set from 0 to 15% in APP. |
| B | When operating off grid, the system reports the low SoC state. |
| C | When starting up in off-grid condition, the system does not output AC power, so as to charge the battery by all PV power. |
| D | When operating grid-connected, the system charges / discharges the battery for PV power economy. SoCback can be set from 20 to 90% in APP. |
| E | When operating grid-connected, the system charges / discharges the battery for PV power economy. |
| F | When operating off-grid, the system charges / discharges the battery to support the system and obtain PV power economy. |
| G | The battery can be discharged to support the system or for PV power economy, while it cannot be charged. The inverter cannot respond to charge command in this range. SoCH can be set from 90 to 100% in APP. |
What are the feed-in and charge-from-grid limitation functions?
Feed-in limitation function
The function of the feed-in limitation is to control the amount of power injected in the grid by the plant. This function requires a power measurement device must be installed. The sum of the feeding-in phases must not exceed the set power limitation value. The power of phases drawing power from the grid is disregarded here.
Charge-from-grid limitation function
The function of the Charge-from-grid limitation is to limit the amount of power charging the battery from the grid. This function requires a power measurement device to be installed. The sum of the Charge-from-grid phases must not exceed the set power limitation value. The power of phases drawing power from the grid is disregarded here.
What is included in the scope of delivery?
The actual product received may differ from this list, which is for reference.
Energy manager*1
Smart meter + current transformer*1
D4 Disassembly tool*1
Photovoltaic connector – straight male*2 (BLACK)
Photovoltaic connector – straight female*2 (BLACK)
Battery connector – straight male*1 (BLUE)
Battery connector – straight female*1 (BLUE)
Multi-COM (2-RJ45+22pin)
Backup connector (BLACK)
Grid-connected connector (BLUE)
Ground terminal*2
Wireless module*1
Mounting bracket*1
Electric meter communication Line*1
Expansion bolt*4
SEM screw M4X12*4
RJ45 connector*1
Quick guide*1, Packing list*1, User manual*1, Delivery inspection report*1, Quality certificate*1, Warranty card*1
What are the storage requirements for the inverter?
The following requirements should be met if the M1 series inverter is not put into use directly:
Do not unpack the M1 series inverter.
Keep the storage temperature at -40°C to +70°C and the humidity at 5%- 95% RH.
The M1 series inverter should be stored in a clean and dry place and be protected from dust and water vapor corrosion.
A maximum of 6 units can be stacked. To avoid personal injury or device damage, stack M1 series inverter with caution to prevent them from falling over.
Periodic inspections are required during the storage. Replace the packing materials if necessary.
If the M1 series inverter has been long-term stored, inspections and tests should be conducted by qualified personnel before it is put into use.
What tools are recommended for installing the inverter?
| No. | Tool | Model | Function |
|---|---|---|---|
| 01 | Hammer drill | Recommended drill diameter: 8mm | Used to drill holes in the wall |
| 02 | Screwdriver | Wiring | |
| 03 | Phillips screwdriver | Used to remove and install the screws of the AC terminal | |
| 04 | Removal tool | Used to remove the PV battery terminal | |
| 05 | Wire stripper | Used to strip the wire | |
| 06 | 6mm Allen key | Used to turn the screw to connect the rear panel to the inverter | |
| 07 | Crimping tool | Used to crimp power cables | |
| 08 | Multimeter | Used to check the Grounding | |
| 09 | Marker | Used for marking | |
| 10 | Measuring tape | Used to measure distances | |
| 11 | Spirit level | Used to align the wall bracket | |
| 12 | ESD gloves | For the installer | |
| 13 | Safety goggles | For the installer | |
| 14 | Anti-dust respiratory mask | For the installer |
What are the environmental and mounting requirements for installation?
Basic environmental requirements
The Hybrid Inverter is protected to IP65 and can be installed indoors or out doors.
Do not install the Hybrid Inverter in a place where personnel are easy to come into contact with its enclosure and heat sinks, because these parts are extremely hot during operation.
