How can I understand the model number of my FRIEDRICH QUIETMASTER KS12J30A air conditioner?

The model number of your FRIEDRICH QUIETMASTER KS12J30A provides specific information about the unit’s features and type. Here is a breakdown of the code:

1st DIGIT – FUNCTION

K = Straight Cool, Challenger or QuietMaster Series

2nd DIGIT – TYPE

S = Small Chassis

3rd & 4th DIGITS – APPROXIMATE BTU/HR (Cooling)

These digits represent the approximate cooling capacity. The heating BTU/HR capacity is listed in the Specifications/Performance Data Section.

5th DIGIT – ALPHABETICAL MODIFIER

This is an alphabetical character that acts as a modifier.

6th DIGIT – VOLTAGE

3 = 230-208 Volts

7th DIGIT

0 = Straight Cool & Heat Pump Models

8th DIGIT

This digit signifies a Major Change in the product line.


What are the specifications for the FRIEDRICH QUIETMASTER KS12J30A air conditioner?

SPECIFICATIONS KS12J30A
BTUH 12500 / 12500
E.E.R. 10.0 / 10.0
Volts 230 / 208
Amperes 5.8 / 6.2
Total Watts 1250 / 1250
Hertz 60
Fuse/Breaker Size 15
Fan RPM 1180
Evaporator Air CFM 325
Fresh Air CFM Yes
Exhaust Air CFM Yes
Dehumidification Pts/HR 3.5
Width 25-15/16″
Height 15-15/16″
Depth 27-3/8″
Minimum Ext. Into Room 3-1/16″
Minimum Ext. to Outside 16-15/16″
Net Weight 111
Shipping Weight 121

What is the performance data for the FRIEDRICH QUIETMASTER KS12J30A air conditioner?

The performance data for the FRIEDRICH QUIETMASTER KS12J30A, based on rating conditions of 80°F Room Air Temperature and 50% Relative Humidity with 95°F Outside Air Temperature at 40% Relative Humidity, is as follows:

Cooling EVAPORATOR AIR TEMP. °F. OPERATING PRESSURES ELECTRICAL RATINGS R-22 REFRIG. COMP. OIL
MODEL DISCHARGE AIR TEMP. DROP °F SUCTION DISCHARGE AMPS LOCKED ROTOR AMPS CHARGE IN OZ. CHARGE IN FLUID OZ.
KS12J30A 57.0 23.0 79.0 293 5.8 / 6.2 26.3 26.0 11.8

How do I perform a winding and ground test on the compressor of my FRIEDRICH QUIETMASTER KS12J30A?

WARNING: DISCONNECT ELECTRICAL POWER TO THE UNIT BEFORE SERVICING OR TESTING.

Compressor Winding Test

1. Remove the compressor terminal box cover and disconnect wires from the terminals.

2. Using an ohmmeter, check for continuity across the following terminals:

Terminal “C” and “S” – no continuity means an open winding, and the compressor must be replaced.

Terminal “C” and “R” – no continuity means an open winding, and the compressor must be replaced.

Terminal “R” and “S” – no continuity means an open winding, and the compressor must be replaced.

Ground Test

1. Use an ohmmeter set on its highest scale.

2. Touch one lead to the compressor body (ensure a clean point of contact for a good connection) and the other probe, in turn, to each compressor terminal.

3. If a reading is obtained, the compressor is grounded and must be replaced.


How can I check the compressor efficiency of my FRIEDRICH QUIETMASTER KS12J30A?

Compressor inefficiency is typically caused by broken or damaged suction and/or discharge valves, which reduces the compressor’s ability to pump refrigerant gas. To check for this condition:

1. Install a piercing valve on the suction and discharge or liquid process tube.

2. Attach gauges to the high and low sides of the system.

3. Start the system and run a “cooling performance test.”

If the test shows:

A. Below normal high side pressure.

B. Above normal low side pressure.

C. Low temperature difference across the coil.

Then the compressor valves are faulty, and the compressor should be replaced.


How do I test the thermal overload on my FRIEDRICH QUIETMASTER KS12J30A?

WARNING: DISCONNECT ELECTRICAL POWER TO THE UNIT BEFORE SERVICING OR TESTING.

Testing an External Overload:

1. Remove the overload.

2. Allow time for the overload to reset before attempting to test.

3. Apply ohmmeter probes to the terminals on the overload wires. There should be continuity through the overload.

Checking an Internal Overload:

1. With no power to the unit, remove the leads from the compressor terminals.

2. Using an ohmmeter, test for continuity between terminals C-S and C-R. If there is no continuity, the compressor’s internal overload is open, and the compressor must be replaced.


