Free English CARRIER TRANSICOLD AIRV 68RV14102A (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD CARRIER TRANSICOLD AIRV 68RV14102A (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the general safety notices for the CARRIER TRANSICOLD AIRV 68RV14102A?
The following are recommended precautions that must be understood and applied during the operation and maintenance of your CARRIER TRANSICOLD AIRV 68RV14102A.
FIRST AID
An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.
OPERATING PRECAUTIONS
• Always wear safety glasses.
• Keep hands clear of the evaporator blower and condenser fan.
• No work should be performed on the unit until all circuit breakers and start-stop switches are turned off, and the power supply is disconnected.
• Always work in pairs. Never work alone.
• In case of severe vibration or unusual noise, stop the unit and investigate.
MAINTENANCE PRECAUTIONS
• Beware of unannounced starting of the evaporator blower & condenser fan. Do not remove the ceiling grill assembly or the upper unit cover assembly before turning the power off, and disconnecting the power supply. Before disconnecting, discharge capacitors by shorting across the capacitor terminals.
• When disassembling wiring, use numbered stickers to identify wire leads and terminals. This aids in quick, accurate reassembly.
• Be sure power is turned off before working on motors, controllers, or electrical control switches. Tag any circuit breakers and power supply to prevent accidental energizing of circuits.
• Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems with the system should be diagnosed and any necessary repairs must be performed by qualified service personnel.
• In case of electrical fire, open circuit switch and extinguish with CO2 (never use water).
• Use dry nitrogen to pressurize the system for leak checking. Be careful not to exceed 150 psig test pressure in the hermetic compressor.
• Coil fins are sharp. Use care when removing the cover from the base pan to avoid personal injury.
• Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use.
• Disconnect power to the AirV unit before checking the capacitor.
How is the CARRIER TRANSICOLD AIRV 68RV14102A system identified by its serial number?
Separate part numbers and serial numbers are provided for the upper and lower unit assemblies. The numbers can be found on plates readable from inside the vehicle.
The first two numbers of the serial number indicate the week the unit was manufactured. For example, 01 would designate the first week of the year, and 52 would designate the last week of the year.
The third and fourth numbers designate the year in which the unit was manufactured. For example, 99 would represent the year 1999, 00 the year 2000, and so on.
The letter Y and all the numbers after it designate the unit serial number. For example, a serial number of 1303Y12345 means the unit was manufactured in the 13th week of 2003 and has the serial number Y12345.
What are the component specifications for the CARRIER TRANSICOLD AIRV 68RV14102A system?
Refrigerant Charge
• Standard – High Capacity – Heat Pump: R-22 – 15.9 Ounces
• Low Profile (All): R-22 – 16.9 Ounces
Compressor – 115 Volts, 60 Cycles, 1 Phase
NOTE: AirV Compressor mounting bolts must be torqued to 15/17 ft./lbs.
• Locked Rotor Amps – Standard – High Capacity – Heat Pump: 60.0 AMPS
• Locked Rotor Amps – Low Profile High Capacity: 59.0 AMPS
• Fully Loaded Amps – Standard: Cooling – Approx. 12.8 AMPS, Heating – N/A
• Fully Loaded Amps – High Capacity: Cooling – Approx. 14.1 AMPS, Heating – Approx. 11 AMPS
• Fully Loaded Amps – Low Profile: Cooling – Approx. 13.4 AMPS, Heating – Approx. 13.8 AMPS
• Fully Loaded Amps – Heat Pump: Cooling – Approx. 12.9 AMPS, Heating – Approx. 13.8 AMPS
Compressor – 220 Volts, 50 Cycles, 1 Phase
• Locked Rotor Amps: 23.6 AMPS
Thermostat Range (All Free Blow Units)
• 61° F (16° C) to 89° F (32° C)
Return Air Sensor (Thermistor)
The Return-Air-Sensor (Thermistor) is part of the PCB Main Assembly. The sensor has a yellow coating and protrudes about 3/16 inch through the ceiling panel when installed. Refer to the resistance table for values.
