MIDEA M1-S5K (01) Image

FREE ENGLISH MIDEA M1-S5K (01) PDF USER GUIDE
FREE ENGLISH MIDEA M1-S5K (01) PDF USER MANUAL
FREE ENGLISH MIDEA M1-S5K (01) PDF OWNER GUIDE
FREE ENGLISH MIDEA M1-S5K (01) PDF OWNER MANUAL
FREE ENGLISH MIDEA M1-S5K (01) PDF REFERENCE GUIDE
FREE ENGLISH MIDEA M1-S5K (01) PDF INSTRUCTION GUIDE
FREE ENGLISH MIDEA M1-S5K (01) PDF REFERENCE MANUAL
FREE ENGLISH MIDEA M1-S5K (01) PDF INSTRUCTION MANUAL
FREE ENGLISH MIDEA M1-S5K (01) PDF OPERATING INSTRUCTIONS


CLICK HERE TO DOWNLOAD MIDEA M1-S5K (01) PDF MANUAL

If this is not the document you want for this product, click here to see if we have any other documents for this product.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What are the basic safety instructions for this inverter?

Read and understand the instructions within this manual and familiarize yourself with the relevant safety symbols in this chapter before beginning with the installation of the device and eliminating any faults.

Before connecting to the power grid, you must obtain official authorization from the local power grid operator in accordance with the corresponding national and state requirements. Furthermore, operation may only be carried out by qualified electricians.

Before installing the device or carrying out maintenance on it, you must open the DC switch in order to interrupt the DC voltage of the PV generator. You can also switch off the DC voltage by opening the DC switch in the generation junction box. Not doing this may result in serious injury.

Qualified Personnel:

Personnel tasked with the operation and maintenance of the device must have the qualifications, competence and experience required to perform the described tasks, while also being capable of fully understanding all instructions contained within the manual. For safety reasons, this inverter may only be installed by a qualified electrician who:

• has received training on occupational safety, as well as the installation and commissioning of electrical systems.

• is familiar with the local laws, standards and regulations of the grid operator.

Installation Requirements:

Please install the inverter according to the information contained in the following section. Mount the inverter to a suitable object with a sufficient load-bearing capacity (e.g. walls, PV frames etc.) and ensure that the inverter is upright. Choose a suitable place for the installation of electrical devices. Ensure that there is sufficient space for an emergency exit which is suitable for maintenance. Ensure sufficient ventilation in order to guarantee an air circulation for the cooling of the inverter.

Transport Requirements:

The factory packaging is specifically designed to prevent transport damage. However, the device must not be installed if it is visibly damaged.

Labelling on the device:

The labels must NOT be concealed by items and foreign objects; they must be regularly cleaned and kept clearly visible at all times.


What safety precautions should be taken for electrical connections and operation?

Electrical Connection:

Observe all applicable electrical regulations when working with the Solar inverter.

DANGER: Dangerous DC voltage

• Before establishing the electrical connection, cover the PV modules using opaque material or disconnect the PV generator from the inverter. Solar radiation will cause dangerous voltage to be generated by the PV generator!

DANGER: Danger through electric shock!

• All installations and electrical connections may only be carried out by trained electricians!

IMPORTANT: Authorization for grid feed-in

• Obtain authorization from the local power grid operator before connecting the inverter to the public power grid.

NOTE: Voiding of guarantee

• Do not open the inverter or remove any of the labels. Otherwise, the guarantee will be voided.

Operation:

DANGER: Dangerous voltage!

• Before carrying out any repair work, first switch off the AC circuit breaker between the inverter and power grid, and then the DC switch.

• After switching off the AC circuit breaker and the DC switch, wait a minimum of 5 minutes before starting any maintenance or repair work.

Electric shock

• Contact with the electrical grid or the device’s terminals may result in an electric shock or fire!

• Do not touch the terminal or the conductor which is connected to the electrical grid.

• Follow all instructions and observe all safety documents that refer to the grid connection.

CAUTION: Burning due to hot housing

• While the inverter is being operated, several internal components will become very hot.

• Please wear protective gloves!

• Keep children away from the device!


What are the safety symbols on the inverter and what do they mean?

Several symbols pertaining to safety can be found on the inverter. Please read and understand the content of these symbols before starting the installation.

Symbol Name/Image Description Description
Lightning bolt inside a triangle with ‘5min’ text. Residual voltage is present in the inverter! Before opening the inverter, you should wait five minutes to ensure that the capacitor has been fully discharged.
Lightning bolt inside a triangle. Caution! Danger through electric shock.
Three wavy vertical lines inside a triangle. Caution! Hot surface.
Exclamation mark inside a triangle. Disconnect the inverter from all the external power sources before maintenance!
Letters ‘CE’. The product is compliant with EU guidelines.
Wheeled bin with a cross over it. Do not dispose of the inverter together with household waste.
Open book with an ‘i’ symbol. Please read the manual before installing the inverter.
Ground symbol (three horizontal lines of decreasing length under a vertical line). Grounding point.
Triangle with text “Do not disconnect under load!”. Do not remove the DC input connector or AC output connector when the inverter is running.

