How is the additional refrigerant charge calculated for the TOSHIBA CARRIER MMY-MUP096H1HT6PUL?

The additional amount of refrigerant charge is calculated using the following formula: [1] + [2] + [3] + [4].

[1] Compensation amount based on outdoor unit capacity type (Table 2).

[2] Additional amount based on liquid pipe size: Real length of liquid pipe × Additional amount of refrigerant charge per foot (Table 3).

[3] Additional amount of refrigerant for indoor units (Table 4).

[4] Corrected amount of refrigerant based on outdoor unit diversity (Table 5).

For the TOSHIBA CARRIER MMY-MUP096H1HT6PUL, the amount of refrigerant charged in the factory is 19.8 lbs (9.0 kg). If the result of the calculation is minus, use the unit without additional refrigerant.

Table 3: Additional refrigerant charge based on liquid pipe size

Liquid pipe diameter (in) 1/4″ 3/8″ 1/2″ 5/8″ 3/4″ 7/8″
Additional amount (lbs/ft) 0.017 0.037 0.071 0.108 0.168 0.235

Table 4: Additional refrigerant for indoor unit capacity codes

Indoor unit capacity code 7.5 to 9.5 12 to 27 30 to 54 72 to 96
Additional amount (lbs) 0.44 0.88 1.32 2.20

How do I perform an automatic address setup for the TOSHIBA CARRIER MMY-MUP096H1HT6PUL?

Follow these steps to set up the address automatically:

1. Turn on the indoor units first, then turn on the outdoor units.

2. Wait about 1 minute after powering on and confirm the 7-segment display on the interface P.C. board of the header outdoor unit indicates “U. 1. Err” and “L08” alternately at 1-second intervals.

3. Push SW06 on the header unit interface P.C. board for more than 1 second to start the setup.

4. The display will indicate “Auto 1” → “Auto 2” → “Auto 3”.

5. The setting is complete when the display changes to “U. 1. – – -” (flashing or light).


What is the manual address setup procedure using a remote controller for the TOSHIBA CARRIER MMY-MUP096H1HT6PUL?

To set up addresses manually from a wired remote controller (RBC-AMT*), follow this procedure:

1. Push the SET + CL + TEST buttons simultaneously for 4 seconds or more. The LCD will begin blinking.

2. Set the Refrigerant line address: Use the TEMP buttons to set DN code to 12. Use the TIME buttons to set the line address (matching the header unit interface P.C. board), then push SET.

3. Set the Indoor address: Use the TEMP buttons to set DN code to 13. Use the TIME buttons to set the indoor address (0001 to 0128 for TU2C-LINK), then push SET.

4. Set the Group address: Use the TEMP buttons to set DN code to 14. Use the TIME buttons to set Individual (0000), Header unit (0001), or Follower unit (0002), then push SET.

5. Set the Central control address: Use the TEMP buttons to set DN code to 03. Use the TIME buttons to set the central control address, then push SET.

6. Push the TEST button to finish. “Setting up” will blink and then go off when operation is possible.


How do I start a cooling or heating test operation from the outdoor unit of the TOSHIBA CARRIER MMY-MUP096H1HT6PUL?

Test operations can be initiated from the interface P.C. board of the header unit:

For Cooling Test Operation:

1. Set rotary switches SW01/SW02/SW03 to [2/5/1]. Section A of the display shows “C.”.

2. Push push-switch SW04 for 2 seconds or more. The display Section B shows “- C” and operation starts.

For Heating Test Operation:

1. Set rotary switches SW01/SW02/SW03 to [2/6/1]. Section A shows “H.”.

2. Push push-switch SW04 for 2 seconds or more. Section B shows “- H” and operation starts.

To stop the test run, return SW01/SW02/SW03 to [1/1/1] or push SW05 for 2 seconds or more. Note that test operations automatically return to normal operation after 60 minutes.


What are the common check codes and typical problem sites for the TOSHIBA CARRIER MMY-MUP096H1HT6PUL?

The following table lists common check codes detected by the outdoor interface:

Check Code Problem Site Description
E06 Signal lack of indoor unit Indoor units initially communicating normally fail to return signal.
F04 Outdoor discharge temp sensor (TD1) Sensor has been open/short-circuited.
H01 Compressor breakdown Inverter current (Idc) detection circuit detects overcurrent.
H02 Compressor trouble (lockup) Compressor lockup is detected.
L08 Indoor group address not set Address setting has not been performed for one or more indoor units.
P04 High-pressure SW activation Outdoor high-pressure switch is activated.
P10 Indoor unit overflow Indoor unit has been shut down due to detection of overflow.

How do I clear check codes for the TOSHIBA CARRIER MMY-MUP096H1HT6PUL?

To clear currently detected check codes from the header unit interface board:

1. Set the rotary switches SW01/SW02/SW03 to [2/16/1]. The display shows “Er”.

2. Push the push-switch SW04 for 5 seconds or more.

3. When “CL” is displayed in the 7-segment display for 5 seconds, the check code is completely cleared.

4. Return the rotary switches to [1/1/1] after completion.


How do I set the priority operation mode for the TOSHIBA CARRIER MMY-MUP096H1HT6PUL?

The priority operation mode is set using Outdoor Unit Function Code (O.DN) [18] on the header unit:

O.DN [18] = 0000: Priority heating (factory default).

O.DN [18] = 0001: Priority cooling.

O.DN [18] = 0002: Priority based on number of units in operation (mode with the largest share gets priority).

O.DN [18] = 0003: Priority indoor unit (priority given to the specific indoor unit address set for priority).


What is the procedure for refrigerant recovery (reclaim) if the TOSHIBA CARRIER MMY-MUP096H1HT6PUL can be energized?

If the troubled outdoor unit can be turned on, follow Refrigerant Recovery Procedure A:

1. Connect the check joint of the liquid pipe and the low pressure-side check joint using a charge hose and purge the hose of air.

2. Fully close the liquid pipe service valve of the troubled outdoor unit, leaving the gas pipe service valve fully open.

3. Set SW01/02/03 on the interface board of the failed unit to [2/11/1]. “rd” will be displayed.

4. Push SW04 and hold for 5 seconds or more. The display will show “rd FF” and reclaim operation starts.

5. After approximately 20 minutes, fully close the gas pipe service valve of the troubled unit.

6. Push SW05 on the interface board to finish the reclaim operation.

7. Turn off the power and recover residual refrigerant using a recovery device.