MIDEA M1-S4.6K (01) Image

FREE ENGLISH MIDEA M1-S4.6K (01) PDF USER GUIDE
FREE ENGLISH MIDEA M1-S4.6K (01) PDF USER MANUAL
FREE ENGLISH MIDEA M1-S4.6K (01) PDF OWNER GUIDE
FREE ENGLISH MIDEA M1-S4.6K (01) PDF OWNER MANUAL
FREE ENGLISH MIDEA M1-S4.6K (01) PDF REFERENCE GUIDE
FREE ENGLISH MIDEA M1-S4.6K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH MIDEA M1-S4.6K (01) PDF REFERENCE MANUAL
FREE ENGLISH MIDEA M1-S4.6K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH MIDEA M1-S4.6K (01) PDF OPERATING INSTRUCTIONS


CLICK HERE TO DOWNLOAD MIDEA M1-S4.6K (01) PDF MANUAL

If this is not the document you want for this product, click here to see if we have any other documents for this product.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What do the safety symbols in the user manual mean?

The manual uses symbols to ensure the safety of persons and property, as well as the efficient operation of the inverter. Please read the symbol explanations carefully to prevent injury or property damage.

  • DANGER: Non-observance will result in death or serious injury. Follow the warnings to prevent death or serious injury.
  • WARNING: Non-observance will result in death or serious injury. Follow the warnings to prevent serious injury.
  • CAUTION: Non-observance may result in minor injury. Follow the warnings to prevent injury.
  • ATTENTION: Non-observance may result in property damage. Follow the warnings to prevent damage to or destruction of the product.
  • NOTE: Provides tips essential to the optimal operation of the product.

Who is qualified to install and operate the hybrid inverter?

This manual is intended for specialist electrical engineers responsible for installation and commissioning, as well as PV Storage system operators. For safety reasons, the inverter may only be installed by a qualified electrician who:

  • has received training on occupational safety, as well as the installation and commissioning of electrical systems.
  • is familiar with the local laws, standards and regulations of the grid operator.

The manufacturer assumes no responsibility for the destruction of property or any injuries to personnel caused by improper usage.


What are the general safety precautions for installation and operation?

Installation:

  • Read and understand all instructions and safety symbols in the manual before beginning installation.
  • Obtain official authorization from the local power grid operator before connecting to the power grid.
  • Before installing or performing maintenance, open the DC switch to interrupt the DC voltage of the PV generator. Not doing this may result in serious injury.
  • Install the inverter on a suitable, upright surface with sufficient load-bearing capacity (e.g., walls, PV frames).
  • Ensure sufficient space for maintenance and sufficient ventilation for cooling.

Electrical Connection:

  • Before establishing the electrical connection, cover the PV modules with opaque material or disconnect the PV generator. Solar radiation generates dangerous voltage.
  • All installations and electrical connections must be carried out by trained electricians.
  • Wait a minimum of 5 minutes after switching off the AC circuit breaker and the DC switch before starting any maintenance or repair work, to allow capacitors to discharge.

Operation:

  • During operation, some internal components and the housing can become very hot. Wear protective gloves and keep children away.
  • Do not open the inverter or remove any labels.

Repair and Maintenance:

  • If any maintenance or repairs are required, contact the nearest authorized service center. Do NOT carry out repairs yourself.
  • The internal components of the inverter must NOT be opened without relevant authorization.

What do the symbols on the inverter itself mean?

Symbol Description
Symbol showing a clock with “5min” inside a warning triangle. Residual voltage is present in the inverter! Before opening the inverter, you should wait five minutes to ensure that the capacitor has been fully discharged.
Lightning bolt inside a warning triangle. Caution! Danger through electric shock.
Three wavy vertical lines (heat symbol) inside a warning triangle. Caution! Hot surface.
Exclamation mark inside a warning triangle. Disconnect the inverter from all the external power sources before maintenance!
CE Mark The product is compliant with EU guidelines.
Crossed-out wheelie bin. Do not dispose of the inverter together with household waste.
Open book with an ‘i’ symbol. Please read the manual before installing the inverter.
Grounding symbol. Grounding point.
“Do not disconnect under load!” text with a warning triangle. Do not remove the DC input connector or AC output connector when the inverter is running.