What are the main components of the hybrid inverter?

NO. Name Description
1 Hanger Plate To hang the inverter on the wall-mounting bracket.
2 LED Indicator Label To explain the current working state of the inverter.
3 DC Switch To safely disconnect the DC circuit whenever necessary.
4 Indicator To indicate the current working state of the inverter.
5 Nameplate To identify the product, including device model, S/N, important specifications, etc.
6 Grounding terminal To connect system to earth.
7 Electrical connection area PV terminals, battery terminal, AC terminal, additional grounding terminal and communication terminals.

How do I interpret the LED indicators?

INDICATOR COLOR STATUS EXPLANATION
DC Green Steady on PV power available
Yellow Steady on PV power not available/too low
Red Steady on Fault
Off System is power-off
AC Green Steady on Inverter is operating
Green Blinking at long intervals (on for 1s and then off for 1s) Inverter in standby in grid-tied mode
Yellow Steady on Inverter is operating in off-grid mode
Yellow Blinking at long intervals (on for 1s and then off for 1s) Inverter in standby in off-grid mode
Red Steady on Fault
Off System is power-off
COM Green Blinking at long intervals (on for 0.2s and then off for 0.2s) Wireless waiting for connection
Green Blinking at long intervals (on for 1s and then off for 1s) Establishing wireless connection
Green Steady on Wireless connected
Yellow Steady on Bluetooth connected
Off No wireless/bluetooth connected

What are the different working modes of the hybrid inverter?

Working mode Description
Standby The Hybrid Inverter enters Standby mode when the external environment does not meet the operating requirements. In Standby mode:
• The Hybrid Inverter continuously performs status check and enters the Operating mode once the operating requirements are met.
• The Hybrid Inverter enters Shutdown mode after detecting a shutdown command or a fault after startup.
Operating In Operating mode:
• The Hybrid Inverter converts DC power from PV strings into AC power and feeds the power to the power grid.
• The Hybrid Inverter tracks the maximum power point to maximize the PV string output.
• If Hybrid Inverter detects a fault or a shutdown command, it enters the Shutdown mode.
• The Hybrid Inverter enters Standby mode after detecting that the PV string output power is not suitable for connecting to the power grid for generating power.
Shutdown • In Standby or Operating mode, the Hybrid Inverter enters Shutdown mode after detecting a fault or shutdown command.
• In Shutdown mode, the Hybrid Inverter enters Standby mode after detecting a startup command or that the fault is rectified.

What should I know about the Back-Up function?

1. For hybrid inverters, the electrical installation typically includes connection of the inverter to both PV modules and batteries. If there is no available power from batteries or PV modules in backup mode, the backup power supply will be automatically terminated.

2. Normally, the Back-Up switching time is less than 3 s. However, some external factors may cause the system to fail on Back-Up mode. Therefore, the users must be aware of conditions and follow the instructions as below:

• Do not connect loads that are dependent on a stable energy supply for a reliable operation.

• Do not connect the loads whose total capacity is greater than the maximum Back-Up capacity.

• Do not connect the loads that may cause very high start-up current surges, such as nonfrequency conversion air conditioning, vacuum cleaner or half-wave loads such as hair dryer, heat gun, hammer drill.

• Due to the condition of the battery itself, battery current might be limited by some factors, including but not limited to the temperature and weather.

• BACK-UP is not recommended if the PV system is not configured with batteries.

• When single overload protection occurs, the inverter can restart automatically; however, the restarting time will be extended if it happens several times.

• When the grid is disconnected, the off-grid function of the inverter will be closed automatically if the load capacity exceeds the inverter’s rated power; to enable it, turn off the large loads and ensure the load power is less than the rated power of the inverter.

Declaration for Back-Up Overload Protection

The inverter will restart in case of overload protection. The time required for restarting will increase (5 min at most) if overload protection repeats. Try to reduce Back-Up load power within maximum limitation or remove the loads which may cause very high start-up current surges.


What are the recommended backup loads for an off-grid scenario?

Please refer to this information before you use the back-up function of the inverter under off-grid situation.

Type Load Power
Dust collector 1.3kW
Water heater/Kettle /Iron /Oven /Toaster /Geothermal blanket / Rice cooker 3 kW
Microwave oven 1.5kW
Refrigerator 1kW
TV / Computer 1Kw
Bath heater 2.5kW
Fluorescent / LED lights 1.3kW
Electric fan / Ceiling fan 2kW
Conditioner (frequency conversion modulation) 1.5P

• The data of the compatibility for backup of Hybrid Inverter are based on the test with batteries (-20 ~ 55 ℃, 5~100% SOC). For the actual application, please refer to the maximum output capacity of the battery used.