Heat Pump Sensors (Thermistors)
The Heat Pump systems have an (ODA) outdoor air thermistor and a (ODC) outdoor coil thermistor, both located in the upper unit, and a (IDC) indoor coil thermistor located in the ceiling unit. Resistance values for these thermistors can be found in the provided tables.
How does the Dry Mode function work on the CARRIER TRANSICOLD AIRV 68RV14102A?
The Dry Mode function effectively eliminates moisture by operating the compressor and fan motor intermittently, maintaining the room temperature at the set temperature. The compressor will be “on” for 5 minutes, then “off” for 5 minutes. The system fan motor will operate on low speed.
Note: The unit determines Dry Mode by sensing the Room Temperature every 5 minutes (a 3-minute minimum operation of the compressor is not applied).
Can a Heat Strip be added to a Cool Only Free-blow CARRIER TRANSICOLD AIRV 68RV14102A unit?
Why is the plug on the heat strip of my CARRIER TRANSICOLD AIRV 68RV14102A too short to reach the connector?
Why does my ducted CARRIER TRANSICOLD AIRV 68RV14102A run in fan and heat mode, with the green “ON” light flashing 5 times?
How do I know if my CARRIER TRANSICOLD AIRV 68RV14102A unit is cooling correctly?
First, check to see if the filters are clean. Once cleaned, measure the temperature of the air going into the filters and compare it to the air temperature coming out of the unit. For ducted units, take the reading as close as possible to the unit air outlet. The temperature difference (Delta-T) should be 20 to 25 degrees. This test requires the interior temperature to be warm enough to provide a good heat load to the air conditioning system. If the interior temperature is cold, the temperature drop may not be as high as 20 to 25 degrees.
If the temperature drop is not as described, take an amp draw on the unit’s 115 VAC and compare it to the correct model specifications.
Why does the compressor on my remote-controlled CARRIER TRANSICOLD AIRV 68RV14102A run for 5 minutes and then shut off repeatedly?
Why does the temperature on the remote control for my CARRIER TRANSICOLD AIRV 68RV14102A adjust in 2-degree increments?
Why do some CARRIER TRANSICOLD AIRV 68RV14102A remote control systems have a furnace mode temperature that goes down to 45 degrees, while others only go down to 63 degrees?
What is the temperature range for the manual thermostat on the Freeblow ceiling package of the CARRIER TRANSICOLD AIRV 68RV14102A?
Is it normal for the fan on my CARRIER TRANSICOLD AIRV 68RV14102A Freeblow ceiling unit to run all the time, even when the compressor is off?
What does the blinking red light on the ducted remote control unit for my CARRIER TRANSICOLD AIRV 68RV14102A indicate?
What are the electrical requirements for my CARRIER TRANSICOLD AIRV 68RV14102A unit?
The heat strip on my CARRIER TRANSICOLD AIRV 68RV14102A free-blow unit no longer works. What should I check?
Not necessarily. Heat strips manufactured after 3507Y are equipped with a manual reset overload protector. Remove the required components to access the electrical connections at the heat strip assembly. On the back of the overload protector, there is a “RED” reset button. Push the button in until it clicks to reset. If no reset button is present, the unit was manufactured prior to 3507Y. Check the element for an open circuit or a resistance value of 9 Ohms.
Why does the remote control set temperature seem to be off by 3 or 4 degrees from the actual temperature at the CARRIER TRANSICOLD AIRV 68RV14102A ceiling unit?
What should I do if my CARRIER TRANSICOLD AIRV 68RV14102A has no power?
If there is no power to the unit, check the following:
1. Reset the master switch.
2. Reset the circuit breaker.
3. If wiring is defective, replace it.
4. Tighten any loose electrical connections.
5. Replace any faulty switches, thermostat, or fan.
6. For Ducted Systems, ensure the 12 VDC power source is connected.
7. For Ducted Systems, replace the 12 VDC in-line fuse if it is open.
What should I do if my ducted CARRIER TRANSICOLD AIRV 68RV14102A unit will not operate?
If the display is not illuminated, check the 12 Volt DC in-line fuse.
If the display is illuminated, check the 115 Volt AC connections.
What does it mean if the green LED light flashes 5 times on my ducted CARRIER TRANSICOLD AIRV 68RV14102A and it won’t cool?