What are the main components on the outside of the inverter?

NO. Name Description
1 Hanger Plate To hang the inverter on the wall-mounting bracket.
2 LED Indicator Label To explain the current working state of the inverter.
3 DC Switch To safely disconnect the DC circuit whenever necessary.
4 Indicator To indicate the current working state of the inverter.
5 Nameplate To identify the product, including device model, S/N, important specifications, etc.
6 Grounding terminal To connect system to earth.
7 Electrical connection area PV terminals, battery terminal, AC terminal, additional grounding terminal and communication terminals.

How do I interpret the LED indicators on the inverter?

INDICATOR COLOR STATUS EXPLANATION
DC Green Steady on PV power available
Yellow Steady on PV power not available/ too low
Red Steady on Fault
Off System is power-off
AC Green Steady on Inverter is operating
Green Blinking at long intervals (on for 1s and then off for 1s) Inverter in standby in grid-tied mode
Yellow Steady on Inverter is operating in off-grid mode
Yellow Blinking at long intervals (on for 1s and then off for 1s) Inverter in standby in off-grid mode
Red Steady on Fault
Off System is power-off
COM Green Blinking at long intervals (on for 0.2s and then off for 0.2s) Wireless waiting for connection
Green Blinking at long intervals (on for 1s and then off for 1s) Establishing wireless connection
Green Steady on Wireless connected
Yellow Steady on Bluetooth connected
Off No wireless/bluetooth connected

What are the different working modes of the hybrid inverter?

Working mode Description
Standby The Hybrid Inverter enters Standby mode when the external environment does not meet operating requirements. It continuously performs status checks and enters Operating mode once requirements are met. It enters Shutdown mode if it detects a command or a fault.
Operating In this mode, the inverter converts DC power from PV strings into AC power and feeds it to the grid. It tracks the maximum power point to maximize PV output. If a fault or shutdown command is detected, it enters Shutdown mode. It enters Standby mode if PV output is not suitable for grid connection.
Shutdown In Standby or Operating mode, the inverter enters Shutdown mode after detecting a fault or shutdown command. From Shutdown mode, it can enter Standby mode after a startup command or once a fault is rectified.

What are the limitations and declarations for the back-up function?

  • If there is no available power from batteries or PV modules in backup mode, the backup power supply will be automatically terminated.
  • The Back-Up switching time is normally less than 3 seconds, but external factors can cause failure.
  • Do not connect loads that are dependent on a stable energy supply for a reliable operation.
  • Do not connect loads whose total capacity is greater than the maximum Back-Up capacity.
  • Do not connect loads that may cause very high start-up current surges (e.g., nonfrequency conversion air conditioning, vacuum cleaner, hair dryer, hammer drill).
  • Battery current may be limited by factors like temperature and weather.
  • BACK-UP is not recommended if the PV system is not configured with batteries.
  • If a single overload protection occurs, the inverter can restart automatically. If it happens several times, the restarting time will be extended.
  • If the load capacity exceeds the inverter’s rated power when the grid is disconnected, the off-grid function will close automatically. To enable it, turn off the large loads.

Declaration for Back-Up Overload Protection:

The inverter will restart in case of overload protection. The time required for restarting will increase (5 min at most) if overload protection repeats. Try to reduce Back-Up load power within maximum limitation or remove loads which may cause very high start-up current surges.


What types of loads are recommended for the back-up function in an off-grid scenario?

The following table provides information on recommended backup loads and their power consumption. This data is based on tests with batteries at -20 ~ 55 °C, 5-100% SOC. For actual applications, refer to the maximum output capacity of the battery used.

Type Load Power
Dust collector 1.3kW
Water heater/Kettle /Iron /Oven /Toaster /Geothermal blanket / Rice cooker 3 kW
Microwave oven 1.5kW
Refrigerator 1kW
TV / Computer 1kW
Bath heater 2.5kW
Fluorescent / LED lights 1.3kW
Electric fan / Ceiling fan 2kW
Conditioner (frequency conversion modulation) 1.5P

What are the different working modes for the PV Energy Storage System?