What are the different working modes for the PV Energy Storage System (PV ESS)?

Mode1: Maximize Self-consumption

This mode is suitable for areas with high electricity tariff. When the PV power is sufficient, priority is given to the local load, and the excess electricity goes to energy storage, and if there is still energy left, it is sold to the grid. When the PV power is insufficient/there is no PV power, the battery is discharged for the local load, and when the battery discharge power and photovoltaic power can not meet the load demand, the insufficient power will be purchased from the grid.

Mode2: Maximize Feed-in

This mode is suitable for areas with high feed-in tariff. When the PV power is greater than the inverter capacity, the excess electricity will be stored by energy storage. When PV power is less than the inverter capacity, the excess electricity will be sold to the grid.

Mode3: Backup power

This mode is suitable for areas where grid outages occur frequently or to prevent grid outages. Reserved Backup SOC setting value can be adjusted, when battery SOC is less than reserved SOC value, battery can only be charged, until SOC reaches reserved value, the battery will be stopped charging; when SOC is larger than SOC setting value, battery will behave as Self-use mode.

Mode4: Charge and discharge schedule

This mode is suitable for areas with peaks and valleys in electricity prices Battery charging period and discharging period can be set, during charging period, battery can only be charged, while in discharging period, battery can only be discharged, the rest of the period, battery will behave as Self-use mode.

Mode5: Peak shaving

This function is to avoid exceeding peak kW limit from grid, by dynamically overriding the max kW limit on the battery. Users can set the peak kW value.


How does the inverter manage the battery charge and discharge?

The maximum allowable charge/discharge current is limited to the smaller value among the following:

• Temperature;

• the maximum power of inverter;

• the maximum / recommended charge/discharge current from the battery manufacturer.

For this reason, the battery charge power may not reach the nominal power. The inverter cannot respond to discharge/charge command when operating off-grid.

Range Battery management behavior
A (SOCL 0-15%) In this range, the battery is no longer discharged, even in battery-backup operation. SoCL can be set from 0 to 15% in APP.
B When operating off grid, the system reports the low SoC state.
C When starting up in off -grid condition, the system does not output AC power, so as to charge the battery by all PV power.
D (SoCback 20-90%) When operating grid-connected, the system charges / discharges the battery for PV power economy. SoCback can be set from 20 to 90% in APP.
E When operating grid-connected, the system charges / discharges the battery for PV power economy.
F When operating off -grid, the system charges / discharges the battery to support the system and obtain PV power economy.
G (SOCH 90-100%) The battery can be discharged to support the system or for PV power economy, while it cannot be charged. The inverter cannot respond to charge command in this range. SoCH can be set from 90 to 100% in APP.

What is included in the box?

The following product and accessories are included. The actual product received may differ.

• Energy manager*1

• Smart meter + current transformer*1

• D4 Disassembly tool*1

• Photovoltaic connector – straight male*2

• Photovoltaic connector – straight female*2

• Battery connector – straight male*1

• Battery connector – straight female*1

• Multi-COM (2-RJ45+22pin)

• Backup connector

• Grid-connected connector

• ground terminal*2

• Wireless module*1

• mounting bracket*1

• Electric meter communication Line*1

• expansion bolt*4

• SEM screw M4X12*4

• RJ45 connector*1

• Quick guide*1

• Packing list*1

• User manual*1

• Delivery inspection report*1

• Quality certificate*1

• Warranty card*1


How should I store the inverter if not used immediately?

The following requirements should be met if the M1 series inverter is not put into use directly:

• Do not unpack the M1 series inverter.

• Keep the storage temperature at -40°C to +70°C and the humidity at 5%–95% RH.

• The M1 series inverter should be stored in a clean and dry place and be protected from dust and water vapor corrosion.

• A maximum of 6 units can be stacked. To avoid personal injury or device damage, stack M1 series inverter with caution to prevent them from falling over.

• Periodic inspections are required during the storage. Replace the packing materials if necessary.

• If the M1 series inverter has been long-term stored, inspections and tests should be conducted by qualified personnel before it is put into use.


What tools are required for installation?

No. Tool Function
01 Hammer drill (Recommended drill diameter: 8mm) Used to drill holes in the wall
02 Screwdriver Wiring
03 Phillips screwdriver Used to remove and install the screws of the AC terminal
04 Removal tool Used to remove the PV battery terminal
05 Wire stripper Used to strip the wire
06 6mm Allen key Used to turn the screw to connect the rear panel to the inverter
07 Crimping tool Used to crimp power cables
08 Multimeter Used to check the Grounding
09 Marker Used for marking
10 Measuring tape Used to measure distances
11 Spirit level Used to align the wall bracket
12 ESD gloves For the installer
13 Safety goggles For the installer
14 Anti-dust respiratory mask For the installer

What are the environmental and mounting requirements for installation?