Do not install the Hybrid Inverter in areas with flammable or explosive materials.
Do not install the Hybrid Inverter at a place within children’s reach.
Do not install the Hybrid Inverter outdoors in salt areas because it will be corroded there and may cause fire. A salt area refers to the region within 500 meters from the coast or prone to sea breeze.
The Hybrid Inverter must be installed in a well-ventilated environment to ensure good heat dissipation.
Recommended: Install the Hybrid Inverter in a sheltered place or a place with an awning.
Mounting requirements
The mounting structure where the Hybrid Inverter is installed must be fireproof.
Do not install the Hybrid Inverter on flammable building materials.
The Hybrid Inverter is heavy. Ensure that the installation surface is solid enough to bear the weight load.
In residential areas, do not install the Hybrid Inverter on drywalls or walls made of similar materials which have a weak sound insulation performance because the noise generated by the Hybrid Inverter is noticeable.
What are the angle and space requirements for mounting the inverter?
Angle Requirements
Install the inverter vertically with a backward tilt of less than 15 degrees. Never install the inverter horizontally, or at forward tilted, side tilted, or upside down.
Space Requirements
Reserve enough space around the inverter to ensure sufficient space for installation and heat dissipation.
Clearance above: ≥ 300mm
Clearance below: ≥ 500mm
Clearance on sides: ≥ 200mm
How do I install the inverter?
ATTENTION: Mechanical damage
In order to prevent injuries and damage to the device, ensure that the inverter is kept balanced while it is being moved – it is very heavy.
Do not place the inverter on its connections, as these are not designed to bear its weight. Place the inverter horizontally on the ground.
When you place the inverter on the ground, place foamed material or paper underneath it in order to protect its housing.
Step 1: Placing the wall-mounting bracket to a proper position on the wall. Use a spirit level to ensure the bubble is in the middle position. Mark the positions by marker and drill four holes (Ø8, Depth 45-50mm).
Step 2: Placing and fixing the expansion Bolts in the holes, and installing the mounting bracket. Tighten the nuts to 5±0.2Nm.
Step 3: Lift the inverter and slide it down along the wall mounting bracket to make sure they match perfectly. Use two screw sets (M4*10) to lock both left and right sides. Tighten the screws to 1.2±0.2Nm.
What are the recommended PV module and DVC specifications?
The connected PV modules must be compliant with IEC 61730 class A.
Recommended backup loads
| Device | Isc PV (absolute maximum) | Maximum output overvoltage protection |
|---|---|---|
| Hybrid Inverter | 20A/20A | 600V |
Description of limits for DVC (decisive voltage classification)
Note: The values in brackets apply when the inverter is installed in a humid environment.
| DVC | AC voltage (RMS) | AC voltage (PK) | DC voltage (AVG) |
|---|---|---|---|
| A | 25(16) | 35.4(22.6) | 60(35) |
| B | 50(33) | 71(46.7) | 120(70) |
| C | 1000 | 4500 | 1500 |
What are the electrical terminals on the bottom of the inverter?
| No. | Name | Description | DVC |
|---|---|---|---|
| 1 | PV input terminal (PV1+/PV1-) | MC4 terminals for PV 1 input. | DVCC |
| 2 | PV input terminal (PV2+/PV2-) | MC4 terminals for PV 2 input. | DVCC |
| 3 | BAT input terminal (BAT+/BAT-) | Connectors for the battery power cables. | DVCC |
| 4 | Communications port(BMS) | Communication connection for Battery BMS. | DVCA |
| 5 | Communications port(RJ45) | Communication port Reserved. | DVCA |
| 6 | Wireless button | Used to enable WiFi distribution network mode or OTA. | / |
| 7 | Communications port(COM) | Communication connection for smart energy meter, DI/DO RSD .etc. | DVCA |
| 8 | AC-Backup output port | AC terminal for Backup loads. | DVCC |
| 9 | AC-Grid output port | AC terminal to connect to the grid. | DVCC |
| 10 | Ventilation valve | / | / |
| 11 | Wireless Communications | Communication accessory port to be connected to WiNet-S communication module. | DVCA |
What are the installation requirements for the electrical components in the system?
