Free English FRIEDRICH QUIETMASTER KS12J10 (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD FRIEDRICH QUIETMASTER KS12J10 (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the specifications for the FRIEDRICH QUIETMASTER J Series models, including the KS12J10?
| SPECIFICATIONS | KS10J10 | KS12J10 | KS12J30A | KM18J30A | KM21J30 | KL25J30A |
|---|---|---|---|---|---|---|
| BTUH | 10000 | 12000 | 12500 / 12500 | 18000 / 18000 | 21000 / 20500 | 25000 / 24700 |
| E.E.R. | 10.3 | 9.5 | 10.0 / 10.0 | 9.6 / 9.6 | 9.0 / 9.0 | 8.3 / 8.2 |
| Volts | 115 | 115 | 230 / 208 | 230 / 208 | 230 / 208 | 230 / 208 |
| Amperes | 9.1 | 10.8 | 5.8 / 6.2 | 8.3 / 9.1 | 10.5 / 11.3 | 13.5 / 15.0 |
| Total Watts | 970 | 1265 | 1250 / 1250 | 1875 / 1875 | 2335 / 2280 | 3010 / 3010 |
| Hertz | 60 | 60 | 60 | 60 | 60 | 60 |
| Fuse/Breaker Size | 15 | 15 | 15 | 15 | 15 | 20 |
| Fan RPM | 1115 | 1080 | 1180 | 1120 | 1120 | 1120 |
| Evaporator Air CFM | 325 | 325 | 325 | 440 | 535 | 610 |
| Fresh Air CFM | Yes | Yes | Yes | Yes | Yes | Yes |
| Exhaust Air CFM | Yes | Yes | Yes | Yes | Yes | Yes |
| Dehumidification Pts/HR | 2.8 | 3.5 | 3.5 | 5.5 | 6.3 | 7.6 |
| Width | 25-15/16″ | 25-15/16″ | 25-15/16″ | 25-15/16″ | 25-15/16″ | 28″ |
| Height | 15-15/16″ | 15-15/16″ | 15-15/16″ | 17-15/16″ | 17-15/16″ | 20-3/16″ |
| Depth | 27-3/8″ | 27-3/8″ | 27-3/8″ | 27-3/8″ | 27-3/8″ | 33-5/8″ |
| Minimum Ext. Into Room | 3-1/16″ | 3-1/16″ | 3-1/16″ | 3-1/16″ | 3-3/16″ | 3-3/16″ |
| Minimum Ext. to Outside | 16-15/16″ | 16-15/16″ | 16-15/16″ | 16-15/16″ | 16-15/16″ | 18-15/16″ |
| Net Weight | 108 | 111 | 111 | 136 | 183 | 190 |
| Shipping Weight | 118 | 121 | 121 | 148 | 203 | 210 |
What is the performance data for the FRIEDRICH QUIETMASTER J Series models, including the KS12J10?
Rating Conditions: 80°F. Room Air Temperature and 50% Relative Humidity with 95°F. Outside Air Temperature at 40% Relative Humidity.
| Cooling | EVAPORATOR AIR TEMP. °F. | OPERATING PRESSURES | ELECTRICAL RATINGS | R-22 REFRIG. | COMP. OIL | |||
|---|---|---|---|---|---|---|---|---|
| DISCHARGE AIR | TEMP. DROP °F | SUCTION | DISCHARGE | AMPS | LOCKED ROTOR AMPS | CHARGE IN OZ. | CHARGE IN FLUID OZ. | |
| KS10J10 | 61.0 | 19.0 | 79.0 | 269 | 9.1 | 48.3 | 21.0 | 11.8 |
| KS12J10 | 57.0 | 23.0 | 78.0 | 288 | 10.8 | 54.0 | 25.0 | 11.8 |
| KS12J30A | 57.0 | 23.0 | 79.0 | 293 | 5.8 / 6.2 | 26.3 | 26.0 | 11.8 |
| KM18J30A | 56.0 | 24.0 | 73.0 | 262 | 8.3 / 9.1 | 42.0 | 46.0 | 13.9 |
| KM21J30 | 56.0 | 24.0 | 75.0 | 260 | 10.5 / 11.3 | 56.0 | 46.0 | 32.0 |
| KL25J30A | 55.0 | 25.0 | 68.5 | 300 | 13.5 / 15.0 | 71.0 | 34.0 | 32.0 |
How do I perform a compressor winding test on my FRIEDRICH QUIETMASTER KS12J10?