How do I test the fan motor and run capacitor on my FRIEDRICH QUIETMASTER KS12J30A?

WARNING: DISCONNECT ELECTRICAL POWER TO THE UNIT BEFORE SERVICING OR TESTING.

Fan Motor Test:

1. Ensure the capacitor is serviceable before testing the motor.

2. Disconnect the fan motor wires from the fan speed switch or system switch.

3. Apply “live” test cord probes on the black wire and the common terminal of the capacitor. The motor should run at high speed.

4. Apply “live” test cord probes on the red wire and the common terminal of the capacitor. The motor should run at low speed.

Run Capacitor Test:

1. Remove the capacitor from the unit.

2. Check for visual damage such as bulges, cracks, or leaks.

3. For dual-rated capacitors, apply an ohmmeter lead to the common (C) terminal and the other probe to the compressor (HERM) terminal. A good capacitor will cause the ohmmeter’s pointer to deflect and then gradually move back to infinity.

4. Reverse the probe leads and momentarily touch the capacitor terminals. The pointer’s deflection should be twice that of the first check if the capacitor is good.

5. Repeat steps 3 and 4 to check the fan motor side of the capacitor.

NOTE: A shorted capacitor will show a low, constant resistance (“0”). An open capacitor will show no movement of the pointer.


How do I test the system control switch and thermostat on my FRIEDRICH QUIETMASTER KS12J30A?

WARNING: DISCONNECT ELECTRICAL POWER TO THE UNIT BEFORE SERVICING OR TESTING.

System Control Switch Test:

Disconnect the leads from the control switch. Using an ohmmeter, check for continuity between the terminals for each position:

“Off” Position – no continuity between terminals.

“Lo Cool” Position – continuity between terminals “L1” and “C”, “LO” and “MS”.

“Med Cool” Position – continuity between terminals “L1” and “C”, “M” and “MS”.

“Hi Cool” Position – continuity between terminals “L1” and “C”, “H” and “MS”.

“Fan Only” Position – continuity between terminals “L1” and “2”.

Thermostat Test:

1. Remove the wires from the thermostat.

2. Turn the thermostat to its coldest position and check for continuity between the two terminals.

3. Turn the thermostat to its warmest position and check to see if the thermostat contacts open (no continuity).

NOTE: The temperature must be within the thermostat’s range of 60°F (± 2°) to 92°F (± 4°) for an accurate test. Do not attempt to adjust the thermostat; if it is faulty, it should be replaced.


How do I test the MoneySaver® switch on my FRIEDRICH QUIETMASTER KS12J30A?

WARNING: DISCONNECT ELECTRICAL POWER TO THE UNIT BEFORE SERVICING OR TESTING.

To test the MoneySaver® rocker switch, disconnect the leads from the switch and use an ohmmeter to check for continuity.

1. When YES is depressed, there should be continuity between terminals “1” and “2”.

2. When NO is depressed, there should be continuity between terminals “2” and “3”.


What is the procedure for replacing a component in the sealed refrigeration system of my FRIEDRICH QUIETMASTER KS12J30A?

This procedure applies when replacing components like the compressor, condenser, evaporator, or capillary tube, or when repairing refrigerant leaks.

1. Recover the refrigerant from the system at the process tube located on the high side of the system using an EPA-approved recovery system. Recover CFCs in the system to at least 5%.

2. Cut the process tube below the pinch-off on the suction side of the compressor.

3. Connect a line from a nitrogen tank to the suction process tube.

4. Drift dry nitrogen through the system and unsolder the most distant connection first (e.g., filter drier, high side process tube).

5. Replace the inoperative component and always install a new filter drier. Drift dry nitrogen through the system while making these connections.

6. Pressurize the system to 30 PSIG with proper refrigerant and then boost the pressure to 150 PSIG with dry nitrogen.

7. Leak test the complete system with an electronic halogen leak detector and correct any leaks found.

8. Reduce the system pressure to zero gauge pressure.

9. Connect a vacuum pump to both the high and low sides of the system using deep vacuum hoses or copper tubing (do not use regular hoses).

10. Evacuate the system to a maximum absolute holding pressure of 200 microns or less.

11. Break the vacuum by charging the system from the high side with the correct amount of specified refrigerant. This prevents boiling the oil out of the crankcase.

12. Restart the unit several times, allowing pressures to stabilize. Pinch off the process tubes, cut and solder the ends. Remove the pinch-off tool and leak check the process tube ends.


What should I do if the compressor on my FRIEDRICH QUIETMASTER KS12J30A does not run?