  • Mode 1: Maximize Self-consumption: Suitable for areas with high electricity tariffs. Priority is given to the local load, then to battery storage, and finally to selling to the grid. When PV power is insufficient, the battery discharges to the local load, and if needed, power is purchased from the grid.
  • Mode 2: Maximize Feed-in: Suitable for areas with high feed-in tariffs. When PV power is greater than inverter capacity, excess electricity is stored in the battery. When PV power is less than inverter capacity, the electricity is sold to the grid.
  • Mode 3: Backup power: Suitable for areas with frequent grid outages. A reserved Backup SOC (State of Charge) is set. The battery can only be charged until it reaches this reserved value. Above this value, the battery behaves as in Self-use mode.
  • Mode 4: Charge and discharge schedule: Suitable for areas with peak and valley electricity prices. You can set specific periods for charging and discharging the battery. For the rest of the time, it behaves as in Self-use mode.
  • Mode 5: Peak shaving: This function avoids exceeding a set peak kW limit from the grid by dynamically overriding the max kW limit on the battery.

How does the inverter manage the battery charge and discharge?

The maximum allowable charge/discharge current is limited by temperature, maximum power of the inverter, and the maximum/recommended current from the battery manufacturer. The inverter manages the battery based on its State of Charge (SoC) and whether it’s grid-connected or off-grid.

Range Battery management behavior
A In this range (SoC 0 to ~15%), the battery is no longer discharged, even in battery-backup operation. SoCL can be set from 0 to 15% in the APP.
B When operating off-grid, the system reports a low SoC state.
C When starting up in off-grid condition, the system does not output AC power, so as to charge the battery by all PV power.
D When operating grid-connected, the system charges/discharges the battery for PV power economy. SoCback can be set from 20 to 90% in the APP.
E When operating grid-connected, the system charges/discharges the battery for PV power economy.
F When operating off-grid, the system charges/discharges the battery to support the system and obtain PV power economy.
G In this range (SoC ~90% to 100%), the battery can be discharged to support the system or for PV power economy, but it cannot be charged. SoCH can be set from 90 to 100% in the APP.

What should I do after unpacking the inverter?

The product is thoroughly tested before delivery, but damage may occur during shipping. Please conduct a thorough inspection after receiving the product:

  • Check the packing case for any visible damage.
  • Check the scope of delivery for completeness according to the packing list.
  • Check the inner contents for damage after unpacking.

If there is any damage or incompleteness, contact the after-sales service provider or transport company and provide photos. It is recommended to store the device in the original packing case for when the product is decommissioned.


How should I store the inverter if it’s not being installed immediately?

  • Do not unpack the inverter.
  • Keep the storage temperature at -40°C to +70°C and the humidity at 5%- 95% RH.
  • Store the inverter in a clean, dry place, protected from dust and water vapor corrosion.
  • A maximum of 6 units can be stacked. Stack with caution to prevent them from falling over.
  • Periodic inspections are required during storage. Replace packing materials if necessary.
  • If stored long-term, inspections and tests should be conducted by qualified personnel before use.

What tools are needed for installation?

No. Tool Function
01 Hammer drill (Recommended drill diameter: 8mm) Used to drill holes in the wall
02 Screwdriver Wiring
03 Phillips screwdriver Used to remove and install the screws of the AC terminal
04 Removal tool Used to remove the PV battery terminal
05 Wire stripper Used to strip the wire
06 6mm Allen key Used to turn the screw to connect the rear panel to the inverter
07 Crimping tool Used to crimp power cables
08 Multimeter Used to check the Grounding
09 Marker Used for marking
10 Measuring tape Used to measure distances
11 Spirit level Used to align the wall bracket
12 ESD gloves For the installer
13 Safety goggles For the installer
14 Anti-dust respiratory mask For the installer

What are the environmental and space requirements for installing the hybrid inverter?