First, disconnect electrical power to the unit before servicing. Remove the compressor terminal box cover and disconnect wires from the terminals. Using an ohmmeter, check for continuity across the following terminals:
1. Terminal “C” and “S” – no continuity means there is an open winding and the compressor must be replaced.
2. Terminal “C” and “R” – no continuity means there is an open winding and the compressor must be replaced.
3. Terminal “R” and “S” – no continuity means there is an open winding and the compressor must be replaced.
How do I perform a ground test on the compressor of my FRIEDRICH QUIETMASTER KS12J10?
First, disconnect electrical power to the unit before servicing. Use an ohmmeter set on its highest scale. Touch one lead to the compressor body, ensuring a clean point of contact for a good connection. Touch the other probe in turn to each compressor terminal. If a reading is obtained, the compressor is grounded and must be replaced.
How do I check for compressor inefficiency on my FRIEDRICH QUIETMASTER KS12J10?
Compressor inefficiency is typically caused by broken or damaged suction and/or discharge valves, which reduces the compressor’s ability to pump refrigerant gas. To check for this condition:
1. Install a piercing valve on the suction and discharge or liquid process tube.
2. Attach gauges to the high and low sides of the system.
3. Start the system and run a “cooling or heating performance test.”
If the test shows A) below normal high side pressure, B) above normal low side pressure, and C) low temperature difference across the coil, the compressor valves are faulty and the compressor must be replaced.
How do I test the external thermal overload on my FRIEDRICH QUIETMASTER KS12J10?
To test the external thermal overload on models equipped with one:
1. Remove the overload.
2. Allow time for the overload to reset before attempting to test.
3. Apply ohmmeter probes to the terminals on the overload wires. There should be continuity through the overload if it is functioning correctly.
How do I check the internal thermal overload on my FRIEDRICH QUIETMASTER KS12J10?
The internal overload is embedded in the motor windings. To check it:
1. With no power connected to the unit, remove the leads from the compressor terminals.
2. Using an ohmmeter, test for continuity between terminals C-S and C-R. If there is no continuity, the compressor overload is open, and the compressor must be replaced.
How do I test the fan motor on my FRIEDRICH QUIETMASTER KS12J10?
To test the fan motor:
1. First, determine that the capacitor is serviceable.
2. Disconnect the fan motor wires from the fan speed switch or system switch.
3. Apply “live” test cord probes to the black wire and the common terminal of the capacitor. The motor should run at high speed.
4. Apply “live” test cord probes to the red wire and the common terminal of the capacitor. The motor should run at low speed.
How do I test the run capacitor on my FRIEDRICH QUIETMASTER KS12J10?
To test the run capacitor:
1. Remove the capacitor from the unit.
2. Check for visual damage such as bulges, cracks, or leaks.
3. For a dual-rated capacitor, apply one ohmmeter lead to the common (C) terminal and the other probe to the compressor (HERM) terminal. A satisfactory capacitor will cause the ohmmeter’s pointer to deflect and then gradually move back to infinity.
4. Reverse the leads of the probe and momentarily touch the capacitor terminals. The pointer’s deflection should be twice that of the first check if the capacitor is good.
5. Repeat steps 3 and 4 to check the fan motor side of the capacitor.
NOTE: A shorted capacitor will indicate a low resistance (pointer moves to “0” and stays). An open capacitor will show no movement of the pointer at all.
How do I test the system control switch on my FRIEDRICH QUIETMASTER KS12J10?
First, disconnect the leads from the control switch. Then, check for continuity between the terminals for each position:
“Off” Position: No continuity between any terminals.
“Lo Cool” Position: Continuity between terminals “L1” and “C”, and between “LO” and “MS”.
“Med Cool” Position: Continuity between terminals “L1” and “C”, and between “M” and “MS”.
“Hi Cool” Position: Continuity between terminals “L1” and “C”, and between “H” and “MS”.
