How should I dispose of my CARRIER 40VD028H-7S-QEE air conditioning product?

Your CARRIER 40VD028H-7S-QEE air conditioning product is marked with a symbol indicating that electrical and electronic products should not be mixed with unsorted household waste. Do not attempt to dismantle the system yourself. The dismantling of the air conditioning system, including the treatment of refrigerant, oil, and other parts, must be done by a qualified installer in accordance with relevant local and national legislation.

Air conditioners must be treated at a specialized treatment facility for reuse, recycling, and recovery. By ensuring the product is disposed of correctly, you will help prevent potential negative consequences for the environment and human health. The battery must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.


What are the main parts of the CARRIER 40VD028H-7S-QEE indoor unit?

The CARRIER 40VD028H-7S-QEE consists of the main indoor unit which is connected to an air duct via a soft connection. The unit has an air inlet port where air is drawn in and an air outlet port where conditioned air is expelled.


What are the key safety warnings for installing the CARRIER 40VD028H-7S-QEE?

Improper installation can lead to severe accidents. Please follow these warnings for your CARRIER 40VD028H-7S-QEE:

• Contact a professional installer for installation, repair, and service. Improper installation can result in water leakage, electric shocks, or fire.

• Ensure the installation location can bear the weight of the air conditioner. Installing on weak structures like metal burglar-proof nets can lead to the machine dislodging and causing injury.

• The installation must be strong enough to withstand typhoons and earthquakes to prevent accidents.

• Select wiring according to applicable codes and standards and ensure terminal connections are secure to prevent shock or fire.

• While placing or reinstalling the unit, do not let air enter the refrigeration cycle system. Air in the system can lead to cracking or physical injuries due to abnormally high pressure.

• Use accompanying or specific spare parts during installation to avoid water leakage, electric shocks, fire, or refrigerant leakage.

• To prevent harmful gases from entering the room, do not drain water from the drainpipe into a sanitation pipe that could contain harmful gases like sulfurated gas.

• Do not install the air conditioner where flammable gas leakage might occur, as this could result in fire.

• Properly mount and insulate the drainpipe according to the manual to ensure smooth drainage and prevent condensation and water leakage.

• Properly insulate the refrigerant gas and liquid pipes to prevent condensation and water damage from dripping.


What safety precautions should I follow when operating my CARRIER 40VD028H-7S-QEE?

For safe operation of your CARRIER 40VD028H-7S-QEE, please observe the following:

• The air conditioner must be effectively grounded. Electric shocks may occur if it’s ungrounded or improperly grounded. The earthing wire should not be connected to gas pipes, water pipes, lightning rods, or telephones.

• A breaker for electricity leakage should be mounted to prevent accidents like electric shocks.

• Do not place heating apparatus under the indoor units, as this might distort the units.

• Do not place flammable items in the direct path of the air from the conditioner.

• Do not place plants and animals in the direct path of the wind from the air conditioner, as it could harm them.

• This appliance is not intended for the preservation of food, living creatures, precision instruments, or artworks.

• Use a fuse with the proper capacity.

• To avoid electric shock, do not touch the switch with wet hands.

• Close windows to keep outdoor air from entering. Use curtains or shutters to avoid sunlight.

• Stop the unit and switch off the manual power when cleaning it.

• Do not clean the unit with water, as it may cause an electric shock.

• Do not place or direct flammable sprays at the air conditioner, which may cause a fire.

• This appliance is not intended for use by persons with reduced physical, sensory, or mental capabilities unless they are supervised or have been given instructions by a person responsible for their safety.


How do I clean the filter on my CARRIER 40VD028H-7S-QEE?

Always switch off and disconnect the CARRIER 40VD028H-7S-QEE from the power supply before cleaning to prevent electric shock and injury.

1. To clean the filter, use a vacuum cleaner or water to remove dust.

2. If there is excessive dust, you can use a fan or directly spray a special cookware detergent on the air inlet grid. Wait 10 minutes, then clean it with water.

3. For heavy dust, use a soft-hair brush and a mild detergent to clean.

4. Allow the filter to dry completely before reinstalling it.

Attention: Do not clean with hot water over 50°C to avoid fading or distortion. Do not dry the filter on a fire, as this might cause the cleaner to ignite.


How do I troubleshoot common issues with my CARRIER 40VD028H-7S-QEE?