The values in the table are recommended values and can be set to other values according to actual conditions.
| Item number in diagram | Requirement |
|---|---|
| 1 | Depends on household loads and inverter capacity |
| 2 | Depends on loads |
| 3 | <63A/230V/400V AC breaker |
| 4 | 32A/230V/400V AC breaker |
| 5 | 30mA RCD |
| 6 | 300mA RCD |
| 7 | 30mA RCD |
What are the cable requirements for the installation?
| NO. | Cable | Type | Cable Diameter | Cross-section |
|---|---|---|---|---|
| 1 | PV cable | Complying with 600V and 16A standard | 6-9mm | 4-6 mm² |
| 2 | AC-Backup cable | Outdoor 3-core copper wire cable | 10-21mm | 4-6 mm² |
| 3 | AC-Grid cable | Outdoor 3-core copper wire cable | 12-25.8mm | 6-16 mm² |
| 4 | BAT Power cable | Complying with 600V and 35A standard | 5.5-8mm | 6 mm² |
| 5 | Communication cable | CAT 5E outdoor shielded network cable | 4.8-6mm | 0.08-0.2 mm² |
| 6 | Grounding cable | Single-core copper wire cable | The same as PE wire in AC cable | |
ATTENTIONS:
If local standard have other requirements for cables, set the cable specification according to the local standard.
The factors that affect cable selection include rated current, cable type, routing mode, ambient temperature, and maximum expected line loss.
The cabling distance between the battery and the inverter should be less than 10m, and within 5m is recommended.
How do I connect the ground cable to the inverter?
Connect the inverter to the equipotential bonding bar by using the protective earth cable (PE) for grounding.
ATTENTION: Pole Grounding not permissible!
As the inverter is transformerless, the plus and minus poles of the PV generator must NOT be earthed. Otherwise, the inverter will malfunction.
Procedure:
1. Strip 6 mm of insulation from the 4 mm² ground cable. The exposed wire length should be 8-10 mm.
2. Insert the stripped end into a ring terminal and cover the connection with heat-shrink tubing.
3. Use a crimping tool to secure the ring terminal to the cable.
4. Locate the grounding terminal on the side of the inverter. Attach the ring terminal using the M4 screw and tighten to 1.2±0.2Nm.
How do I install the AC output connector?
The blue connector is for grid, and the black connector is for backup. Installation and line connection is the same. The AC disconnecting device must be easily accessible, and each inverter must have its own circuit breaker.
1. Prepare the AC cable by stripping the outer jacket to about 30-50mm.
2. Feed the cable through the AC connector components (cable gland, seal, housing).
3. Strip the individual conductors (L, N, PE) and connect them to the correct terminals inside the connector housing. Tighten the terminal screws to 1.2±0.2Nm.
| Connection | Cable |
|---|---|
| L | Phase 1 (brown) |
| N | Neutral conductor (blue) |
| PE | Grounding cable (yellow-green) |
4. Assemble the connector housing and screw the cable gland tight. Then, connect the AC connector to the corresponding AC port on the inverter by turning it clockwise until it clicks into place.
To connect the black backup connector, plug it into the AC BACKUP port until it clicks.
To connect the blue grid connector, plug it into the AC GRID port until it clicks.
To remove the AC connector, turn it anticlockwise.
How do I install the DC (PV and Battery) connectors?
NOTE: The connection steps for the battery and PV are the same, only the terminal specifications are different. The battery terminal is blue, and the PV terminal is black.
Installing the PV/Battery Connectors (on the cable):
1. Strip 7 mm of insulation from the 4 mm² DC cable.
2. Insert the stripped wire into the metal pin of the DC connector.
3. Use a crimping tool to secure the pin to the wire.
4. Insert the crimped pin into the connector housing (positive or negative) until it clicks.
5. Screw the end cap onto the connector housing.
6. Use an MC4 wrench to tighten the end cap securely.
Installing PV Connector to Inverter:
Step 1: Rotate the DC switch on the inverter to the “OFF” position.