Basic Environmental Requirements:

  • The inverter is protected to IP65 and can be installed indoors or outdoors.
  • Do not install where personnel can easily touch its enclosure and heat sinks, as these parts get very hot.
  • Do not install in areas with flammable or explosive materials.
  • Do not install within children’s reach.
  • Do not install outdoors in salt areas (within 500 meters from the coast or prone to sea breeze) as it can cause corrosion and fire.
  • Install in a well-ventilated environment for good heat dissipation. A sheltered place or one with an awning is recommended.

Mounting Requirements:

  • The mounting structure must be fireproof. Do not install on flammable building materials.
  • The installation surface must be solid enough to bear the inverter’s weight.
  • In residential areas, do not install on drywalls or walls with weak sound insulation, as the inverter generates noticeable noise.

Angle and Space Requirements:

  • Install the inverter vertically (tilted no more than 15°). Never install it horizontally, at a forward/backward tilt, side tilted, or upside down.
  • Reserve enough space around the inverter for installation and heat dissipation:
    • ≥ 300mm above
    • ≥ 500mm below
    • ≥ 200mm on the left side
    • ≥ 200mm on the right side
    • ≥ 300mm in front

How do I install the inverter on the wall?

Step 1: Place the wall-mounting bracket in a proper position on the wall. Use a spirit level to ensure the bubble is in the middle position. Mark the hole positions with a marker and drill the holes (Ø8mm, Depth 45-50mm).

Step 2: Insert the expansion bolts into the holes and fix the mounting bracket to the wall. Tighten the bolts to 5±0.2Nm.

Step 3: Lift the inverter and slide it down along the wall mounting bracket, ensuring they match perfectly. Use two M4*10 screw sets (one on each side) to lock the inverter to the bracket. Tighten to 1.2±0.2Nm.


What are the different terminals at the bottom of the inverter?

No. Name Description
1 PV input terminal (PV1+/PV1-) MC4 terminals for PV 1 input.
2 PV input terminal (PV2+/PV2-) MC4 terminals for PV 2 input.
3 BAT input terminal (BAT+/BAT-) Connectors for the battery power cables.
4 Communications port(BMS) Communication connection for Battery BMS.
5 Communications port(RJ45) Communication port Reserved.
6 Wireless button Used to enable WiFi distribution network mode or OTA.
7 Communications port(COM) Communication connection for smart energy meter, DI/DO RSD, etc.
8 AC-Backup output port AC terminal for Backup loads.
9 AC-Grid output port AC terminal to connect to the grid.
10 Ventilation valve /
11 Wireless Communications Communication accessory port to be connected to WiNet-S communication module.

What are the cable requirements for the inverter?

NO. Cable Type Cable Diameter Cross-section
1 PV cable Complying with 600V and 16A standard 6-9mm 4-6 mm²
2 AC-Backup cable Outdoor 3-core copper wire cable 10-21mm 4-6 mm²
3 AC-Grid cable Outdoor 3-core copper wire cable 12-25.8mm 6-16 mm²
4 BAT Power cable Complying with 600V and 35A standard 5.5-8mm 6 mm²
5 Communication cable CAT 5E outdoor shielded network cable 4.8-6mm 0.08-0.2 mm²
6 Grounding cable Single-core copper wire cable The same as PE wire in AC cable

ATTENTIONS:

  • If local standards have other requirements for cables, set the cable specification according to the local standard.
  • Factors that affect cable selection include rated current, cable type, routing mode, ambient temperature, and maximum expected line loss.
  • The cabling distance between the battery and the inverter should be less than 10m, and within 5m is recommended.

How do I connect the ground cable to the inverter?

Connect the inverter to the equipotential bonding bar using the protective earth cable (PE) for grounding. The inverter is transformerless, so the plus and minus poles of the PV generator must NOT be earthed.

1. Strip 6 mm of insulation from the 4 mm² grounding cable. The stripped length should be 8-10 mm.

2. Attach a terminal lug and cover it with heat-shrink tubing.

3. Crimp the terminal onto the wire.

4. Attach the grounding cable to the grounding terminal on the inverter using an M4 screw. Tighten to 1.2±0.2Nm.


How do I connect the AC output cables?