“Fan Only” Position: Continuity between terminals “L1” and “2”.
How do I test the thermostat on my FRIEDRICH QUIETMASTER KS12J10?
Remove the wires from the thermostat. Turn the thermostat to its coldest position and check for continuity between the two terminals. Next, turn the thermostat to its warmest position and check that the thermostat contacts open (no continuity). NOTE: The ambient temperature must be within the thermostat’s operating range of 60°F (± 2°) to 92°F (± 4°) for an accurate test.
Can I adjust the thermostat on my FRIEDRICH QUIETMASTER KS12J10?
No attempt should be made to adjust the thermostat. Due to the sensitivity of the internal mechanism and the sophisticated equipment required to check the calibration, it is suggested that the thermostat be replaced rather than calibrated.
How do I test the MoneySaver (Rocker) switch on my FRIEDRICH QUIETMASTER KS12J10?
Disconnect the leads from the switch. Depress the switch to the function you are testing.
1. When YES is depressed, there should be continuity between terminals “1” and “2”.
2. When NO is depressed, there should be continuity between terminals “2” and “3”.
What is the procedure for hermetic component replacement on a FRIEDRICH QUIETMASTER KS12J10?
The following procedure applies when replacing components in the sealed refrigeration circuit (e.g., compressor, condenser, evaporator, capillary tube):
1. Recover the refrigerant from the system at the process tube.
2. Cut the process tube below the pinch off on the suction side of the compressor.
3. Connect a nitrogen tank to the suction process tube.
4. Drift dry nitrogen through the system and unsolder the most distant connection first (e.g., filter drier).
5. Replace the inoperative component and always install a new filter drier. Drift dry nitrogen through the system while making these connections.
6. Pressurize the system to 30 PSIG with proper refrigerant and then boost the pressure to 150 PSIG with dry nitrogen.
7. Leak test the complete system with an electronic halogen leak detector and correct any leaks found.
8. Reduce the system to zero gauge pressure.
9. Connect a vacuum pump to both the high and low sides of the system using deep vacuum hoses.
10. Evacuate the system to a maximum absolute holding pressure of 200 microns or less.
11. Break the vacuum by charging the system from the high side with the correct amount of specified refrigerant. This prevents boiling the oil out of the crankcase.
12. Restart the unit several times, allowing pressures to stabilize. Pinch off the process tubes, cut and solder the ends. Remove the pinch off tool and leak check the process tube ends.
What is the special procedure in case of a motor compressor burn-out on a FRIEDRICH QUIETMASTER KS12J10?
1. Recover all refrigerant and oil from the system.
2. Remove the compressor, capillary tube, and filter drier from the system.
3. Flush the evaporator, condenser, and all connecting tubing with dry nitrogen or an equivalent substance to remove all contamination. Inspect the suction and discharge lines for carbon deposits and clean them if necessary.
4. Reassemble the system, including a new drier strainer and capillary tube.
5. Proceed with processing as outlined under the standard hermetic component replacement procedure.
What are the special considerations for troubleshooting a rotary compressor on a FRIEDRICH QUIETMASTER KS12J10?
1. Due to the spinning motion of the rotary compressor, the mounts are critical. If you notice vibration, check the mounts carefully.
2. The electrical terminals on a rotary compressor are in a different order than on reciprocating compressors. The terminal markings are on the cover gasket. Use your wiring diagram to ensure correct connections.
What is the correct method for charging the refrigerant on a FRIEDRICH QUIETMASTER KS12J10?
The refrigerant charge is extremely critical and must be measured carefully to be as exact as possible to the nameplate charge. The correct method for charging is to introduce liquid refrigerant into the high side of the system while the unit is off. Then, start the compressor and enter the balance of the charge as gas only into the low side. Introducing liquid directly into the low side without a capillary tube will cause damage to the discharge valve of the rotary compressor.
