Free English EMERSON BETTIS XTE3000 (01) PDF Document. Free English EMERSON BETTIS XTE3000 (01) PDF User Guide. Free English EMERSON BETTIS XTE3000 (01) PDF User Manual. Free English EMERSON BETTIS XTE3000 (01) PDF Owner Guide. Free English EMERSON BETTIS XTE3000 (01) PDF Owner Manual. Free English EMERSON BETTIS XTE3000 (01) PDF Reference Guide. Free English EMERSON BETTIS XTE3000 (01) PDF Instruction Guide. Free English EMERSON BETTIS XTE3000 (01) PDF Reference Manual. Free English EMERSON BETTIS XTE3000 (01) PDF Instruction Manual. Free English EMERSON BETTIS XTE3000 (01) PDF Operating Instructions.
CLICK HERE TO DOWNLOAD EMERSON BETTIS XTE3000 (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What is the SLEEP function on the EMERSON BETTIS XTE3000 electric actuator?
The SLEEP function on the EMERSON BETTIS XTE3000 is a feature that reduces power consumption from the electronics when the actuator is not moving. This is particularly useful when the actuator is powered by a battery and solar panel, especially in applications where valve travel events are infrequent. In such cases, the solar panels recharge the battery and power the actuator’s electronics while the motor is off. Since the motor’s run time is a small fraction of the total time, the energy needed to power the electronics during the rest phase is significant. By reducing the energy requirements when the motor is off, the SLEEP function allows for the use of a smaller solar panel.
What conditions are required to activate the SLEEP function on my EMERSON BETTIS XTE3000?
The SLEEP function on the EMERSON BETTIS XTE3000 is activated when the following conditions are met:
• Parameter SLEEP in the “Actuator Setup” menu, “Restricted” section: ENABLED
• Firmware releases of microprocessors of BASE card:
– >= 9.00 for H8S
– >= 7.00 for PIC
• Firmware release of microprocessors of TERMINAL BOARD card:
– >= 6.0 for PIC
• Parameter SW TYPE in the “Actuator Setup” menu, “Restricted” section: XTE
• Parameter POSITIONER in the “Actuator Setup” menu, “Restricted” section: DISABLED
• Parameter HW CONFIG in the “Actuator Setup” menu, “Restricted” section: BASE
• Parameter BACKLIGHT in the “Actuator Setup” menu, “Restricted” section: AUTO
• Parameter POWER TYPE in the “Nameplate” menu, “Power Supply” section: DC
Under what conditions does the EMERSON BETTIS XTE3000 switch to SLEEP mode?
The EMERSON BETTIS XTE3000 electronics switch to SLEEP status under the following conditions:
• 30 seconds after the end of the last command (OPEN, CLOSE, ESD) via remote control
• 2 minutes after the last operation on the local interface of the actuator (local selector and push buttons)
• 30 seconds after closure of Bluetooth or RS232 communication channel (if present)
• 255 seconds after closure of IrDA communication channel (if enabled)
How does the EMERSON BETTIS XTE3000 exit from SLEEP mode?
The EMERSON BETTIS XTE3000 electronics exit from SLEEP status when:
• A command via remote control OPEN, CLOSE, ESD is given (duration of command: > 0.7 second)
• The actuator local interface (local push buttons or selector) is operated (duration of command: >1 second)
• There is a change of position > 5% via manual operation (handwheel)
When the XTE3000 exits from SLEEP mode, all functions are restored and the actuator is available for normal operation.
What is the status of the EMERSON BETTIS XTE3000 when it is in SLEEP mode?
When the EMERSON BETTIS XTE3000 is in SLEEP mode:
• The alphanumeric display of the actuator shows the message “SLEEP”
• Auxiliary relays AS1, AS7 do not change
• Auxiliary relay AS8 is de-energized
• Monitor Relay status is as follows:
– de-energized if parameter “MR in SLEEP” in “Actuator Setup” menu, “Restricted” section is “OFF” (with local selector in REMOTE)
– energized if parameter “MR in SLEEP” in “Actuator Setup” menu, “Restricted” section is “ON” (with local selector in REMOTE)
• Any internal heater on the electronic cards are OFF
What is the current consumption of the EMERSON BETTIS XTE3000 in SLEEP mode?
The minimum current consumption is obtained with an actuator without a 4 – 20 mA position re-transmission card and with the parameter “MR in SLEEP” in the “Actuator Setup” menu, “Restricted” section set to “OFF”. In this configuration, the current consumption measured on an XTE3000 supplied at 24 V DC is 58 mA, which corresponds to 1.4 W.
• If the actuator is equipped with a 4 – 20 mA position transmitter module, the current consumption is 78 mA.
• If the parameter “MR in SLEEP” in the “Actuator Setup” menu, “Restricted” section is set to “ON”, the current consumption is 98 mA (2.4 W at 24 V DC).
When the actuator exits from SLEEP mode, all XTE3000 functions are restored to normal operation and the current consumption returns to normal.