Basic Requirements

• The Hybrid Inverter is protected to IP65 and can be installed indoors or out doors.

• Do not install the Hybrid Inverter in a place where personnel are easy to come into contact with its enclosure and heat sinks, because these parts are extremely hot during operation.

• Do not install the Hybrid Inverter in areas with flammable or explosive materials.

• Do not install the Hybrid Inverter at a place within children’s reach.

• Do not install the Hybrid Inverter outdoors in salt areas because it will be corroded there and may cause fire. A salt area refers to the region within 500 meters from the coast or prone to sea breeze.

• The Hybrid Inverter must be installed in a well-ventilated environment to ensure good heat dissipation.

• Recommended: Install the Hybrid Inverter in a sheltered place or a place with an awning.

Mounting Requirements

• The mounting structure where the Hybrid Inverter is installed must be fireproof.

• Do not install the Hybrid Inverter on flammable building materials.

• The Hybrid Inverter is heavy. Ensure that the installation surface is solid enough to bear the weight load.

• In residential areas, do not install the Hybrid Inverter on drywalls or walls made of similar materials which have a weak sound insulation performance because the noise generated by the Hybrid Inverter is noticeable.

Space Requirements

• Install the inverter vertically. Never install the inverter horizontally, or at forward/backward tilted, side tilted, or upside down. The forward tilt angle must be less than 15 degrees.

• Reserve enough space around the inverter to ensure sufficient space for installation and heat dissipation:

– Above: ≥ 300mm

– Below: ≥ 500mm

– Left side: ≥ 200mm

– Right side: ≥ 200mm

– Front: ≥ 300mm


How do I install the inverter on the wall?

Step 1: Mark and drill holes

Place the wall-mounting bracket to a proper position on the wall. Use the spirit level on the bracket to ensure it is level (the bubble should be in the middle position). Mark the hole positions with a marker and drill the holes (Diameter: 8mm, Depth: 45-50mm).

Step 2: Install the mounting bracket

Insert the expansion bolts into the holes. Install the mounting bracket and tighten the bolts to a torque of 5±0.2Nm.

Step 3: Mount the inverter

Lift the inverter and slide it down along the wall mounting bracket to make sure they match perfectly. Use two M4*10 screw sets to lock both the left and right sides of the inverter to the bracket. Tighten to a torque of 1.2±0.2Nm.


What are the electrical terminal descriptions?

No. Name Description DVC
1 PV input terminal (PV1+/PV1-) MC4 terminals for PV 1 input. DVCC
2 PV input terminal (PV2+/PV2-) MC4 terminals for PV 2 input. DVCC
3 BAT input terminal (BAT+/BAT-) Connectors for the battery power cables. DVCC
4 Communications port (BMS) Communication connection for Battery BMS. DVCA
5 Communications port (RJ45) Communication port Reserved. DVCA
6 Wireless button Used to enable WiFi distribution network mode or OTA. /
7 Communications port (COM) Communication connection for smart energy meter, DI/DO RSD, etc. DVCA
8 AC-Backup output port AC terminal for Backup loads. DVCC
9 AC-Grid output port AC terminal to connect to the grid. DVCC
10 Ventilation valve / /
11 Wireless Communications Communication accessory port to be connected to WiNet-S communication module. DVCA

What are the recommended values for the electrical diagram installation requirements?

The values in the table are recommended values and can be set to other values according to actual conditions.

Component Number (from diagram) Requirement
1 Depends on household loads and inverter capacity
2 Depends on loads
3 < 63A/230V/400V AC breaker
4 32A/230V/400V AC breaker
5 30mA RCD
6 300mA RCD
7 30mA RCD

What are the cable requirements for installation?

NO. Cable Type Cable Diameter Cross-section
1 PV cable Complying with 600V and 16A standard 6-9mm 4-6 mm²
2 AC-Backup cable Outdoor 3-core copper wire cable 10-21mm 4-6 mm²
3 AC-Grid cable Outdoor 3-core copper wire cable 12-25.8mm 6-16 mm²
4 BAT Power cable Complying with 600V and 35A standard 5.5-8mm 6 mm²
5 Communication cable CAT 5E outdoor shielded network cable 4.8-6mm 0.08-0.2 mm²
6 Grounding cable Single-core copper wire cable The same as PE wire in AC cable

How do I connect the ground cable?

Connect the inverter to the equipotential bonding bar by using the protective earth cable (PE) for grounding.

1. Strip 6 mm of insulation from the end of the 4 mm² ground cable. Also prepare a heat-shrink tubing and slide it onto the cable.