This indicates a compressor drive malfunction. Follow these steps:
1. Check the 115 volt AC power source.
2. Momentarily disconnect the 12 VDC power source.
3. Disable the compressor malfunction test switch.
4. Check the AMP draw.
5. Check the temperature difference (ΔT).
What should I do if my CARRIER TRANSICOLD AIRV 68RV14102A cools for a few moments then stops?
Follow these steps:
1. Remove the grill and verify the evaporator coil probe is inserted into the coil.
2. Check the AMP draw.
3. Check the temperature difference (ΔT).
4. If the issue persists, replace the unit.
What should I check if the compressor power supply is open on my CARRIER TRANSICOLD AIRV 68RV14102A?
1. Tighten any loose leads at the compressor terminals.
2. Replace a defective motor overload switch.
3. Replace a defective capacitor.
4. If compressor windings are open, replace the compressor.
5. If the compressor is seized, replace it.
6. Verify the capacitor wiring is correct according to the wiring diagram.
Why does the compressor on my CARRIER TRANSICOLD AIRV 68RV14102A run but cycle, with the fan operating erratically?
This could be caused by several issues. Here are the probable causes and remedies:
• Loose lead at fan motor: Tighten the lead.
• Defective or burned out motor: Replace the motor.
• Outdoor air restricted or recirculating: Check for a dirty condenser coil, ensure proper clearance around the unit, and remove any obstructions.
• Overcharge or noncondensables in system: Check the AMP draw.
• Restricted discharge line: Check for an obstruction in the line, check the temperature difference (ΔT), and replace the unit if necessary.
• Defective motor overload switch: Replace the switch.
What causes the compressor on my CARRIER TRANSICOLD AIRV 68RV14102A to cycle on overload?
• Defective run capacitor: Replace the capacitor.
• Defective compressor bearings or valves: Replace the unit.
• Greatly restricted evaporator air, iced evaporator coil: Defrost the evaporator coil.
• Low refrigerant charge: Replace the unit.
• Evaporator capillary restricted: Replace the unit.
• Liquid line restricted: Replace the unit.
• Compressor hot: Verify the refrigerant charge, check the AMP draw, and check the temperature difference (ΔT).
• Weak or inconsistent line power: Check the line voltage at the time of compressor start-up.
What should I do if there is insufficient cooling or inadequate cooling air from my CARRIER TRANSICOLD AIRV 68RV14102A?
• Dirty evaporator coil: Clean as required.
• Iced evaporator coil, slightly low refrigerant charge: Defrost or recharge.
• Improper fan operation: Verify fan rotation (refer to the wiring diagram).
• Defective fan motor: Replace the fan motor.
• Return air filter is dirty: Remove and clean the filters.
What should I do if the condenser air is not adequate on my CARRIER TRANSICOLD AIRV 68RV14102A?
• Outside Air Restricted: Check for obstruction at the coil and remedy as required.
• Dirty coil: Clean the coil.
• Defective fan motor: Replace the fan motor.
What if my CARRIER TRANSICOLD AIRV 68RV14102A provides insufficient cooling?
• Unit undersized: Re-evaluate the unit for proper capacity.
• Capillary restricted: Check the AMP draw, check the temperature difference (ΔT), and replace the unit if necessary.
What causes compressor flooding in my CARRIER TRANSICOLD AIRV 68RV14102A?
• Unit overcharged: Check the AMP draw, check the temperature difference (ΔT), and replace the unit if necessary.
• Low evaporator airflow: Clean the filter and/or evaporator coil.
• Defective electrical connections: Check connections per the wiring diagram and tighten any loose connections.
Why does the heater cycle on the limit switch on my heat/cool CARRIER TRANSICOLD AIRV 68RV14102A?
• Dirty filter: Clean or replace the filter.
• Blocked evaporator air inlet (indoor): Remove the blockage.
• Low airflow due to fan motor speed: Check the fan motor. Repair or replace as necessary.
What should I do if the air sweep feature is not working on my free-blow CARRIER TRANSICOLD AIRV 68RV14102A?
• Ceiling grill not properly aligned: Align the ceiling grill.
• Linkage in upper control box stuck: Align and lubricate the linkage.