What should I do if the compressor on my FRIEDRICH QUIETMASTER KS12J10 does not run?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Low voltage. | Check for voltage at the compressor. 115 volt and 230 volt units will operate at 10% voltage variance. |
| Thermostat not set cold enough or inoperative. | Set thermostat to the coldest position. Test the thermostat and replace if inoperative. |
| Compressor hums but cuts off on overload. | Hard start compressor. Direct test compressor. If compressor starts, add starting components. |
| Open or shorted compressor windings. | Check for continuity and resistance. |
| Open overload. | Test overload protector and replace if inoperative. |
| Open capacitor. | Test capacitor and replace if inoperative. |
| Inoperative system switch. | Test for continuity in all positions. Replace if inoperative. |
| Broken, loose or incorrect wiring. | Refer to the appropriate wiring diagram to check wiring. |
What should I do if the fan motor on my FRIEDRICH QUIETMASTER KS12J10 does not run?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Inoperative system switch. | Test switch and replace if inoperative. |
| Broken, loose or incorrect wiring. | Refer to the applicable wiring diagram. |
| Open capacitor. | Test capacitor and replace if inoperative. |
| Fan speed switch open. | Test switch and replace if inoperative. |
| Inoperative fan motor. | Test fan motor and replace if inoperative (be sure the internal overload has had time to reset). |
Why does my FRIEDRICH QUIETMASTER KS12J10 not cool, or cool only slightly?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Undersized unit. | Refer to Sizing Charts. |
| Thermostat open or inoperative. | Set to the coldest position. Test the thermostat and replace if necessary. |
| Dirty filter. | Clean as recommended in the Owner’s Manual. |
| Dirty or plugged condenser or evaporator coil. | Use steam or detergents to clean. |
| Poor air circulation in area being cooled. | Adjust discharge air louvers. Use high fan speed. |
| Fresh air or exhaust air door open on applicable models. | Close doors. Instruct customer on the use of this feature. |
| Low capacity – undercharge. | Check for a leak and make the repair. |
| Compressor not pumping properly. | Check amperage draw against the nameplate. If not conclusive, perform a pressure test. |
Why won’t my FRIEDRICH QUIETMASTER KS12J10 run?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Fuse blown or circuit tripped. | Replace the fuse or reset the breaker. If it repeats, check the fuse or breaker size. Check for shorts in unit wiring and components. |
| Power cord not plugged in. | Plug in the power cord. |
| System switch in “Off” position. | Set the switch correctly. |
| Inoperative system switch. | Test for continuity in each switch position. |
| Loose or disconnected wiring at switch or other components. | Check wiring and connections. Reconnect per the wiring diagram. |
Why does the evaporator coil on my FRIEDRICH QUIETMASTER KS12J10 freeze up?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Dirty filter. | Clean as recommended in the Owner’s Manual. |
| Restricted air flow. | Check for a dirty or obstructed coil; clean as required. |
| Inoperative thermostat. | Test for a shorted thermostat or stuck contacts. |
| Short of refrigerant. | De-ice the coil and check for a leak. |
| Inoperative fan motor. | Test the fan motor and replace if inoperative. |
| Partially restricted capillary. | De-ice the coil. Check the temperature differential across the coil. Touch test coil return bends for the same temperature. Test for low running current. |
Why does the compressor on my FRIEDRICH QUIETMASTER KS12J10 run continually and not cycle off?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Excessive heat load. | The unit is undersized. Test the cooling performance of the unit. Replace with a larger unit. |
| Restriction in line. | Check for a partially iced coil. Check the temperature split across the coil. |
| Refrigerant leak. | Check for oil at silver-soldered connections. Check for a partially iced coil. Check the split across the coil. Check for low running amperage. |
| Thermostat contacts stuck. | Check the operation of the thermostat. Replace if contacts remain closed. |
| Thermostat incorrectly wired. | Refer to the appropriate wiring diagram. |
Why doesn’t the thermostat turn off my FRIEDRICH QUIETMASTER KS12J10?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Thermostat contacts stuck. | Replace the thermostat. |
| Thermostat set at the coldest point. | Turn to a higher temperature setting to see if the unit cycles off. |
| Incorrect wiring. | Refer to the appropriate wiring diagram. |
| Unit undersized for the area to be cooled. | Refer to the Sizing Chart. |