2. Crimp the ground terminal (ring terminal) onto the stripped end of the cable using a crimping tool.

3. Slide the heat-shrink tubing over the crimped terminal and use a heat gun to shrink it.

4. Locate the grounding terminal on the side of the inverter. Unscrew the M4 screw, place the ring terminal onto the screw, and then securely fasten the screw back into the terminal. The recommended torque is 1.2±0.2Nm.


How do I perform the AC Output Connection?

The blue connector is for the grid, and the black connector is for backup. The installation and line connection process is the same for both. Follow these steps to install the AC connector:

1. Strip the outer jacket of the AC cable by 30-50mm. Then, strip the insulation from the individual L, N, and PE wires.

2. Insert the stripped wires into the corresponding terminals of the connector plug. Use a screwdriver to tighten the screws to a torque of 1.2±0.2Nm.

Connection Cable
L Phase 1 (brown)
N Neutral conductor (blue)
PE Grounding cable (yellow-green)

3. Assemble the connector housing and screw the cable gland tight.

4. Connect the assembled AC connector to the corresponding AC port on the inverter (AC BACKUP or AC GRID) by turning it clockwise until it clicks and locks into place.

To remove the AC connector, turn it anticlockwise.


How do I install the PV and Battery connectors?

The connection steps for the battery and PV connectors are the same, but the terminal specifications and colors are different. The battery terminal is blue, and the PV terminal is black.

Creating the Connectors:

1. Strip 7 mm of insulation from the end of the red (+) and black (-) 4mm² cables.

2. Insert the stripped wire ends into the metal pin contacts.

3. Use a crimping tool to crimp the metal pins onto the wires.

4. Insert the crimped red (+) and black (-) cables into their corresponding positive and negative plastic connector housings until they click into place.

5. Tighten the sealing caps onto the back of the connectors. You can use an MC4 Wrench to ensure they are tight.

Installing the PV Connector:

1. Rotate the DC switch on the inverter to the “OFF” position.

2. Check the cable connection of the PV string for correct polarity and ensure the open-circuit voltage does not exceed the inverter input limit of 600V using a multimeter.

3. Connect the PV connectors to the corresponding PV terminals (PV1+/PV1-, PV2+/PV2-) on the inverter until there is an audible click.

Installing the Battery Connector:

1. Ensure the DC switch is “OFF”.

2. Connect the prepared battery connectors to the corresponding BAT+ and BAT- terminals on the inverter until there is an audible click.

NOTE: Insert the protective caps into any unused DC connections.


How do I make the BMS RJ45 connection?

The Enable cable, along with the RJ45 cable, is used for communication between the inverter and the Li-ion battery.

Step 1 (optional, if not using a pre-made cable):

• Thread the communication cable (diameter 4.8-6mm) through the waterproof component (nut, seal, body).

• Strip the insulation layer of the cable with an Ethernet wire stripper.

• Insert the stripped communication cable wires into the RJ45 plug in the correct order and crimp it with a crimper.

• Tighten the waterproof cover before installing the connector.

Skip this step if a standard network cable with an RJ45 plug is already prepared.

Step 2:

• Find the BMS terminal under the inverter.

• Insert the RJ45 plug into the BMS terminal, ensuring it is inserted correctly.

• Tighten the waterproof screw cap securely.


How do I connect the Smart Meter with CT?

The Meter can be installed in the AC combiner box or other places that are not accessible to children. Connect the smart meter and CT as follows:

1. Connect the L and N wires from the grid to terminals 4(L) and 3(N) on the meter respectively.

2. Connect the L and N wires going to the inverter to the same terminals 4(L) and 3(N).

3. Clamp the Current Transformer (CT) around the main L (Live) wire coming from the grid. Ensure the arrow on the CT points towards the load (inverter/house).

4. Connect the two wires from the CT to terminals 1(L-S1) and 2(L-S2) on the meter.

5. Connect the communication cable between the meter’s terminals 10(A+) and 9(B-) and the inverter’s RS485 communication port.

Meter Terminals Definition:

NO. Definition Function
1 L-S1 To detect the CT current and direction
2 L-S2
3 N Power supplied from grid
4 L
5-7 /
8 GND Ground connection
9 B- Communicate with hybrid inverter
10 A+

Smart Meter Parameter Setting: The energy meter is preconfigured. If you need to change settings, follow the button press sequence shown in the manual’s Figure 7-4 to set the ID, Baud rate, and primary current.


How do I connect the Wireless Module?

Procedure:

1. Locate the Wireless Communications port at the bottom of the inverter.

2. Remove the protective cap from the USB interface.

3. Insert the Wireless stick (WiNet-S module).

4. Tighten the connecting nut to secure the module and ensure a waterproof seal.


What are the definitions for the Communication Ports (Multi-COM and RJ45)?

