DANFOSS AME 113 NLX SD (01) Image

FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF DOCUMENT.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF USER GUIDE.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF USER MANUAL.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF OWNER GUIDE.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF OWNER MANUAL.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF REFERENCE GUIDE.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF REFERENCE MANUAL.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH DANFOSS AME 113 NLX SD (01) PDF OPERATING INSTRUCTIONS.


CLICK HERE TO DOWNLOAD DANFOSS AME 113 NLX SD (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What important safety instructions should be followed for the DANFOSS AME 113 NLX SD?

To avoid injury and damage to the DANFOSS AME 113 NLX SD, it is absolutely necessary to read and observe the instructions carefully.

The device is supplied with 24V (safe voltage). To avoid electric shocks, all connections should be made according to existing regulations.

The device must be connected to a DC supply according to EN 61558-1 or EN 61558-2-6 or EN 61558-2-16. For AC supply, a transformer according to EN 61558-1 or EN 61558-2-6 must be used.


What should be checked before assembling the DANFOSS AME 113 NLX SD onto a valve?

Only operate the DANFOSS AME 113 NLX SD on a connected valve.

Before installing the actuator, make sure the nut on the valve is tight.


How do I assemble the DANFOSS AME 113 NLX SD?

Follow these steps for assembly:

1. Place the actuator on the valve.

2. Tighten the nut to secure the actuator to the valve body.

3. Connect the wiring according to the wiring diagram.

4. Place the cover back on the actuator.


What is important to know about long-term storage of the DANFOSS AME 113 NLX SD?

Please note that the battery will discharge during long-term storage of the DANFOSS AME 113 NLX SD.


How do I charge the battery for the DANFOSS AME 113 NLX SD?

The battery for the DANFOSS AME 113 NLX SD should be charged in advance. The approximate battery charging time is 20 hours.


How do I connect the wiring for the DANFOSS AME 113 NLX SD?

Connect the device according to the wiring diagram. The wire colors for the DANFOSS AME 113 NLX SD are as follows:

AME 113 NLX Main Connection:

Black: 24V AC/DC ~

Black/White: 24V AC/DC ⏚ / Common ground

Red: 0-10V Control signal

NLX Feedback Connection:

Yellow: 0-10V Feedback signal

Yellow/White: ⏚ / Common ground


How does the initialisation process for the DANFOSS AME 113 NLX SD work?

Initialisation for the DANFOSS AME 113 NLX SD starts automatically after it is connected to the power supply. The process takes between 2-3 to 15 minutes.

During initialisation, the actuator moves to one end position and then to the other. After this cycle, the actuator is ready for operation.

Note: For initialisation to complete successfully, the battery must be charged. If it fails to initialise after more than one attempt, replace the device.


How can I manually adjust the DANFOSS AME 113 NLX SD?

The manual overriding button is located under the cover of the DANFOSS AME 113 NLX SD.

1. Push and hold the manual overriding button.

2. To move the actuator spindle up, turn the screwdriver counterclockwise until the stop is reached.

3. To move the actuator spindle down, turn the screwdriver clockwise.


What do the indicators on the function display of the DANFOSS AME 113 NLX SD represent?

The function display consists of the following components:

A – Button

B – LEDs

C – LED 1 / LED 2 indicators for status


What do the symbols on the function display of the DANFOSS AME 113 NLX SD mean?

Symbol Description
Clicking direction on
Clicking direction off
0 – 10 V Control voltage
0 – 10 V Feedback

*Initialization: Visual alternative information on display is shown (duration approx. 20 min., several movements).


What do the LED status lights on the DANFOSS AME 113 NLX SD indicate?

LED 2 LED 1 Description
Off Off No power
Green (Flashes) Green Normal operation, parking position is running
Green Green Ready for operation, battery is charging
Green Off No operation
Orange (flashing) Orange (flashing) Alternating display
Red (flashing) Red (flashing) Error. If it doesn’t connect more than once, replace the device.

*On initialisation: Alternating display (Green – Orange) for 20 minutes. If the problem persists, replace the device.

**For initialisation, the battery must be charged and connect more than once, replace the device.


What are the selectable back channel settings for the DANFOSS AME 113 NLX SD?

The following settings are available for the back channel:

Tension Description
0 – 5 V Proportional at stroke
0 – 10 V Proportional at stroke
2 – 10 V Proportional at stroke
5 V End switch
9.5 V Internal fault
0 V Normal status during initialisation

What are the selectable speed settings for the DANFOSS AME 113 NLX SD?

The selectable speed settings are 3 s/mm, 8 s/mm, and 12 s/mm.


What are the selectable settings for the test mode on the DANFOSS AME 113 NLX SD?

The following settings are available for the test mode:

Tension Description
0 – 5 V Proportional upon closing
0 – 10 V Proportional upon closing
2 – 10 V Proportional upon closing
5 V Stroke up
9.5 V Internal failure
0 V Normal status during initialisation

What are the technical specifications for the DANFOSS AME 113 NLX SD?

Voltage 24 V AC, -10% … +20%, 50-60 Hz
24 V DC, -10% … +20%
Power consumption 5 VA / 2 W
Control signal 0-10 V (Ri=24 kΩ), 2-10 V (Ri=24 kΩ)
0-20 mA (Ri=500 kΩ), 4-20 mA (Ri=500 kΩ)
Feedback signal 0-10 V
Output current 2 mA
Actuator speed 3 s/mm, 8 s/mm, 12 s/mm
Thrust 400 N
Stroke 15 mm
Ambient temperature 0 … +50 °C
Storage temperature -20 °C … +60 °C
Dimensions 147 x 65 x 82 mm

What is the active control signal range for the DANFOSS AME 113 NLX SD?

The active voltage control range for the DANFOSS AME 113 NLX SD is from 1 V to 9 V. Signals below 1 V or above 9 V will drive the valve to its fully closed or fully open positions, respectively.


How does the feedback signal relate to the valve stroke on the DANFOSS AME 113 NLX SD?

For the DANFOSS AME 113 NLX SD, the feedback signal is proportional to the valve stroke. As the valve stroke increases (moves from 0% to 100%), the feedback signal (Y control) increases linearly from 0 V to 10 V.


How is the DANFOSS AME 113 NLX SD disassembled?

Disassembly of the DANFOSS AME 113 NLX SD is performed in the reverse order of assembly. First, remove the cover, then disconnect the wiring, and finally, loosen the nut to remove the actuator from the valve.


How can I secure the DANFOSS AME 113 NLX SD using the antitheft device?

To use the antitheft feature, insert and tighten the provided screw on the side of the DANFOSS AME 113 NLX SD. This will secure the actuator and help prevent unauthorized removal.


CLICK HERE TO DOWNLOAD DANFOSS AME 113 NLX SD (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.