Why does the compressor on my FRIEDRICH QUIETMASTER KS12J10 attempt to start, or run for short periods only and cycle on overload?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Overload inoperative. Opens too soon. | Check the operation of the unit. Replace the overload if system operation is satisfactory. |
| Compressor attempts to start before system pressures are equalized. | Allow a minimum of two (2) minutes for pressures to equalize before attempting to restart. Instruct the customer about this waiting period. |
| Low or fluctuating voltage. | Check the voltage with the unit operating. Check for other appliances on the circuit. The air conditioner should be on a separate circuit with proper voltage and fused separately. |
| Incorrect wiring. | Refer to the appropriate wiring diagram. |
| Shorted or incorrect capacitor. | Check by substituting a known good capacitor of the correct rating. |
| Restricted or low air flow through the condenser coil. | Check for proper fan speed or a blocked condenser. |
| Compressor running abnormally hot. | Check for a kinked discharge line or restricted condenser. Check amperage. |
What should I do if the thermostat on my FRIEDRICH QUIETMASTER KS12J10 does not turn the unit on?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Loss of charge in thermostat bulb. | Place a jumper across the thermostat terminals to check if the unit operates. If the unit operates, replace the thermostat. |
| Loose or broken parts in thermostat. | Check as above. |
| Incorrect wiring. | Refer to the appropriate wiring diagram. |
What causes noisy operation in my FRIEDRICH QUIETMASTER KS12J10?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Poorly installed unit. | Refer to the Installation Instructions for proper installation. |
| Fan blade striking chassis. | Reposition – adjust motor mount. |
| Compressor vibrating. | Check that compressor grommets have not deteriorated. |
| Improperly mounted or loose cabinet parts. | Check that compressor mounting parts are not missing. |
Why is water leaking into the room from my FRIEDRICH QUIETMASTER KS12J10?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Evaporator drain pan overflowing. | Clean the obstructed drain trough. |
| Condensation forming on base pan. | The evaporator drain pan is broken or cracked. Reseal or replace. |
| Poor installation resulting in rain entering the room. | Check installation instructions. Reseal as required. |
| Condensation on discharge grilles. | Dirty evaporator coil – clean. This can also be caused by a very high humidity level. |
Why does the thermostat on my FRIEDRICH QUIETMASTER KS12J10 short cycle?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Thermostat differential too narrow. | Replace the thermostat. |
| Plenum gasket not sealing, allowing discharge air to short cycle the thermostat. | Check the gasket, reposition or replace. |
| Restricted coil or dirty filter. | Clean and advise the customer of periodic cleaning of the filter. |
| Thermostat bulb touching thermostat bulb support bracket (applicable models). | Adjust the bulb bracket. |
What causes prolonged off cycles in automatic operation on my FRIEDRICH QUIETMASTER KS12J10?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Anticipator (resistor) wire disconnected at thermostat or system switch. | Refer to the appropriate wiring diagram. |
| Anticipator (resistor shorted or open) (applicable models). | Replace the thermostat block and resistor. |
| Partial loss of charge in thermostat bulb causing a wide differential. | Replace the thermostat. |
What should I do if my FRIEDRICH QUIETMASTER KS12J10 switches from cooling to heating?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Thermostat sticking. | Change the room thermostat. |
| Incorrect wiring. | Refer to the appropriate wiring diagram. |
What causes outside water leaks on my FRIEDRICH QUIETMASTER KS12J10?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Evaporator drain pan cracked or obstructed. | Repair, clean or replace as required. |
| Water in compressor area. | Detach the shroud from the pan and coil. Clean and remove old sealer. Reseal, reinstall and check. |
| Obstructed condenser coil. | Steam clean. |
| Fan blade and slinger ring improperly positioned. | Adjust the fan blade 3/16 to 1/4″ from the condenser shroud. Adjust the fan motor mount to allow 3/16 to 1/4″ clearance between the condenser fan blade and the base pan. |
What should I do about high indoor humidity with my FRIEDRICH QUIETMASTER KS12J10?
| POSSIBLE CAUSE | TO CORRECT |
|---|---|
| Insufficient air circulation in the air conditioned area. | Adjust louvers for best possible air circulation. |
| Oversized unit. | Operate in “Fan-Auto (Moneysaver)” position. |
| Inadequate vapor barrier in building structure, particularly floors. | Advise customer. |
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD FRIEDRICH QUIETMASTER KS12J10 (01) PDF DOCUMENT