Multi-COM Port Definition

PIN Definition Function
P1 RJ45 RS485+(A2)/RS485-(B2) Communicate with smart meters
P2 RJ45 RS485+(A2)/RS485-(B2) Communicate with heat pump
1 DO1+ Dry contacts of load control
2 DO1-
3 DO2 Dry contacts of load control
4 DO3
5 DO_COM
6 DRM1/5 Demand response modes (DRED For Australia and New Zealand, RCR For Germany and some other European countries)
7 DRM2/6
8 DRM3/7
9 DRM4/8
10 COM 12V power supply
11 COM_LOAD/0 Demand response modes
12 ES For WSD(wired shut down)/NS protection
13 Grid on For grid operator
14 COM 12V power supply
15 RS485B1 Communicate with inverter
16 RS485A1
17 RS485B1
18 RS485A1
19 RS485B3 Communicate with upper computer
20 RS485A3
21 / Reserved
22 / Reserved

RJ45 Terminal Definition

No. Color P1 RJ45(Smart meters) P2 RJ45(Heat pump)
1 White with orange stripes RS485+(A2) RS485+(A2)
2 Orange RS485-(B2) RS485-(B2)
3 White with green stripes NC NC
4 Blue NC NC
5 White with blue stripes NC NC
6 Green NC NC
7 White with brown stripes NC NC
8 Brown NC NC

How do I install the Multi-COM cable and connector?

1. Prepare the individual wires by stripping about 12mm of insulation. Crimp the appropriate pin terminals onto the ends of the wires.

2. Disassemble the Multi-COM connector, which consists of a nut, sealing screen, sealing ring, body, and housing.

3. Thread the prepared cables through the nut, sealing screen, and sealing ring. You can cut a small gap in the sealing screen to help thread the cables.

4. Insert the crimped terminals into the correct positions in the connector body according to the pin definition table. You should hear a click when they are properly seated.

5. Assemble the connector by pushing the body into the housing and tightening the nut. A final click will indicate it is locked.

6. To install the Multi-COM connector to the inverter, align it with the COM port on the bottom of the inverter and push it in, then rotate the locking ring clockwise until it is secure.


What checks should be performed before powering on the system?

Ensure that the DC and AC voltages are within the permissible range of the inverter.

No. Item Acceptance Criterion
1 Inverter installation The Inverter is installed correctly and securely.
2 Battery installation (optional) The Energy Storage Unit is installed correctly and securely.
3 Wireless module The Wireless module is installed correctly and securely.
4 Cable routing The cables are routed properly as required by the customer.
5 Cable ties Cable ties are secured evenly and no burr exists.
6 Reliable grounding The PE cable is connected correctly and securely.
7 Switch DC switches and all the switches connecting to the Inverter are OFF.
8 Cable connection The AC output power cable, DC input power cables, battery cable, and signal cable are connected correctly and securely
9 Unused terminals and ports Unused terminals and ports are locked by watertight caps.
10 Installation environment The installation space is proper, and the installation environment is clean and tidy.

How do I power-on the system?

1. If a battery is connected, turn on the battery switch.

2. Turn on the AC switch between the inverter and the power grid.

3. Turn on the DC switch (if any) between the PV string and the inverter.

4. Turn on the DC switch at the bottom of the inverter.

5. Wait for about 1 minute and observe the LED indicators on the inverter to check its running status.


How do I perform a system power-off?

If the inverter needs to be shut down for electrical inspection, please follow the following steps:

1. Turn off the AC switch between the inverter and the power grid.

2. Turn off the DC switch at the bottom of the inverter.

3. If there is a DC switch between the inverter and PV string, turn off the DC switch.

4. Turn off the DC switch at the battery (Optional).

5. Wait for 5 minutes before checking the inverter.


What routine maintenance is required for the inverter?

Inverters do not generally require daily or routine maintenance. Before carrying out cleaning, ensure that the DC switch and AC circuit breaker between the inverter and power grid have been switched off. Wait at least 5 minutes before carrying out cleaning.

Cleaning the inverter

Clean the inverter using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, cleaning agents etc.

Cleaning the heat sink

In order to help guarantee correct long-term operation of the inverter, make sure that there is sufficient space for ventilation around the heat sink. Check the heat sink for blockages (dust, snow etc.) and remove them if present. Please clean the heat sink using an air blower and a dry, soft cloth or a soft bristle brush. Do not clean the heat sink with water, corrosive chemicals, cleaning agents etc.


How do I troubleshoot common errors and alarms?

If an earth fault alarm occurs, the error is displayed on the LED indicators, the red light illuminate. For other errors, check the error list below. If no error information is displayed, check the following:

• Has the inverter been set up in a clean, dry, well-ventilated area?

• Is the DC switch set to ON?

• Are the cables sufficiently dimensioned and short enough?

