How is the ETC UNISON PARADIGM P-TS7 Wall Mount powered?
The ETC UNISON PARADIGM P-TS7 Wall Mount Touchscreen is powered by either LinkPower with auxiliary power or by PoE (Power over Ethernet 802.3af).
Power Options:
• Echelon® LinkPower® (LinkConnect) control network using Belden 8471 (or approved equal) and 24 Vdc Auxiliary power (two 16 AWG 1.5mm²) wires.
• PoE (Power Over Ethernet 802.3af) using Category 5 cable (or approved equal).
Control wiring should only be installed and terminated by a qualified technician and should follow standard wiring installation practices. Leave approximately 10 inches (254mm) of wiring in the backbox for connection and to allow slack for future service needs.
What backboxes are available for the ETC UNISON PARADIGM P-TS7?
The following backboxes are available for the ETC UNISON PARADIGM P-TS7:
| Model | Description |
|---|---|
| P-LCD-FBB | Paradigm Touchscreen flush mount backbox |
| P-LCD-SBB | Paradigm Touchscreen surface mount backbox |
How do I install the backbox collar for the ETC UNISON PARADIGM P-TS7?
To install the collar into the backbox for your ETC UNISON PARADIGM P-TS7, follow these steps:
Step 1: For flush mount applications, thread the four M3 depth adjustment screws into the collar. For surface mount applications, do not use these adjustment screws.
Step 2: Insert the collar so that the touchscreen mounting pins are at the top.
Step 3: For flush mount, turn the depth adjustment screws (if required) so that the cover is even against the wall surface.
Step 4: Insert the four M4 mounting screws through the collar and tighten into the holes in the backbox.
What are the important precautions when installing the termination PCB for the ETC UNISON PARADIGM P-TS7?
When installing the termination PCB for your ETC UNISON PARADIGM P-TS7, please observe the following cautions:
• Only one network type (LON or Ethernet) may be connected to the touchscreen at a time. Do not connect both Auxiliary power and PoE.
• ETC requires that all backboxes and touchscreens are grounded in accordance with local electrical codes.
• The RJ11 connection must be used to provide a ground connection from the backbox to the touchscreen even when Ethernet connectivity is used.
How do I connect an Ethernet cable to the ETC UNISON PARADIGM P-TS7?
Note: All Ethernet terminations must follow IEEE 802.3 and be terminated to the T568B standard.
Step 1: Terminate the network wiring in the RJ45 punch down strip using a standard 110 punch down tool (not provided). Reference the connector label for the CAT5e wire termination color code. The punch down connector provides insulation displacement. Do not pre-strip wire.
Step 2: Snap the connector into the bracket.
How do I connect LinkPower and Auxiliary Power to the ETC UNISON PARADIGM P-TS7?
Use the provided WAGO CAGE CLAMP® connectors to terminate the wiring to the provided LinkPower and Auxiliary power pigtails. Strip the ends of each wire (both installed control wires and pigtail wires) approximately 3/8″ (10mm).
Step 1: Terminate the installed LinkPower wiring to the white and black LinkPower pigtail. Using two Wago connectors connect (typically white) installed wire(s) with white pigtail wire and connect the (typically black) installed wire(s) with black pigtail wire.
Step 2: Plug the LinkPower connector into the LinkPower receptacle on the termination PCB.
Step 3: Terminate the installed Auxiliary power conductor to the red and black Auxiliary power pigtail wires. Using two Wago connectors connect the (typically red) installed wire(s) with red pigtail wire and connect the (typically black) installed wire(s) with black pigtail wire as shown above.
Step 4: Plug the Auxiliary power connector into the Aux power receptacle on the termination PCB.
Step 5: A ground connection is required for all touchscreen assemblies. If the backbox is not already grounded, attach the ground wire to the ground spade on the PCB.
How do I install the termination PCB into the backbox for the ETC UNISON PARADIGM P-TS7?
Step 1: Position the termination PCB on the four standoffs in the backbox and secure with two M3x10mm pan head screws on the RJ11 side of the PCB only.
Note: The termination PCB can be installed in any orientation to accommodate wiring.
Step 2: Place the bracket and RJ45 assembly (if used) on top of the PCB. Secure the PCB to the backbox through the remaining holes in the PCB with two M3x10mm pan head screws.
How do I install the touchscreen onto the collar of the ETC UNISON PARADIGM P-TS7?
The touchscreen bracket is designed for two positions, service and operation. Follow these steps to install the touchscreen:
Step 1: Install the RJ11 control cable provided in the installation kit to the RJ11 jack on the PCB. Also attach the RJ45 control cable if ethernet will be used for communication and power.
Note: The RJ11 cable provides the ground connection to the back box and must always be installed.
Step 2: Plug the other end of the cable(s) into the touchscreen.
Step 3: Hold the touchscreen at a slight angle, insert the top of the unit into the collar and hook the bracket onto the pins on each side of the collar. When installed so that the pins are in the first slots on the bracket, the touchscreen is held out at the bottom for service (service position).
Step 4: To move the touchscreen from the service position to the operation position, lift to unhook the pins and rotate the bottom inward until the touchscreen face is vertical.
Step 5: Apply firm pressure simultaneously to the center of the left and right edges of the touchscreen, pushing the unit inward until it audibly snaps onto the collar. When properly installed, the touchscreen should not easily unsnap from the collar.
How do I remove the ETC UNISON PARADIGM P-TS7 touchscreen from its collar?
To remove the ETC UNISON PARADIGM P-TS7 touchscreen, insert a flat bladed screwdriver into the pry slot and unsnap the touchscreen from the collar. Then lift the bottom upward slightly and rotate outward.
What do the indicators on the bottom of the ETC UNISON PARADIGM P-TS7 show?
After the ETC UNISON PARADIGM P-TS7 touchscreen has been powered up, the appropriate LEDs on the service panel on the bottom of the touchscreen illuminate. The LCD will display a startup screen a few seconds after booting. The service panel includes:
• Pry slot
• USB Port
• SD card slot
• Status LED
• LON LED
• Net LED
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD ETC UNISON PARADIGM P-TS7 (01) PDF DOCUMENT