Step 2: Check the cable connection of the PV string for polarity correctness and ensure the open circuit voltage in any case does not exceed the inverter input limit of 600V.
Step 3: Connect the PV connectors to the corresponding PV1 or PV2 terminals (positive to positive, negative to negative) until there is an audible click.
Installing Battery Connector to Inverter:
Connect the battery connectors to the corresponding BAT terminals (positive to positive, negative to negative) until there is an audible click.
NOTE: Insert the protective caps into the unused DC connections.
CAUTION: Danger of DC arcing
Before removing the plus and minus connector, ensure that the DC switch has been set to OFF.
How do I make the BMS RJ45 connection?
The Enable cable along with the RJ45 cable are used for communication between the inverter and the Li-ion battery.
Step 1 (optional, if not using a pre-made cable):
Thread the communication cable (Ø4.8-6mm) through the waterproof component (nut, seal, housing). Strip the insulation layer of the cable with an Ethernet wire stripper. Insert the stripped communication cable into the RJ45 plug in the correct order, and crimp it with a crimper. Before installing the connector, tighten the waterproof cover.
Step 2:
Find the BMS terminal under the inverter. Insert the cable terminal into the BMS terminal, after confirming the RJ45 plug is inserted correctly, and then tighten the waterproof Screw cap.
How do I connect the Smart Meter?
The Current Transformer (CT) is usually installed on the L wire between the house loads and the power grid.
CT Parameters
| Voltage | AC 230 V |
| Current | 100A/100mA |
| Frequency | 50/60 Hz |
| Pulse | 1000 Imp / kWh |
Communication Terminal Definition
| Inverter Multi-com P1 | Function | Meter Pin | Communication Cable |
|---|---|---|---|
| RJ45 Pin 1 | RS485+ (A2) | Pin 10 | Red line |
| RJ45 Pin 2 | RS485- (B2) | Pin 9 | Black line |
Smart meter with CT connection
Follow the electrical diagram to connect the smart meter and CT. The meter can be installed in the AC combiner box or other places that are unable to be touched by children.
Meter Terminals Definition
| NO. | Definition | Function |
|---|---|---|
| 1 | L-S1 | To detect the CT current and direction |
| 2 | L-S2 | |
| 3 | N | Power supplied from grid |
| 4 | L | |
| 5, 6, 7 | / | |
| 8 | GND | Ground connection |
| 9 | B- | Communicate with hybrid inverter |
| 10 | A+ |
The energy meter is preconfigured. To change or check settings, use the buttons on the meter. A long-press enters setting mode, and a tap cycles through options. The sequence is: Set ID -> Set Baud rate -> Set primary current.
How do I connect the Wireless Module?
Procedure:
1. Remove the protective cap from the USB interface.
2. Install the Wireless stick.
3. Tighten the connecting nut.
What are the definitions for the communication ports?
Communication Port Definition (Multi-COM)
| PIN | Definition | Function |
|---|---|---|
| P1 RJ45 | RS485+(A2)/RS485-(B2) | Communicate with smart meters |
| P2 RJ45 | RS485+(A2)/RS485-(B2) | Communicate with heat pump |
| 1, 2 | DO1+, DO1- | Dry contacts of load control |
| 3, 4, 5 | DO2, DO3, DO_COM | |
| 6, 7, 8, 9 | DRM1/5, DRM2/6, DRM3/7, DRM4/8 | Demand response modes (DRED/RCR) |
| 10 | COM | 12V power supply |
| 11 | COM_LOAD/0 | Demand response modes |
| 12 | ES | For WSD(wired shut down)/NS protection |
| 13 | Grid on | For grid operator |
| 14 | COM | 12V power supply |
| 15, 16 | RS485B1, RS485A1 | Communicate with inverter |
| 17, 18 | RS485B1, RS485A1 | |
| 19, 20 | RS485B3, RS485A3 | Communicate with upper computer |
| 21, 22 | / | Reserved |
RJ45 Terminal Definition
| No. | Color | P1 RJ45(Smart meters) | P2 RJ45(Heat pump) |
|---|---|---|---|
| 1 | White with orange stripes | RS485+(A2) | RS485+(A2) |
| 2 | Orange | RS485-(B2) | RS485-(B2) |
| 3 | White with green stripes | NC | NC |
| 4 | Blue | NC | NC |
| 5 | White with blue stripes | NC | NC |
| 6 | Green | NC | NC |
| 7 | White with brown stripes | NC | NC |
| 8 | Brown | NC | NC |
How do I install the Multi-COM connector?