• Air sweep motor failure: Replace the motor.
What should I do if water is dripping from the ceiling unit of my CARRIER TRANSICOLD AIRV 68RV14102A?
Verify that the vehicle is level. Tighten the unit mounting bolts evenly or replace the unit gasket.
What should I do if there is inadequate heat from the heat strip on my free-blow CARRIER TRANSICOLD AIRV 68RV14102A?
If there is no heat from the heat strip, perform the following checks:
1. Verify the AMP draw (should be 13.8 AMP).
2. Verify the resistance through the heating element (should be 9 OHM).
3. Check the bi-metal switch. If it is open, replace the switch.
What should I do if there is inadequate heat from the heat pump on my CARRIER TRANSICOLD AIRV 68RV14102A?
NOTE: Allow the unit to operate for 15 minutes after switching from cooling mode.
• Reversing valve not operating: Check for 115 volts at the reversing valve coil, check for a reversing valve restriction, and verify compressor operation.
• Outdoor coil icing: Check the outdoor coil sensor.
How do I clear diagnostic alarms on my CARRIER TRANSICOLD AIRV 68RV14102A?
What do the self-diagnostics flash codes mean on my ducted CARRIER TRANSICOLD AIRV 68RV14102A?
The GREEN operation indicator LED will flash if there is a problem. If more than two errors occur, the highest ranked code is displayed. If the highest ranked error is cleared, the next highest ranked error code is displayed.
| Flashes | Error Codes (Priority) | Error Contents (Malfunction) | Allowed Modes |
|---|---|---|---|
| 2 | 1 | ROOM AIR THERMISTOR FAILURE | FAN Mode |
| 3 | 2 | INDOOR COIL THERMISTOR FAILURE | FAN Mode, FURNACE Mode |
| 4 | 3 | OUTDOOR COIL THERMISTOR FAILURE | FAN Mode, FURNACE Mode |
| 5 | 4 | COMPRESSOR DRIVE MALFUNCTION | FAN Mode, FURNACE Mode |
| 6 | 5 | REVERSING VALVE DRIVE MALFUNCTION | FAN Mode, FURNACE Mode |
| 1 | 6 | DISCHARGE AIR THERMISTOR FAILURE | FAN Mode, FURNACE Mode |
| Continuous | 7 | THERMISTOR WIRING WRONG (only in cooling test mode) | FAN Mode |
How do I perform preventative maintenance on my CARRIER TRANSICOLD AIRV 68RV14102A?
Cleaning: Clean the evaporator and condenser coils. Hold a flashlight behind the coil to see if all spaces are clear. Dust accumulation reduces airflow and cooling capacity. Both coils can be vacuumed when dry or brushed with a stiff brush and blown out with compressed air. Thoroughly clean the base pan, motors, fan wheels, and other components. Clean the cover and ceiling grill with mild detergents. CAUTION: Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plastic sections.
Painting: Paint any parts that show evidence of rust with a good rust-prevention paint.
Wiring: Check all wiring for deterioration and all electrical contacts for tightness or corrosion.
Mounting: Ensure the unit is secure on the roof according to installation instructions. Check fans to ensure they are correctly positioned and tight on the shaft.
Leaks: Check any connections that show evidence of oil or leaks. Check gaskets for possible air leakage.
Controls: Check the unit to ensure all controls are functioning correctly and operation is normal. Vibrations can cause unwanted noise. NOTE: Check to ensure that piping is not vibrating against the side of the unit.
How do I remove the filter on the Free Blow ceiling unit of my CARRIER TRANSICOLD AIRV 68RV14102A?
The filters are located in the ceiling grill. To remove them:
a. Grasp the edge of the filter at the recess in the end of the ceiling grill.
b. Pull the filter completely out of the filter slot.
c. Vacuum the filter or wash it in lukewarm water. Shake off excess water and dry thoroughly.
d. Replace the filter by sliding it into the filter slot in the ceiling grill until the filter frame is flush with the interior grill.
How do I test and replace a capacitor on my CARRIER TRANSICOLD AIRV 68RV14102A?
