How is the FIREYE MP230 installed into the chassis?
WARNING: Remove power from the control and remove the control from its wiring base before proceeding.
The FIREYE MP230 and related programmer modules are used with the Fireye modular M-Series II Chassis. They are installed in the chassis by grabbing hold of the programmer module by the ridged finger grips on the side on the module, aligning the module with the guide slots on the opening farthest from the transformer, and inserting the module into the pin connectors. The programmer modules are designed to fit in the proper slot only. DO NOT FORCE THEM.
How do I select the correct programmer module features for the FIREYE MP230 series?
The operational characteristics of the control are determined by the selection of the programmer module. The following table outlines the descriptions for various part numbers:
| Part Number | DESCRIPTION |
|---|---|
| MP100/MP100E | Relight operation. |
| MP101 | Same as MP100, except will ignore flame signal in off cycle. |
| MP102/MP102E | Operates like the MP100, except the standing pilot and relight features are eliminated. Ignition safety time is 5 seconds. Control will lockout on flame failure. |
| MP230 | Selectable purge timing, trial-for-ignition timing, and recycle/non-recycle operation. |
| MP230H | Selectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition. For use with two-stage burners. |
| MP560 | Selectable purge timing, pilot-trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch. |
| MP561 | Selectable purge timing, pilot-trial-for-ignition timing, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch. |
| MP562 | Same as MP560, with lockout on loss of air flow. Non-recycle operation. |
Note: Programmers with the suffix “E” (e.g. MP100E) are for use with the MC230 and MC230R chassis only.
Where is the fuse located on the FIREYE MP230 and how is it replaced?
The programmer modules are designed with a field-replaceable fuse located on the printed circuit board near the connectors. In the event the fuse opens, remove the fuse using a small screwdriver and install a replacement.
What causes the fuse to open on the FIREYE MP230?
The fuse will open as a result of an overload condition on terminals 3, 4, or 5.
What are the correct replacement fuse specifications for the FIREYE MP230?
For standard programmers, use a Fireye replacement fuse (P/N 23-176) or equivalent 2AG, 8 amp fuse (e.g. Littlefuse #225008).
For programmers used with the MC230 and MC230R chassis, use replacement fuse P/N 23-183 or equivalent (3.5 amp, 2AG, SLO-BLO) Littlefuse #22903.5.
Does the FIREYE MP230 possess specific agency approvals?
Yes. The following table lists the agency approvals for the FIREYE MP230 and other modules:
| Part Number | UL | CSA | FM | EN298 |
|---|---|---|---|---|
| MP100 | Yes | Yes | Yes | Yes |
| MP100E | Yes | |||
| MP101 | Yes | Yes | Yes | |
| MP102 | Yes | |||
| MP102E | Yes | |||
| MP230 | Yes | Yes | Yes | |
| MP230H | Yes | Yes | Yes | |
| MP560 | Yes | Yes | Yes | |
| MP561 | Yes | Yes | Yes | |
| MP562 | Yes | Yes | Yes |
Note: Approvals do not apply to MC230 and MC230R Chassis and associated programmers.
What visual indicators are available on the FIREYE MP230?
LED indicator lights are on all programmer modules, indicating the operating status of the control.
How is the Flame Failure Response Time (FFRT) determined for the FIREYE MP230?
Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module.
Does the FIREYE MP230 have dipswitches?
Some programmer modules (MP230, MP230H, MP560, MP561, and MP562) are equipped with a series of dipswitches to select Purge Timing, Pilot Trial for Ignition (PTFI) Timing, and Recycle or Non-Recycle operation.
Is there a check-run switch on the FIREYE MP230?
A “check-run” switch is provided on the MP560, MP561, and MP562 programmer modules to assist in testing size and stabilization of the pilot. The MP230 does not explicitly list a check-run switch in its description.