Installing the cable and Multi-com
1. Prepare the wires by stripping about 12mm of insulation.
2. Disassemble the Multi-COM connector into its parts: nut, sealing screen, sealing ring, body, and housing.
3. Thread the prepared cables through the nut, sealing screen, and housing.
4. Insert the terminals into the body according to the pin definition table. Push until they click into place.
5. Assemble the body and housing, then push the entire assembly together until it clicks.
Installing the Multi-COM to inverter
Align the assembled Multi-COM connector with the COM port on the inverter and push it in until it clicks. Then screw the outer ring tight to secure it.
What checks should be performed before powering on the system?
| No. | Item | Acceptance Criterion |
|---|---|---|
| 1 | Inverter installation | The Inverter is installed correctly and securely. |
| 2 | Battery installation (optional) | The Energy Storage Unit is installed correctly and securely. |
| 3 | Wireless module | The Wireless module is installed correctly and securely. |
| 4 | Cable routing | The cables are routed properly as required by the customer. |
| 5 | Cable ties | Cable ties are secured evenly and no burr exists. |
| 6 | Reliable grounding | The PE cable is connected correctly and securely. |
| 7 | Switch | DC switches and all the switches connecting to the Inverter are OFF. |
| 8 | Cable connection | The AC output power cable, DC input power cables, battery cable, and signal cable are connected correctly and securely |
| 9 | Unused terminals and ports | Unused terminals and ports are locked by watertight caps. |
| 10 | Installation environment | The installation space is proper, and the installation environment is clean and tidy. |
How do I power on the system?
1. If a battery is connected, turn on the battery switch.
2. Turn on the AC switch between the inverter and the power grid.
3. Turn on the DC switch (if any) between the PV string and the inverter.
4. Turn on the DC switch at the bottom of the inverter.
5. Wait for about 1 minute and observe the LED indicators on the inverter to check its running status.
How do I power off the system for maintenance?
If the inverter needs to be shut down for electrical inspection, please follow the following steps:
1. Turn off the AC switch between the inverter and the power grid.
2. Turn off the DC switch at the bottom of the inverter.
3. If there is a DC switch between the inverter and PV string, turn off the DC switch.
4. Turn off the DC switch at the battery(Optional).
5. Wait for 5 minutes before checking the inverter.
What is the routine maintenance for the inverter?
Inverters do not generally require daily or routine maintenance. Before carrying out cleaning, ensure that the DC switch and AC circuit breaker between the inverter and power grid have been switched off. Wait at least 5 minutes before carrying out cleaning.
Cleaning the inverter
Clean the inverter using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, cleaning agents etc.
Cleaning the heat sink
In order to help guarantee correct long-term operation of the inverter, make sure that there is sufficient space for ventilation around the heat sink. Check the heat sink for blockages (dust, snow etc.) and remove them if present. Please clean the heat sink using an air blower and a dry, soft cloth or a soft bristle brush. Do not clean the heat sink with water, corrosive chemicals, cleaning agents etc.
How do I troubleshoot the inverter?
First, check the warnings, error messages or error codes displayed on the screen of the app.
If no error information is displayed on the screen, check whether the following requirements have been fulfilled:
Has the inverter been set up in a clean, dry, well-ventilated area?