WARNING: Disconnect power to the AirV unit before checking the capacitor. Capacitors must be discharged properly before testing.
a. Place a 20,000 ohm, 2-watt resistor across the terminals of the capacitor for approximately 30 seconds. WARNING: Do not touch the metal of the screwdriver when discharging the capacitor. You could receive a shock.
b. After the capacitor has been discharged and all wires are removed, use an ohmmeter to test its resistance.
c. Set the scale to R x 1K or 10K ohm and place the ohmmeter leads across the capacitor terminals.
d. If the ohmmeter first reads 0, then rises toward infinity or some higher resistance, the capacitor is good.
e. If the ohmmeter goes to 0 or a low resistance and stays there, the capacitor is shorted and needs to be replaced.
f. If the ohmmeter reads infinity (OL), the capacitor is open and needs to be replaced.
How do I troubleshoot the Positive Temperature Coefficient Thermistor (PTC) (Start Thermistor) on my CARRIER TRANSICOLD AIRV 68RV14102A?
a. Disconnect power from the AirV unit.
b. Disconnect the wires to the PTC.
c. Using an ohm meter, check for continuity across the PTC. If there is no continuity, it must be replaced. If continuity exists, reconnect the wires to the PTC.
d. Reconnect power to the AirV unit.
e. Turn on the AirV unit to start.
f. Use a clamp-on amp probe to monitor the amp draw of the compressor during its start-up. When the compressor starts, an amp draw will be indicated for almost a second. If no amp draw is indicated or if the amp draw occurs for much longer than a second, the PTC is defective and must be replaced.
How do I change the remote control for my CARRIER TRANSICOLD AIRV 68RV14102A from a Fahrenheit to a Celsius display?
CAUTION: The change from Fahrenheit to Celsius will be permanent. It cannot be changed back to Fahrenheit.
a. Remove the batteries from the remote control.
b. Carefully remove the remote cover by inserting a narrow flat object between the cover and remote body and prying apart.
c. Remove the brass screw holding the PCB in place.
d. Carefully remove the PCB board from the remote body, making sure the battery springs release from their holders.
e. Locate FR9 on the PCB board.
f. Carefully cut the FR9 jumper wire.
g. Reverse the above procedure for reassembly. CAUTION: When re-assembling, ensure the battery springs are correctly placed in the battery spring holders.
How do I install a wall-mounted thermostat for my CARRIER TRANSICOLD AIRV 68RV14102A?
WARNING: Before installing the thermostat, turn off all power to the unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
Thermostat Location:
• Mount approximately 5 feet (1.5m) from the floor, on an inside partitioning wall in a frequently used room.
• Avoid mounting near windows, outside walls, doors, direct heat sources, supply/return air grilles, or in areas with poor air circulation.
Installation Steps:
a. Turn off all power to the unit.
b. If replacing an old thermostat, remove it, disconnect wires one at a time, and record the wire color and terminal marking for each.
c. Separate the front and back pieces of the new thermostat plastic case.
d. Route thermostat wires through the hole in the back piece. Level it against the wall and mark the wall through the 2 mounting holes.
e. Drill two 3/16 inch mounting holes in the wall where marked.
f. Secure the back plastic to the wall with the 2 anchors and screws provided.
g. Connect wires to the proper terminals of the connector block in the front piece.
h. Push any excess wire back into the wall and seal the hole to prevent air leaks.
i. Snap the front and back pieces of plastic together.
j. Turn on power to the unit.
How do I configure the wall-mounted thermostat for my CARRIER TRANSICOLD AIRV 68RV14102A?
To enter configuration mode, press and hold the FAN button for approximately 10 seconds until the room temperature disappears and the display reads ‘A’. While in configuration mode, you can adjust three options: Anticipator (A), Fahrenheit/Celsius (d), and Room Temperature Offset (oF).