• Are the input connections, output connections and the wiring all in good condition?

• Are the configuration settings for the relevant installation correct?

• Are the the communication cables correctly connected and undamaged?

Error List

Alarm ID Alarm Name Possible Cause Troubleshooting
1001 String reverse connection The PV string polarity is reversed. Check whether the PV string is reversely connected to the inverter. If so, wait until the PV string current decreases to below 0.5 A. Then, turn off the DC switch and correct the PV string polarity.
1002 Abnormal residual current The input-to-ground insulation impedance has decreased during the inverter operation. 1. If the alarm occurs accidentally, the external power cable may be abnormal temporarily. The inverter automatically recovers after the fault is rectified. 2. If the alarm persists or lasts a long time, check whether the impedance between the PV string and ground is too low.
1003 Low insulation resistance 1. A short circuit exists between the PV array and the ground. 2. The PV array is in a moist environment and the circuit is not well. 1. Check the impedance between the PV array output and the ground. If a short circuit occurs or the insulation is insufficient, rectify the fault. 2. Check whether the PE cable of the inverter is correctly connected. 3. If you have confirmed that the impedance is lower than the specified protection threshold in a cloudy or rainy environment, log in to the APP and set the Insulation resistance protection threshold.
1004 Cabinet over temperature 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds the upper threshold. 3. The inverter is not operating properly. 1. Check the ventilation and ambient temperature at the inverter installation position. 2. If the ventilation is poor or the ambient temperature exceeds the upper threshold, improve the ventilation and heat dissipation. 3. If the ventilation and ambient temperature are normal, contact your dealer or technical support.
1005 Grid loss 1. Power grid outage occurs. 2. The AC circuit is disconnected or the AC switch is off. 1. The alarm is cleared automatically after the power grid recovers. 2. Check whether the AC circuit is disconnected or the AC switch is off.
1006 Power Module Communication failure The battery communication is abnormal. Check that the communications cable is correctly installed, and that the communication parameters are the same as the inverter RS485 configurations.
1007 BMS Communication failure The battery communication is abnormal. Check that the communications cable is correctly installed, and that the communications parameters are the same as the inverter RS485 configurations.
1008 Meter Communication failure The meter communication is abnormal. Check that the communications cable is correctly installed, and that the communication parameters are the same as the inverter RS485 configurations.
1009 Equipment fault An unrecoverable fault occurs on a circuit inside the inverter. Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the alarm persists, replace the monitoring board or contact your dealer or technical support.
1010 Grid overvoltage The grid voltage exceeds the upper threshold. 1. The inverter automatically recovers when the grid becomes normal. 2. If the alarm persists, check if grid voltage is in range. If not, contact local power operator. If yes, modify the grid overvoltage protection threshold via the app with operator consent.
1011 Grid undervoltage The grid voltage is below the lower threshold. 1. The inverter automatically recovers when the grid becomes normal. 2. If the alarm persists, check if grid voltage is in range. If not, contact local power operator. If yes, modify the grid undervoltage protection threshold via the app with operator consent.
1012 Grid over frequency The actual power grid frequency is higher than the requirements. 1. The inverter automatically recovers when the grid becomes normal. 2. If the alarm persists, contact the local power operator.
1013 Grid under frequency The actual power grid frequency is lower than the requirements. 1. The inverter automatically recovers when the grid becomes normal. 2. If the alarm persists, contact the local power operator.
1014 AC-grid output overcurrent The power grid voltage drops dramatically or the power grid is short circuited. 1. The inverter monitors external operating conditions and automatically recovers. 2. If the alarm persists, check if the output is short-circuited. If the fault persists, contact your dealer.
1015 AC-backup output overcurrent The backup load power exceeds the upper threshold. 1. Try to reduce the load power; 2. If it doesn’t work out, contact your dealer or technical support.
2001 Power module over temperature 1. Poor ventilation. 2. High ambient temp. 3. Abnormal battery power control module. 1. Check ventilation and ambient temperature. 2. Improve ventilation/heat dissipation if needed. 3. If conditions are normal, contact your dealer.
2002 Low battery DC input bus voltage 1. DC bus voltage of the battery is low. 2. The battery DC switch is OFF. 3. The battery cables are not correctly connected. 1. The inverter will recover when grid becomes normal. 2. If it persists, check grid voltage range. If out of range, contact power operator. If in range, modify overvoltage threshold via app (with consent).
2003 Battery expansion module undervoltage The voltage of a battery expansion module is low. If sunlight is sufficient or AC reverse charging is allowed, the battery expansion modules can be charged when the inverter is running.
2004 Power module reversely connected The positive and negative terminals are reversely connected. 1. Turn off all switches and wait 5 mins. 2. Check cable connections. 3. After checking, turn on switches in sequence. 4. If alarm persists, contact support.
2005 Abnormal BMS communication The power module fails to communicate with the battery expansion modules. 1. Turn off the battery DC switch. 2. Check power and communication cables. 3. After checking, turn on the battery DC switch. 4. If alarm persists, contact support.
2006 Equipment fault An unrecoverable fault occurs on a circuit inside the device. Turn off the DC switch, and then turn them on after 5 minutes. If the alarm persists, replace the monitoring board or contact your dealer.
2007 Black start-up failed 1. The battery level is less than 10%. 2. The energy storage DC switch is not turned on. 1. Turn off PV and AC output switch, wait 1 minute. 2. Turn on PV and AC output switch, and start black start again.
2008 Battery reversal connection Battery reversal connection. Check whether the battery is reversely connected to the power module. If so, turn off the DC switch and correct the battery polarity.
3001 Battery Pack Undervoltage 1. The voltage of the battery pack is too low. 2. The battery pack has been stored for a long time. 3. The battery pack has been idle for a long time. 1. Connect to the power grid and charge batteries in a timely manner. 2. If the alarm persists after one hour, contact support.
3002 Battery module over temperature 1. Poor ventilation. 2. High ambient temp. 3. Abnormal battery power control module. 1. Check ventilation and ambient temperature. 2. Improve ventilation/heat dissipation if needed. 3. If conditions are normal, contact support.
3003 Battery module low temperature 1. The ambient temperature is excessively low. 2. A battery expansion module is abnormal. 1. Check ambient temperature at installation position. 2. If temp is too low, improve installation environment. 3. If alarm persists after temp becomes normal, contact support.