The blue connector is for the grid, and the black connector is for backup. The installation and line connection are the same for both. Each inverter must have its own circuit breaker, and the AC disconnecting device must be easily accessible.

Cable Connection Explanation:

  • L: Phase 1 (brown)
  • N: Neutral conductor (blue)
  • PE: Grounding cable (yellow-green)

Procedure:

1. Disassemble the AC connector. Strip the wires and insert them into the correct terminals (L, N, PE). Tighten the screws to 1.2±0.2Nm.

2. Assemble the connector housing and screw the cable gland tight.

3. Connect the AC connector to the corresponding AC port on the inverter (AC GRID or AC BACKUP) by turning it clockwise until it clicks and locks into place.

To remove the AC connector, turn it anticlockwise.


How do I install and connect the PV and Battery DC cables?

The connection steps for battery and PV cables are the same, but the terminal specifications differ. The battery terminal is blue, and the PV terminal is black.

Creating the PV Connectors:

1. Strip 7 mm of insulation from the red (+) and black (-) 4 mm² PV cables.

2. Crimp the metal contacts onto the stripped ends of the wires.

3. Insert the crimped wires into the corresponding positive (red) and negative (black) connector housings until they click.

4. Tighten the screw caps onto the connector housings using an MC4 Wrench.

Installing the PV and Battery Connectors:

1. Rotate the DC switch on the inverter to the “OFF” position.

2. Check the polarity and open-circuit voltage of the PV string to ensure it does not exceed the inverter input limit of 600V.

3. Connect the PV connectors to the corresponding PV1/PV2 terminals and the Battery connectors to the BAT terminals until there is an audible click.

NOTE: Insert the protective caps into any unused DC connections. Before removing a plus and minus connector, ensure the DC switch has been set to OFF.


What should I check before powering on the system?

Before commissioning, ensure that the DC and AC voltages are within the permissible range of the inverter. Perform the following checks:

No. Item Acceptance Criterion
1 Inverter installation The Inverter is installed correctly and securely.
2 Battery installation (optional) The Energy Storage Unit is installed correctly and securely.
3 Wireless module The Wireless module is installed correctly and securely.
4 Cable routing The cables are routed properly as required by the customer.
5 Cable ties Cable ties are secured evenly and no burr exists.
6 Reliable grounding The PE cable is connected correctly and securely.
7 Switch DC switches and all the switches connecting to the Inverter are OFF.
8 Cable connection The AC output power cable, DC input power cables, battery cable, and signal cable are connected correctly and securely.
9 Unused terminals and ports Unused terminals and ports are locked by watertight caps.
10 Installation environment The installation space is proper, and the installation environment is clean and tidy.

What is the procedure for powering on the system?

1. If a battery is connected, turn on the battery switch.

2. Turn on the AC switch between the inverter and the power grid.

3. Turn on the DC switch (if any) between the PV string and the inverter.

4. Turn on the DC switch at the bottom of the inverter.

5. Wait for about 1 minute and observe the LED indicators on the inverter to check its running status.


How do I safely power-off the system for maintenance?

If the inverter needs to be shut down for electrical inspection, please follow these steps:

1. Turn off the AC switch between the inverter and the power grid.

2. Turn off the DC switch at the bottom of the inverter.

3. If there is a DC switch between the inverter and PV string, turn off the DC switch.

4. Turn off the DC switch at the battery (Optional).

5. Wait for 5 minutes before checking the inverter.


How do I perform routine maintenance and cleaning on the inverter?

Inverters do not generally require daily or routine maintenance. Before cleaning, ensure the DC switch and AC circuit breaker have been switched off. Wait at least 5 minutes before carrying out cleaning.

Cleaning the inverter:

Clean the inverter using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, or cleaning agents.

Cleaning the heat sink:

To ensure correct long-term operation, check the heat sink for blockages (dust, snow, etc.) and remove them if present. Clean the heat sink using an air blower and a dry, soft cloth or a soft bristle brush. Do not clean the heat sink with water, corrosive chemicals, or cleaning agents.


How do I troubleshoot problems with the inverter?