A. ANTICIPATOR – Value Adjustment:
This controls sensitivity and cycle rate. Higher numbers (1-3) decrease sensitivity. The factory default is 2. To adjust:
1. Enter configuration mode.
2. Use UP & DOWN buttons to display ‘A’.
3. Press MODE once to display the current value.
4. Use UP & DOWN buttons to change the value.
5. Press MODE to return to ‘A’.
d. Fahrenheit/Celsius Selection:
To select:
1. Enter configuration mode.
2. Use UP & DOWN buttons to display ‘d’.
3. Press MODE once to display ‘F’ or ‘C’.
4. Use UP & DOWN buttons to change between F & C.
5. Press MODE to return to ‘d’.
oF. Room Temperature Offset Adjust Selection:
This adds or subtracts degrees (-5 to +5) from the actual temperature reading. The factory default is 0. To select:
1. Enter configuration mode.
2. Use UP & DOWN buttons to display ‘oF’.
3. Press MODE once to display the offset value.
4. Use UP & DOWN buttons to select a value between -5 and 5.
5. Press MODE to return to ‘oF’.
To exit configuration mode, press the FAN button or wait for two minutes.
How do I check the thermostat operation on my CARRIER TRANSICOLD AIRV 68RV14102A?
Temperature Display: The thermostat displays the room temperature. When UP or DOWN is pressed, ‘SET’ appears with the set point. After 5 seconds of inactivity, it returns to showing room temperature.
Timeguard Timer: A 3-minute timeguard is active upon power-up and any time the compressor turns off. Pressing UP and FAN simultaneously overrides the timer for 1 cycle.
Cycle Timer: The thermostat allows a maximum of 4 equipment cycles per hour. A 15-minute timer starts when an output is turned on, preventing it from turning back on too soon.
Minimum On Timer: Once the equipment turns on, it will remain on for a minimum of 2 minutes, unless the set point or mode is changed.
Error Messages:
• E4: Internal memory failure. Replace the thermostat.
• — (two dashes): Cannot read room temperature. Replace the thermostat.
What are the upper unit models for the CARRIER TRANSICOLD AIRV 68RV14102A?
| MODEL NUMBER | PART NUMBER | CONFIGURATION | VOLTAGE | AMPS | COLOR |
|---|---|---|---|---|---|
| 68RV14102A | 99-00468-00 | STANDARD A/C | 115/1/60 | 12.8 | WHITE |
| 99-00468-01 | STANDARD A/C | 115/1/60 | 12.8 | IVORY | |
| 99-00469-20 | STANDARD A/C | 115/1/60 | 12.8 | BLACK | |
| 68RV11302A | 99-00468-02 | STANDARD A/C | 220/1/50 | 5.3 COOL | WHITE |
| 99-00468-03 | STANDARD A/C | 220/1/50 | 6.7 HEAT | IVORY | |
| 68RV15102A | 99-00468-08 | HIGH-CAPACITY | 115/1/60 | 14.1 | WHITE |
| 99-00468-09 | HIGH-CAPACITY | 115/1/60 | 14.1 | IVORY | |
| 99-00468-28 | HIGH-CAPACITY | 115/1/60 | 14.1 | BLACK | |
| HEAT PUMP 68RV11122A | 99-00468-04 | HEAT PUMP FREE-BLOW | 115/1/60 | 12.7 COOL 10.9 HEAT | WHITE |
| 99-00468-05 | HEAT PUMP FREE-BLOW | 115/1/60 | 12.7 COOL 10.9 HEAT | IVORY | |
| 99-00468-24 | HEAT PUMP FREE-BLOW | 115/1/60 | 12.7 COOL 10.9 HEAT | BLACK | |
| HEAT PUMP 68RV11112A | 99-00468-06 | HEAT PUMP DUCTED | 115/1/60 | 12.7 COOL 10.9 HEAT | WHITE |
| 99-00468-07 | HEAT PUMP DUCTED | 115/1/60 | 12.7 COOL 10.9 HEAT | IVORY | |
| 99-00468-26 | HEAT PUMP DUCTED | 115/1/60 | 12.7 COOL 10.9 HEAT | BLACK | |
| LOW PROFILE 68RV15103A | 99-00468-10 | FREE-BLOW HIGH CAPACITY | 115/1/60 | 14.1 COOL 13.8 HEAT | WHITE |
| 99-00468-32 | FREE-BLOW HIGH CAPACITY | 115/1/60 | 14.1 COOL 13.8 HEAT | BLACK | |
| LOW PROFILE 68RV14103A | 99-00468-12 | FREE-BLOW STANDARD | 115/1/60 | 13.4 COOL 13.8 HEAT | WHITE |
| 99-00468-30 | FREE-BLOW STANDARD | 115/1/60 | 13.4 COOL 13.8 HEAT | BLACK | |
| LOW PROFILE 68RV14113A | 99-00468-13 | HEAT PUMP HIGH CAPACITY | 115/1/60 | 14.5 COOL 13.8 HEAT | WHITE |
| 99-00468-33 | HEAT PUMP DUCTED | 115/1/60 | 12.7 COOL 10.9 HEAT | BLACK | |
| LOW PROFILE 68RV14123A | 99-00468-11 | HEAT PUMP FREE-BLOW | 115/1/60 | 12.7 COOL 10.9 HEAT | WHITE |
What are the ceiling unit models for the CARRIER TRANSICOLD AIRV 68RV14102A?