Is the DC switch set to ON?
Are the cables sufficiently dimensioned and short enough?
Are the input connections, output connections and the wiring all in good condition?
Are the configuration settings for the relevant installation correct?
Are the the communication cables correctly connected and undamaged?
What are the common alarm codes, their causes, and troubleshooting steps?
| Alarm ID | Alarm Name | Possible Cause | Trouble shooting |
|---|---|---|---|
| 1001 | String reverse connection | The PV string polarity is reversed. | Check whether the PV string is reversely connected to the inverter. If so, wait until the PV string current decreases to below 0.5 A. Then, turn off the DC switch and correct the PV string polarity. |
| 1002 | Abnormal residual current | The input-to-ground insulation impedance has decreased during the inverter operation. | 1. If the alarm occurs accidentally, the external power cable may be abnormal temporarily. The inverter automatically recovers after the fault is rectified. 2. If the alarm persists or lasts a long time, check whether the impedance between the PV string and ground is too low. |
| 1003 | Low insulation resistance | 1. A short circuit exists between the PV array and the ground. 2. The PV array is in a moist environment and the circuit is not well. |
1. Check the impedance between the PV array output and the ground. If a short circuit occurs or the insulation is insufficient, rectify the fault. 2. Check whether the PE cable of the inverter is correctly connected. 3. If you have confirmed that the impedance is lower than the specified protection threshold in a cloudy or rainy environment, log in to the app to set the Insulation resistance protection threshold. |
| 1004 | Cabinet over temperature | 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds the upper threshold. 3. The inverter is not operating properly. |
1. Check the ventilation and ambient temperature at the inverter installation position. 2. If the ventilation is poor or the ambient temperature exceeds the upper threshold, improve the ventilation and heat dissipation. 3. If the ventilation and ambient temperature are normal, contact your dealer or technical support. |
| 1005 | Grid loss | 1. Power grid outage occurs. 2. The AC circuit is disconnected or the AC switch is off. |
1. The alarm is cleared automatically after the power grid recovers. 2. Check whether the AC circuit is disconnected or the AC switch is off. |
| 1006 | Power Module Communication failure | The battery communication is abnormal | Check that the communications cable is correctly installed, and that the communication parameters are the same as the inverter RS485 configurations. |
| 1007 | BMS Communication failure | The battery communication is abnormal | Check that the communications cable is correctly installed, and that the communications parameters are the same as the inverter RS485 configurations. |
| 1008 | Meter Communication failure | The meter communication is abnormal | Check that the communications cable is correctly installed, and that the communication parameters are the same as the inverter RS485 configurations. |
| 1009 | Equipment fault | An unrecoverable fault occurs on a circuit inside the inverter. | Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the alarm persists, contact your dealer or technical support. |
| 1010 | Grid overvoltage | The grid voltage exceeds the upper threshold or the high voltage duration has lasted for more than the value specified by high voltage ride-through (HVRT). | 1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers. 2. If the alarm persists, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. If yes, modify the grid overvoltage protection threshold. 3. Check whether the peak voltage of the power grid is too high. If the alarm persists, contact the power operator. |
| 1011 | Grid undervoltage | The grid voltage is below the lower threshold or the low-voltage duration has lasted for more than the value specified by low voltage ride-through (LVRT). | 1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers. 2. If the alarm persists, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. If yes, modify the grid undervoltage protection threshold. 3. Check whether the peak voltage of the power grid is too low. If the alarm persists, contact the power operator. |
| 1012 | Grid over frequency | Power grid exception: The actual power grid frequency is higher than the requirements for the local power grid code. | 1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers. 2. If the alarm persists, check the power grid frequency. If it is out of range, contact the local power operator. 3. If the alarm persists, contact the power operator. |
| 1013 | Grid under frequency | Power grid exception: The actual power grid frequency is lower than the requirements for the local power grid code. | 1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers. 2. If the alarm persists, check the power grid frequency. If it is out of range, contact the local power operator. 3. If the alarm persists, contact the power operator. |