Before calling for service for your CARRIER 40VD028H-7S-QEE, please check the following common symptoms and their potential causes:

Symptom Reason/Check
Water flow sound This sound can be heard at the start, during, or after operation. It is the sound of refrigerant flowing or condensed water draining and is normal.
Cracking sound This sound may occur during operation and is caused by temperature changes or slight dilation of the heat exchanger.
Bad smell in outlet air Smells from walls, carpet, furniture, clothing, or cigarette smoke can attach to the conditioner and be circulated.
Flashing operating indicator If the unit is switched on again after a power failure, the operating indicator will flash. Turn on the manual power switch.
Awaiting indication This happens when the unit is set to a mode (e.g., cooling) opposite to what other indoor units are doing (e.g., heating).
Sound when indoor unit is shut down; or occurrence of white steam or cold air Refrigerant flows for a short time after shutdown to prevent oil and refrigerant from blocking the unit, causing a sound. White steam or cold air may appear depending on the operating mode of other units.
Clicking sound when switching on This sound is due to the resetting of the expansion valve when the unit is powered on.
Failure to work

• Check if there is a power failure.

• Check if the manual power switch is turned off.

• Check if the supply fuse and breaker are disconnected.

• Check if the protective unit is working.

Bad cooling and heating effects

• Check if the air intake and outlet ports of the outdoor units are blocked.

• Check if doors and windows are open.

• Check if the filter is blocked with dust.

• Check if the wind quantity is set to low.

• Check if the operation is set to Fan mode.

• Check if the temperature setting is proper.

Immediately stop operation, disconnect the manual supply switch, and contact after-service personnel if: buttons are inflexibly actuated, the fuse and breaker have burnt, there are foreign objects and water in the refrigerant, or other abnormal conditions occur.


What are the installation procedures for the drainpipes on the CARRIER 40VD028H-7S-QEE?

Proper drainpipe installation is crucial for your CARRIER 40VD028H-7S-QEE.

• Keep a downward gradient of 1/50 to 1/100 for the drain pipes and avoid lobing or curving.

• When connecting the drainpipe to the equipment, do not apply too much force. Position the piping as close to the equipment as possible.

• For the drainpipe, a general-purpose hard PVC tube can be used. Insert the end of the PVC tube into the wash port and fasten it with a drainage hose and thread clip. Do not use binding agents or glues.

• When used for multiple equipment, the public piping should be about 100mm lower than the wash ports.

• The hard PVC tube in the room must be insulated.

• Do not place drainpipes in areas with irritant gases or directly into a sewer where gases with sulfur might be present.

• A backwater bend should be designed to prevent water leakage caused by sub-atmospheric pressure in the drain pan.

• The pump’s maximum lift reaches 600mm. Follow the recommended installation dimensions in the manual.

Testing the Drainage System:

1. After testing the electrical system, test the drainage system.

2. During testing, ensure water flows correctly through the piping without any leakage at the connections.

3. In a new house, test the drainage system before fitting the ceiling.

4. The test should be performed even if the unit is installed in a season when heating is needed.

5. To check the system, provide about 1000cc of water to the equipment via the air outlet port with a feed pump and check the drainage during refrigerating operation.


How do I connect the refrigerant tubing for the CARRIER 40VD028H-7S-QEE?

Follow these procedures for connecting the refrigerant tubing on your CARRIER 40VD028H-7S-QEE.

1. Proceed with the flare tube connecting operation. Dual wrenches must be used for connecting the indoor unit tubing.

2. Use the correct mounting torque for the tubing connections. Refer to the table below:

Outer Diameter of Tubing (mm) Mounting Torque
Ø6.35 11.8 – 13.7N.m
Ø9.52 32.7 – 39.9N.m
Ø12.7 49.0 – 53.9N.m
Ø15.88 78.4 – 98.0N.m
Ø19.05 97.2 – 118.6N.m

3. Add refrigerant according to the installation instructions for the outdoor units. Compressor failure can be caused by filling too much or too little refrigerant.


What do the indoor error indicators and fault codes mean on the CARRIER 40VD028H-7S-QEE?

The following table lists the fault descriptions for the error codes on the CARRIER 40VD028H-7S-QEE.

Error Code Timer Lights/LED 5 Flik Times Fault Descriptions
01 1 Ambient sensor TA
02 2 Gas Pipe Sensor TC1
03 3 Liquid Pipe Sensor TC2
04 4 Heat Source Sensor
05 5 EEPROM
06 6 Comm. Error with Outdoor unit
07 7 Comm. Error With controller
08 8 Drainage malfunction
09 9 Repeated address
12 12 50Hz Zero-crossing
13 13 DC motor match (AD*MQERA)
14 14 fault of indoor unit DC motor
16 16 DC motor communication (AD*MQERA)
18 18 BS valve box or 4WV switch failure
20 20 Corresponding faults of outdoor units

How do I set the dipswitches on the indoor unit PCB of the CARRIER 40VD028H-7S-QEE?