| MODEL NUMBER | PART NUMBER | VOLTAGE | COLOR | OPTIONS | INTERFACE |
|---|---|---|---|---|---|
| 68RV0010AA | 99-00469-00 | 115/1/60 | White | Cool Only | Free-Blow |
| 99-00469-01 | 115/1/60 | Ivory | Cool Only | Free-Blow | |
| 68RV0010BA | 99-00469-02 | 115/1/60 | White | Heat/Cool | Free-Blow |
| 99-00469-03 | 115/1/60 | Ivory | Heat/Cool | Free-Blow | |
| 68RV0010ΚΑ | 99-00469-06 | 115/1/60 (12VDC) | White | Cool Only | Ducted |
| 68RV0030AA | 99-00469-04 | 220/1/50 | White | Cool Only | Free-Blow |
| 99-00469-05 | 220/1/50 | Ivory | Cool Only | Free-Blow | |
| 68RV0030BA | 99-00469-08 | 220/1/50 | White | Heat/Cool | Free-Blow |
| 68RV0030KA | 99-00469-10 | 220/1/50 | White | Cool Only | Ducted |
| 68RV0012CA | 99-00469-11 | 115/1/60 | White | Heat Pump | Free-Blow |
| 99-00469-12 | 115/1/60 | Ivory | Heat Pump | Free-Blow | |
| 68RV0011LA | 99-00469-13 | 115/1/60 (12VDC) | White | Heat Pump | Ducted |
| 68RV0010EA | 99-00469-17 | 115/1/60 (12VDC) | White | Heat/Cool | Free-Blow Wall Thermostat |
| 68RV0040MA | 99-00469-22 | 115/1/60 | White | Cool Only | Ducted Wall Thermostat |
| 68RV0010AB (Phased Out) | 99-00469-23 | 115/1/60 | White | Cool Only | Free-Blow |
| 99-00469-24 | 115/1/60 | Ivory | Cool Only | Free-Blow | |
| 68RV0010BB (Phased Out) | 99-00469-25 | 115/1/60 | White | Heat/Cool | Free-Blow |
| 99-00469-26 | 115/1/60 | Ivory | Heat/Cool | Free-Blow | |
| 68RV0010DB | 99-00469-29 | 115/1/60 | White | Cool Only | Free-Blow Wall Thermostat |
| 68RV0010EB | 99-00469-31 | 115/1/60 | White | Heat/Cool | Free-Blow Wall Thermostat |
| 68RV0012FB | 99-00469-33 | 115/1/60 | White | Heat Pump | Free-Blow Wall Thermostat |
| 68RV0010KS | 99-00469-35 | 115/1/60 | White | Cool Only Thick Roof Kit | Ducted Remote |
| 68RV0011KS | 99-00469-36 | 115/1/60 | White | Heat Pump Thick Roof Kit | Ducted Remote |
| 68RV0010MS (Phased Out) | 99-00469-37 | 115/1/60 | White | Cool Only Thick Roof Kit | Ducted W/Wall Sensor |
| 68RV0011OS (Phased Out) | 99-00469-38 | 115/1/60 | White | Heat Pump Thick Roof Kit | Ducted W/Wall Sensor |
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD CARRIER TRANSICOLD AIRV 68RV14102A (01) PDF DOCUMENT
