FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF DOCUMENT.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF USER GUIDE.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF USER MANUAL.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF OWNER GUIDE.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF OWNER MANUAL.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF REFERENCE GUIDE.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF REFERENCE MANUAL.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH DANFOSS AME 113 NL SD (01) PDF OPERATING INSTRUCTIONS.
CLICK HERE TO DOWNLOAD DANFOSS AME 113 NL SD (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What safety precautions should be followed before installing the DANFOSS AME 113 NL SD?
To avoid injury and damage to the DANFOSS AME 113 NL SD, the following instructions must be carefully read and observed before installation and commissioning.
What are the power supply and installation environment requirements for the DANFOSS AME 113 NL SD?
To avoid voltage failure, supply the DANFOSS AME 113 NL SD actuator from a separate safety isolation transformer (for DC supply) according to EN 61558-2-6, or with double insulation (for AC supply) according to EN 61558-2-6. The actuator must be installed in an environment which meets the requirements of the EN 60730-1 standard for control contamination degree 2 (or better) with impulse voltages up to 2.5 kV.
How do I mount the DANFOSS AME 113 NL SD?
The mounting process for the DANFOSS AME 113 NL SD involves two main steps as illustrated in the diagrams:
1. Attach the actuator securely onto the valve body.
2. Connect the electrical wiring according to the specified connection diagram.
How do I wire the DANFOSS AME 113 NL SD?
For the DANFOSS AME 113 NL SD, wiring is as follows:
24V AC/DC ~ :
Black wire: Common ground
Red wire: 24V supply
Feedback 0-10V:
For the NLX model, the wiring is:
Yellow wire: Position feedback (y-pos. 0-10 V)
Pink wire: Position feedback (y-pos. 2-10 V)
What is the initialisation process for the DANFOSS AME 113 NL SD after powering on?
After being powered on, the DANFOSS AME 113 NL SD will undergo an initialisation process. This process takes approximately 2-3 minutes, followed by an additional 15 minutes.
How do I manually adjust the DANFOSS AME 113 NL SD?
To manually adjust the DANFOSS AME 113 NL SD when the power cord is not connected:
Turn the screwdriver clockwise to open the valve.
Turn the screwdriver counterclockwise to close the valve.
What should I know about the battery in the DANFOSS AME 113 NL SD?
The DANFOSS AME 113 NL SD is equipped with a rechargeable battery that conforms to the EN 62133-2 standard. The device should only be opened in a clean and dry place. The battery can only be replaced by trained personnel.
What do the main indicators on the function display of the DANFOSS AME 113 NL SD mean?
The main function display shows the following:
A: Error
B: Direction
C: Command 1
What do the secondary symbols on the display of the DANFOSS AME 113 NL SD represent?
The display can show various symbols to indicate the current function or status of the DANFOSS AME 113 NL SD:
| Symbol | Description |
|---|---|
| Clicking direction on | Indicates the direction of movement. |
| Override signal on | Indicates that a manual override is active. |
| Control voltage | Indicates the current control voltage level (0-10 V). |
| External button | Indicates that an external button has been pressed. |
How do I interpret the LED light status on the DANFOSS AME 113 NL SD?
The LED indicator provides information on the status of the DANFOSS AME 113 NL SD. On first power-up, the green LED will flash for a maximum of 20 minutes while the battery is charging; the actuator can be operated normally during this time.
| LED | Description |
|---|---|
| Green (flashing) | Initialisation, parking battery is charging. |
| Green (stable) | Ready for operation, battery is charged. |
| Orange (flashing) | No operation. Alternating display shows reason. |
| Red (stable) | Internal failure, please restart and check the cabling. If the error occurs more than once, replace the device. |
How do I disassemble the DANFOSS AME 113 NL SD?
To disassemble the DANFOSS AME 113 NL SD, reverse the mounting steps. Ensure the device is powered off before starting the disassembly process.
Does the DANFOSS AME 113 NL SD have an antitheft feature?
Yes, the DANFOSS AME 113 NL SD is equipped with an antitheft device for protection.
What are the technical specifications of the DANFOSS AME 113 NL SD?
| Parameter | Value |
|---|---|
| Supply voltage | 24 V AC, –10% … +20%, 50-60 Hz 24 V DC, –10% … +20% |
| Power consumption | 5 VA / 2 W |
| Control signal | 0-10 V |
| Feedback signal | 0-10 V |
| Output data | 1 mA Ri ext. < 1000 kΩ Ri int. < 10 kΩ |
| Stroke | 15 mm |
| Force | 450 N |
| Speed | 11-15 s/mm |
| Ambient temperature | 0 °C … +55 °C |
| Storage temperature | -20 °C … +65 °C |
| Protection class | IP 54 |
| Weight | 0.9 kg |