| 1014 | AC-grid output overcurrent | The power grid voltage drops dramatically or the power grid is short circuited. As a result, the inverter transient output current exceeds the upper threshold, and protection is triggered. | 1. The inverter monitors its external operating conditions in real time and automatically recovers after the fault is rectified. 2. If the alarm persists and affects the energy yield, check whether the output is short circuited. If the fault persists, contact your dealer or technical support. |
| 1015 | AC-backup output overcurrent | The backup load power exceeds the upper threshold. | 1. Try to reduce the load power. 2. If it doesn’t work out, contact your dealer or technical support. |
| 2001 | Power module over temperature | 1. The installation position of the battery power control module is not well ventilated. 2. The ambient temperature is excessively high. 3. The battery power control module is abnormal. |
1. Check the ventilation and whether the ambient temperature of the power control module exceeds the upper threshold. 2. If the ventilation is poor or the ambient temperature is excessively high, improve the ventilation and heat dissipation. 3. If the ventilation and ambient temperature are normal, contact your dealer or technical support. |
| 2002 | Low battery DC input bus voltage | 1. The DC bus voltage of the battery is low. 2. The battery DC switch is OFF. 3. The battery cables are not correctly connected. |
If the alarm persists, check battery connections and ensure the battery DC switch is ON. If the issue continues, contact the power operator or technical support. |
| 2003 | Battery expansion module undervoltage | The voltage of a battery expansion module is low. | If the sunlight is sufficient or AC reverse charging is allowed, the battery expansion modules can be charged when the inverter is running. |
| 2004 | Power module reversely connected | The positive and negative terminals are reversely connected when the power module connects to the inverter. | 1. Turn off all switches and wait 5 minutes. 2. Check cable connections to the power control module. 3. After checking, turn on switches in sequence (battery DC, AC output, inverter DC). 4. If alarm persists, contact technical support. |
| 2005 | Abnormal BMS communication | The power module fails to communicate with the battery expansion modules. | 1. Turn off the battery DC switch. 2. Check power and communication cables to battery modules. 3. After checking, turn on the battery DC switch. 4. If alarm persists, contact technical support. |
| 2006 | Equipment fault | An unrecoverable fault occurs on a circuit inside the device. | Turn off the DC switch, and then turn them on after 5 minutes. If the alarm persists, contact your dealer or technical support. |
| 2007 | Black start-up failed | 1. The battery level is less than 10%. 2. The energy storage DC switch is not turned on. |
1. Turn off the PV switch and AC output switch, and wait for 1 minute for the device to turn off all LED lights. 2, turn on the PV switch and AC output switch, and start black again. |
| 2008 | Battery reversal connection | Battery reversal connection | Check whether the battery is reversely connected to the power module. If so, turn off the DC switch and correct the battery polarity. |
| 3001 | Battery Pack Undervoltage | 1. The voltage of the battery pack or its cell is too low. 2. The battery pack has been stored for a long period of time. 3. The battery pack has been idle for a long time after grid connection. |
1. Connect to the power grid and charge batteries in a timely manner. 2. If the alarm persists after the battery has been charged for one hour, contact your dealer or technical support. |
| 3002 | Battery module over temperature | 1. The battery installation position is not well ventilated. 2. The ambient temperature is excessively high. 3. The battery power control module is abnormal. |
1. Check the ventilation and whether the ambient temperature of the battery expansion modules exceeds the upper threshold. 2. If the ventilation is poor or the ambient temperature is excessively high, improve the ventilation and heat dissipation. 3. If the ventilation and ambient temperature are normal, contact your dealer or technical support. |
| 3003 | Battery module low temperature | 1. The ambient temperature is excessively low. 2. A battery expansion module is abnormal. |
1. Check whether the ambient temperature in the installation positions of the battery expansion modules is lower than the lower threshold. 2. If the ambient temperature is excessively low, improve the installation environment. 3. If the alarm persists after the ambient temperature becomes normal, contact your dealer or technical support. |
How do I remove, pack, and dispose of the inverter?