POSSIBLE CAUSE TO CORRECT
Low voltage. Check for voltage at the compressor. 115 volt and 230 volt units will operate at 10% voltage variance.
Thermostat not set cold enough or inoperative. Set thermostat to the coldest position. Test thermostat and replace if inoperative.
Compressor hums but cuts off on overload. Hard start compressor. Direct test compressor. If the compressor starts, add starting components.
Open or shorted compressor windings. Check for continuity and resistance.
Open overload. Test overload protector and replace if inoperative.
Open capacitor. Test capacitor and replace if inoperative.
Inoperative system switch. Test for continuity in all positions. Replace if inoperative.
Broken, loose or incorrect wiring. Refer to the appropriate wiring diagram to check wiring.

What should I do if the fan motor on my FRIEDRICH QUIETMASTER KS12J30A does not run?

POSSIBLE CAUSE TO CORRECT
Inoperative system switch. Test switch and replace if inoperative.
Broken, loose or incorrect wiring. Refer to applicable wiring diagram.
Open capacitor. Test capacitor and replace if inoperative.
Fan speed switch open. Test switch and replace if inoperative.
Inoperative fan motor. Test fan motor and replace if inoperative (be sure internal overload has had time to reset).

Why doesn’t my FRIEDRICH QUIETMASTER KS12J30A cool well, or only cools slightly?

POSSIBLE CAUSE TO CORRECT
Undersized unit. Refer to Sizing Charts.
Thermostat open or inoperative. Set to coldest position. Test thermostat and replace if necessary.
Dirty filter. Clean as recommended in the Owner’s Manual.
Dirty or plugged condenser or evaporator coil. Use steam or detergents to clean.
Poor air circulation in area being cooled. Adjust discharge air louvers. Use high fan speed.
Fresh air or exhaust air door open on applicable models. Close doors. Instruct customer on use of this feature.
Low capacity – undercharge. Check for leak and make repair.
Compressor not pumping properly. Check amperage draw against nameplate. If not conclusive, make pressure test.

Why won’t my FRIEDRICH QUIETMASTER KS12J30A run at all?

POSSIBLE CAUSE TO CORRECT
Fuse blown or circuit tripped. Replace fuse, reset breaker. If repeats, check fuse or breaker size. Check for shorts in unit wiring and components.
Power cord not plugged in. Plug in power cord.
System switch in “Off” position. Set switch correctly.
Inoperative system switch. Test for continuity in each switch position.
Loose or disconnected wiring at switch or other components. Check wiring and connections. Reconnect per wiring diagram.

Why is the evaporator coil on my FRIEDRICH QUIETMASTER KS12J30A freezing up?

POSSIBLE CAUSE TO CORRECT
Dirty filter. Clean as recommended in Owner’s Manual.
Restricted air flow. Check for dirty or obstructed coil – clean as required.
Inoperative thermostat. Test for shorted thermostat or stuck contacts.
Short of refrigerant. De-ice coil and check for leak.
Inoperative fan motor. Test fan motor and replace if inoperative.
Partially restricted capillary. De-ice coil. Check temperature differential across coil. Touch test coil return bends for same temperature. Test for low running current.

Why does the compressor on my FRIEDRICH QUIETMASTER KS12J30A run continually and not cycle off?

POSSIBLE CAUSE TO CORRECT
Excessive heat load. Unit undersized. Test cooling performance of unit. Replace with larger unit.
Restriction in line. Check for partially iced coil. Check temperature split across coil.
Refrigerant leak. Check for oil at silver soldered connections. Check for partially iced coil. Check split across coil. Check for low running amperage.
Thermostat contacts stuck. Check operation of thermostat. Replace if contacts remain closed.
Thermostat incorrectly wired. Refer to appropriate wiring diagram.

What should I do if the thermostat does not turn off my FRIEDRICH QUIETMASTER KS12J30A?

POSSIBLE CAUSE TO CORRECT
Thermostat contacts stuck. Replace thermostat.
Thermostat set at coldest point. Turn to higher temperature setting to see if unit cycles off.
Incorrect wiring. Refer to appropriate wiring diagram.
Unit undersized for area to be cooled. Refer to Sizing Chart.

Why does my FRIEDRICH QUIETMASTER KS12J30A compressor attempt to start, or run for short periods, then cycle on overload?