How do I handle the inverter for removal, packing, or disposal?

Removing the inverter

Before removing the inverter, power off the AC and DC (batteries).

1. Disconnect all cables from the inverter, including RS485 communications cables, DC input power cables, AC output power cables, and PGND cables.

2. Remove the inverter from the mounting bracket.

3. Remove the mounting bracket.

Packing the inverter

• If the original packing materials are available, put the inverter inside them and then seal them by using adhesive tape.

• If the original packing materials are not available, put the inverter inside a suitable cardboard box and seal it properly.

Disposing of the inverter

If the inverter service life expires, dispose of it according to the local disposal rules for electrical equipment waste. This product complies with the EU WEEE Directive and bears a classification symbol for waste electrical and electronic equipment (WEEE). This symbol indicates that this product shall not be disposed with other household wastes at the end of its service life. Used device must be returned to an official collection point for recycling.


What are the technical specifications for the M1-S(3-6)K series inverters?

Model M1-S3K M1-S3.68K M1-S4K M1-S4.6K M1-S5K M1-S6K
DC Input (PV)
Max. PV array power (Wp) 6000 7400 8000 9200 10000 12000
Max. PV input power (Wp) 4500 5500 6000 6900 7500 10000
Max. input voltage (V) 600
MPPT operating voltage range (V) 60~550
Start-up voltage (V) 75
Rated input voltage (V) 360
Max. input current (input PV1 /input PV2) 16/16
Max. short-circuit current 20/20
No. of MPP trackers / Strings per MPP tracker 2
Battery connection
Battery type Li-ion
Voltage range (V) 85-460
Max. charge current (A) 30
Max. discharging current (A) 30
Max. charge power (W) 4500 5500 6000 6000 6000 6000
max. discharge power (W) 3000 3680 4000 4600 5000 6000
AC Output Data (on-grid)
Nominal AC output power (W) 3000 3680 4000 4600 5000 6000
Max. AC output apparent power (VA) 3300 3680 4400 5000 5500 6000
Nominal Output Current(A) 13.0 16.0 17.4 20.0 21.7 26.1
Max. AC output current (A) 15.0 16.0 20.0 23.0 25.0 27.3
Max. AC input apparent power (VA) 6300 7360 8400 9600 10000 10000
Max. AC input current (VA) 27.4 32.0 36.5 41.7 43.5 43.5
Nominal AC voltage (V) 220Vac/230Vac/ 240Vac,L/N/PE
Nominal AC Grid Frequency (Hz) 50 / 60
Adjustable power factor 0.8 leading … 0.8 lagging
Max. total harmonic distortion ≤3%
AC Output Data (back-up)
Nominal output power (W) 3000 3680 4000 4600 5000 6000
Max. continuous current (A) 13.0 16.0 17.4 20.0 21.7 26.1
Nominal voltage (V) 230Vac,L/N/PE
Frequency (Hz) 50/60
General Data
Operating temperature range (°C) -25°C to + 60°C (Derating above 45°C @ Rated output power)
Weight (kg) 24.5
Max. operating altitude (m) 4000
Dimension(W/H/D) (mm) 485/450/187
Degree of protection IP66

CLICK HERE TO DOWNLOAD MIDEA M1-S5K (01) PDF MANUAL


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.