Removing the inverter
Before removing the inverter, power off the AC and DC (batteries).
1. Disconnect all cables from the inverter, including RS485 communications cables, DC input power cables, AC output power cables, and PGND cables.
2. Remove the inverter from the mounting bracket.
3. Remove the mounting bracket.
Packing the inverter
If the original packing materials are available, put the inverter inside them and then seal them by using adhesive tape.
If the original packing materials are not available, put the inverter inside a suitable cardboard box and seal it properly.
Disposing of the inverter
If the inverter service life expires, dispose of it according to the local disposal rules for electrical equipment waste. This product complies with EU WEEE Directive and bears a classification symbol for waster electrical and electronic equipment (WEEE). This symbol indicates that this product shall not be disposed with other household wastes at the end of its service life. Used device must be returned to official collection point for recycling of electrical electronic devices.
What are the technical specifications for the M1-S(3-6)K series inverters?
| Specification | M1-S3K | M1-S3.68K | M1-S4K | M1-S4.6K | M1-S5K | M1-S6K |
|---|---|---|---|---|---|---|
| DC Input (PV) | ||||||
| Max. PV array power (Wp) | 6000 | 7400 | 8000 | 9200 | 10000 | 12000 |
| Max. PV input power (Wp) | 4500 | 5500 | 6000 | 6900 | 7500 | 10000 |
| Max. input voltage (V) | 600 | |||||
| MPPT operating voltage range (V) | 60~550 | |||||
| Start-up voltage (V) | 75 | |||||
| Rated input voltage (V) | 360 | |||||
| Max. input current (input PV1 /input PV2) | 16/16 | |||||
| Max. short-circuit current | 20/20 | |||||
| No. of MPP trackers / Strings per MPP tracker | 2 | |||||
| Battery connection | ||||||
| Battery type | Li-ion | |||||
| Voltage range (V) | 85-460 | |||||
| Max. charge current (A) | 30 | |||||
| Max. discharging current (A) | 30 | |||||
| Max. charge power (W) | 4500 | 5500 | 6000 | 6000 | 6000 | 6000 |
| max. discharge power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| AC Output Data (on-grid) | ||||||
| Nominal AC output power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| Max. AC output apparent power (VA) | 3300 | 3680 | 4400 | 5000 | 5500 | 6000 |
| Nominal Output Current(A) | 13.0 | 16.0 | 17.4 | 20.0 | 21.7 | 26.1 |
| Max. AC output current (A) | 15.0 | 16.0 | 20.0 | 23.0 | 25.0 | 27.3 |
| Max. AC input apparent power (VA) | 6300 | 7360 | 8400 | 9600 | 10000 | 10000 |
| Max. AC input current (VA) | 27.4 | 32.0 | 36.5 | 41.7 | 43.5 | 43.5 |
| Nominal AC voltage (V) | 220Vac/230Vac/ 240Vac,L/N/PE | |||||
| Nominal AC Grid Frequency (Hz) | 50/60 | |||||
| Adjustable power factor | 0.8 leading … 0.8 lagging | |||||
| Max. total harmonic distortion | ≤3% | |||||
| AC Output Data (back-up) | ||||||
| Nominal output power (W) | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
| Max. continuous current (A) | 13.0 | 16.0 | 17.4 | 20.0 | 21.7 | 26.1 |
| Nominal voltage (V) | 230Vac,L/N/PE | |||||
| Frequency (Hz) | 50/60 | |||||
| General Data | ||||||
| Operating temperature range (°C) | -25°C to + 60°C(Derating above 45°C @ Rated output power) | |||||
| Weight (kg) | 24.5 | |||||
| Max. operating altitude (m) | 4000 | |||||
| Dimension(W/H/D) (mm) | 485/450/187 | |||||
| Degree of protection | IP66 | |||||
CLICK HERE TO DOWNLOAD MIDEA M1-S3K (01) PDF MANUAL