POSSIBLE CAUSE TO CORRECT
Overload inoperative. Opens too soon. Check operation of unit. Replace overload if system operation is satisfactory.
Compressor attempts to start before system pressures are equalized. Allow a minimum of two (2) minutes for pressures to equalize before attempting to restart. Instruct customer of waiting period.
Low or fluctuating voltage. Check voltage with unit operating. Check for other appliances on the circuit. The air conditioner should be on a separate circuit for proper voltage, and be fused separately.
Incorrect wiring. Refer to appropriate wiring diagram.
Shorted or incorrect capacitor. Check by substituting a known good capacitor of correct rating.
Restricted or low air flow through condenser coil. Check for proper fan speed or blocked condenser.
Compressor running abnormally hot. Check for kinked discharge line or restricted condenser. Check amperage.

Why doesn’t the thermostat turn on my FRIEDRICH QUIETMASTER KS12J30A?

POSSIBLE CAUSE TO CORRECT
Loss of charge in thermostat bulb. Place jumper across thermostat terminals to check if unit operates. If unit operates, replace the thermostat.
Loose or broken parts in thermostat. Check as above.
Incorrect wiring. Refer to appropriate wiring diagram.

What are the causes of noisy operation from my FRIEDRICH QUIETMASTER KS12J30A?

POSSIBLE CAUSE TO CORRECT
Poorly installed unit. Refer to Installation Instructions for proper installation.
Fan blade striking chassis. Reposition – adjust motor mount.
Compressor vibrating. Check that compressor grommets have not deteriorated.
Improperly mounted or loose cabinet parts. Check that compressor mounting parts are not missing.

Why is my FRIEDRICH QUIETMASTER KS12J30A leaking water into the room?

POSSIBLE CAUSE TO CORRECT
Evaporator drain pan overflowing. Clean obstructed drain trough.
Condensation forming on base pan. Evaporator drain pan broken or cracked. Reseal or replace.
Poor installation resulting in rain entering room. Check installation instructions. Reseal as required.
Condensation on discharge grilles. Dirty evaporator coil – clean. Very high humidity level.

What causes the thermostat on my FRIEDRICH QUIETMASTER KS12J30A to short cycle?

POSSIBLE CAUSE TO CORRECT
Thermostat differential too narrow. Replace thermostat.
Plenum gasket not sealing, allowing discharge air to short cycle the thermostat. Check gasket, reposition or replace.
Restricted coil or dirty filter. Clean and advise customer of periodic cleaning of filter.
Thermostat bulb touching thermostat bulb support bracket. (Applicable models.) Adjust bulb bracket. (Applicable models.)

Why are there prolonged off cycles during automatic operation of my FRIEDRICH QUIETMASTER KS12J30A?

POSSIBLE CAUSE TO CORRECT
Anticipator (resistor) wire disconnected at thermostat or system switch. Refer to appropriate wiring diagram.
Anticipator (resistor shorted or open). (Applicable models.) Replace thermostat block and resistor.
Partial loss of charge in thermostat bulb causing a wide differential. Replace thermostat.

Why is my FRIEDRICH QUIETMASTER KS12J30A leaking water outside?

POSSIBLE CAUSE TO CORRECT
Evaporator drain pan cracked or obstructed. Repair, clean or replace as required.
Water in compressor area. Detach shroud from pan and coil. Clean and remove old sealer. Reseal, reinstall and check.
Obstructed condenser coil. Steam clean.
Fan blade and slinger ring improperly positioned. Adjust fan blade 3/16 to 1/4″ from condenser shroud. Adjust fan motor mount to allow 3/16 to 1/4″ clearance between condenser fan blade and base pan.

What can I do about high indoor humidity when using my FRIEDRICH QUIETMASTER KS12J30A?

POSSIBLE CAUSE TO CORRECT
Insufficient air circulation in air conditioned area. Adjust louvers for best possible air circulation.
Oversized unit. Operate in “Fan-Auto (Moneysaver)” position.
Inadequate vapor barrier in building structure, particularly floors. Advise customer.

What is the switch logic and legend for the wiring diagram of the FRIEDRICH QUIETMASTER KS12J30A?

The following tables explain the components in the wiring diagram and the logic for the system switch positions.

LEGEND

ARANTICIPATOR RESISTOR
MSMONEY SAVER/ROCKER SWITCH
CAPCAPACITOR
COMPRCOMPRESSOR
MTRFAN MOTOR
OVLDOVERLOAD PROTECTOR
SYS SWSYSTEM SWITCH
IDTINDOOR THERMOSTAT

SWITCH LOGIC (X = CLOSED, O = OPEN)

SWITCH POSITION CIRCUIT
1 2 3 4 5
OFF O O O O O
LOW COOL X O O O X
MED COOL X O O X O
HI COOL X O X O O
FAN ONLY O X O O O

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD FRIEDRICH QUIETMASTER KS12J30A (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.