First, check for warnings, error messages, or error codes displayed on the screen of the app. If no error information is displayed, check if the following requirements have been fulfilled:

  • Has the inverter been set up in a clean, dry, well-ventilated area?
  • Is the DC switch set to ON?
  • Are the cables sufficiently dimensioned and short enough?
  • Are the input connections, output connections, and the wiring all in good condition?
  • Are the configuration settings for the relevant installation correct?
  • Are the communication cables correctly connected and undamaged?

Error List:

Alarm ID Alarm Name Possible Cause Troubleshooting
1001 String reverse connection The PV string polarity is reversed. Check if the PV string is reversely connected. If so, wait until the string current is below 0.5 A. Then, turn off the DC switch and correct the polarity.
1002 Abnormal residual current The input-to-ground insulation impedance has decreased. If the alarm is accidental, it may recover automatically. If it persists, check if the impedance between the PV string and ground is too low.
1003 Low insulation resistance 1. Short circuit between PV array and ground.
2. Moist environment.
1. Check impedance between PV array output and ground. Rectify any short circuit.
2. Check if the PE cable is correctly connected.
1004 Cabinet over temperature 1. Poor ventilation.
2. High ambient temperature.
3. Inverter not operating properly.
1. Check ventilation and ambient temperature.
2. Improve ventilation if needed.
3. If conditions are normal, contact your dealer.
1005 Grid loss 1. Power grid outage.
2. AC circuit is disconnected or AC switch is off.
1. Alarm clears automatically when grid recovers.
2. Check the AC circuit and switch.
1006 Power Module Communication failure The battery communication is abnormal. Check that communications cable is correctly installed and parameters match inverter settings.
1007 BMS Communication failure The battery communication is abnormal. Check that communications cable is correctly installed and parameters match inverter settings.
1008 Meter Communication failure The meter communication is abnormal. Check that communications cable is correctly installed and parameters match inverter settings.
1009 Equipment fault An unrecoverable fault has occurred inside the inverter. Turn off AC and DC switches, wait 5 minutes, then turn them back on. If alarm persists, contact your dealer.
1010 Grid overvoltage Grid voltage exceeds the upper threshold. 1. The inverter will recover automatically if the grid normalizes.
2. If it persists, check grid voltage. Contact local power operator if out of range.
1011 Grid undervoltage Grid voltage is below the lower threshold. 1. The inverter will recover automatically if the grid normalizes.
2. If it persists, check grid voltage. Contact local power operator if out of range.
1012 Grid over frequency Grid frequency is too high. The inverter will recover automatically. If persistent, contact the local power operator.
1013 Grid under frequency Grid frequency is too low. The inverter will recover automatically. If persistent, contact the local power operator.
1014 AC-grid output overcurrent Grid voltage drops dramatically or is short-circuited. The inverter monitors and recovers automatically. If persistent, check for short circuits. Contact your dealer if needed.
1015 AC-backup output overcurrent Backup load power exceeds the upper threshold. 1. Try to reduce the load power.
2. If it doesn’t work, contact your dealer.
2001 Power module over temperature 1. Poor ventilation.
2. High ambient temperature.
3. Abnormal battery module.
1. Check ventilation and ambient temperature.
2. Improve ventilation if needed.
3. If conditions are normal, contact your dealer.
2002 Low battery DC input bus voltage 1. Battery DC bus voltage is low.
2. Battery DC switch is OFF.
3. Battery cables not connected correctly.
Inverter recovers when grid normalizes. If persistent, check grid voltage and contact power operator.
2003 Battery expansion module undervoltage Voltage of a battery expansion module is low. The battery modules can be charged when the inverter is running if there is sufficient sunlight or AC reverse charging is allowed.
2004 Power module reversely connected Positive and negative terminals are reversely connected. 1. Turn off all switches, wait 5 mins.
2. Check cable connections.
3. Turn on switches in sequence.
4. If alarm persists, contact dealer.
2005 Abnormal BMS communication The power module fails to communicate with battery expansion modules. 1. Turn off battery DC switch.
2. Check power and communication cables.
3. Turn on battery DC switch.
4. If alarm persists, contact dealer.
2006 Equipment fault An unrecoverable fault occurs. Turn off DC switch, then on after 5 mins. If alarm persists, contact dealer.
2007 Black start-up failed 1. Battery level is less than 10%.
2. Energy storage DC switch is not turned on.
1. Turn off PV and AC switches, wait 1 minute.
2. Turn on PV and AC switches to start black again.
2008 Battery reversal connection Battery is reversely connected to the power module. Check if the battery is reversely connected. If so, turn off the DC switch and correct the polarity.
3001 Battery Pack Undervoltage 1. Battery pack voltage is too low.
2. Stored for a long time.
1. Connect to power grid and charge batteries.
2. If alarm persists after 1 hour of charging, contact dealer.
3002 Battery module over temperature 1. Poor ventilation.
2. High ambient temperature.
3. Abnormal module.
Check and improve ventilation and environment. If conditions are normal, contact dealer.
3003 Battery module low temperature 1. Ambient temperature is too low.
2. Abnormal module.
Check and improve installation environment temperature. If alarm persists when temp is normal, contact dealer.

How do I remove, pack, and dispose of the inverter?

Removing the inverter:

Before removing, power off the AC and DC (batteries).

1. Disconnect all cables from the inverter (RS485, DC input, AC output, PGND).

2. Remove the inverter from the mounting bracket.

3. Remove the mounting bracket from the wall.

Packing the inverter:

  • If the original packing materials are available, put the inverter inside them and seal with adhesive tape.
  • If not available, put the inverter inside a suitable cardboard box and seal it properly.

Disposing of the inverter:

If the inverter service life expires, dispose of it according to the local disposal rules for electrical equipment waste. This product complies with the WEEE Directive and should not be disposed of with other household waste.


What are the technical specifications of the M1-S(3-6)K series inverters?

Model M1-S3K M1-S3.68K M1-S4K M1-S4.6K M1-S5K M1-S6K
DC Input (PV)
Max. PV array power (Wp) 6000 7400 8000 9200 10000 12000
Max. PV input power (Wp) 4500 5500 6000 6900 7500 10000
Max. input voltage (V) 600
MPPT operating voltage range (V) 60~550
Start-up voltage (V) 75
Rated input voltage (V) 360
Max. input current (input PV1 /input PV2) 16/16
Max. short-circuit current 20/20
No. of MPP trackers / Strings per MPP tracker 2
Battery connection
Battery type Li-ion
Voltage range (V) 85-460
Max. charge current (A) 30
Max. discharging current (A) 30
Max. charge power (W) 4500 5500 6000 6000 6000 6000
max. discharge power (W) 3000 3680 4000 4600 5000 6000
AC Output Data (on-grid)
Nominal AC output power (W) 3000 3680 4000 4600 5000 6000
Max. AC output apparent power (VA) 3300 3680 4400 5000 5500 6000
Nominal Output Current(A) 13.0 16.0 17.4 20.0 21.7 26.1
Max. AC output current (A) 15.0 16.0 20.0 23.0 25.0 27.3
Max. AC input apparent power (VA) 6300 7360 8400 9600 10000 10000
Max. AC input current (VA) 27.4 32.0 36.5 41.7 43.5 43.5
Nominal AC voltage (V) 220Vac/230Vac/ 240Vac,L/N/PE
Nominal AC Grid Frequency (Hz) 50/60
Adjustable power factor 0.8 leading … 0.8 lagging
Max. total harmonic distortion ≤3%
AC Output Data (back-up)
Nominal output power (W) 3000 3680 4000 4600 5000 6000
Max. continous current (A) 13.0 16.0 17.4 20.0 21.7 26.1
Nominal voltage (V) 230Vac,L/N/PE
Frequency (Hz) 50/60
General Data
Operating temperature range (°C) -25°C to + 60°C (Derating above 45°C @ Rated output power)
Weight (kg) 24.5
Max. operating altitude (m) 4000
Dimension(W/H/D) (mm) 485/450/187
Degree of protection IP66

CLICK HERE TO DOWNLOAD MIDEA M1-S4.6K (01) PDF MANUAL


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.