The dipswitches on the indoor unit PCB of your CARRIER 40VD028H-7S-QEE are used to configure various settings. In the tables, 1 represents ON and 0 represents OFF.

SW01 Settings:

Switch Setting Function
SW01_1 1 Operation modes displayed on wired controller: [air supply] [refrigerating] [dehumidification]
0 Operation modes displayed on wired controller: [automatic] [air supply] [refrigerating] [dehumidification] [heating]
SW01_2 to SW01_4 000 Address of wire controlled indoor unit: 0# (wire-controlled master unit) (default)
001 Address of wire controlled indoor unit: 1# (wire-controlled slave unit)
010 Address of wire controlled indoor unit: 2# (wire-controlled slave unit)
011 Address of wire controlled indoor unit: 3# (wire-controlled slave unit)
100 Address of wire controlled indoor unit: 4# (wire-controlled slave unit)
101 Address of wire controlled indoor unit: 5# (wire-controlled slave unit)
110 Address of wire controlled indoor unit: 6# (wire-controlled slave unit)
111 Address of wire controlled indoor unit: 7# (wire-controlled slave unit)
SW01_5 to SW01_8 0000 Capability of indoor unit: 0.6HP
0001 Capability of indoor unit: 0.8HP
0010 Capability of indoor unit: 1.0HP
0011 Capability of indoor unit: 1.2HP
0100 Capability of indoor unit: 1.5HP
0101 Capability of indoor unit: 1.7HP
0110 Capability of indoor unit: 2.0HP
0111 Capability of indoor unit: 2.5HP
1000 Capability of indoor unit: 3.0HP
1001 Capability of indoor unit: 3.2HP
1010 Capability of indoor unit: 4.0HP
1011 Capability of indoor unit: 5.0HP
1100 Capability of indoor unit: 6.0HP
1101 Capability of indoor unit: 8.0HP
1110 Capability of indoor unit: 10.0HP
1111 Capability of indoor unit: 15.0HP

Note: A wired controller can be connected to at most 16 ultra-thin air-duct indoor units.


How do I activate or deactivate the 26°C Lock function on the CARRIER 40VD028H-7S-QEE?

The 26°C Lock function on your CARRIER 40VD028H-7S-QEE is deactivated by default.

Activation: Press the “Health” button on the remote controller 8 times in 5 seconds. When you hear the beep 4 times, the function is activated.

Deactivation: Press the “Health” button on the remote controller 8 times in 5 seconds. When you hear the beep 2 times, the function is deactivated.


How do I perform a test run on the CARRIER 40VD028H-7S-QEE?

Before starting a test run on your CARRIER 40VD028H-7S-QEE, perform the following checks:

Before Test Run:

• Test the supply terminal tier (L, N terminals) and grounding points with a 500V mega-ohm meter. The resistance must be above 1MΩ. Do not operate if it is below 1MΩ.

• Connect to the power supply of outdoor units to energize the compressor’s heating belt. Power it on for 12 hours prior to operation to protect the compressor on startup.

• Check that the drainpipe and connection line installations are correct.

Installation Checkup:

• Check if the mains voltage is correct.

• Check for leakage at piping joints.

• Check if the connections of mains power and indoor & outdoor units are correct.

• Check if the serial numbers of the terminals match.

• Check if the installation place meets specifications.

• Check if there is too much noise.

• Check if the connecting line is fastened.

• Check if the connectors for tubing are heat insulated.

• Check if water is draining outside properly.

• Check if the indoor units are positioned correctly.

Ways of Test Run (Forced Run):

If the machine fails to start due to room temperature, you can initiate a forced run. This function is not available with a remote control.

• Set the wired controller to refrigerating/heating mode, then press the “ON/OFF” button for 5 seconds to enter the compulsive refrigerating/heating mode. Press the “ON/OFF” button again to quit compulsive running and stop the operation.


What do the fault codes on the wired controller for the CARRIER 40VD028H-7S-QEE mean?

If a fault appears on your CARRIER 40VD028H-7S-QEE, consult the table below to understand the fault descriptions based on the code displayed on the wired controller or the flashing of the PCB LED5/Receiver Timer Lamp.

Failure code at wired controller PCB LED5 (Indoor Units)/ Receiver Timer Lamp (Remote Controller) Fault Descriptions
01 1 Fault of indoor unit ambient temp. transducer TA
02 2 Fault of indoor unit pipe temp. transducer TC1
03 3 Fault of indoor unit pipe temp. transducer TC2
04 4 Fault of indoor unit dual heat source temp. transducer
05 5 Fault of indoor unit EEPROM
06 6 Fault of communication between indoor & outdoor units
07 7 Fault of communication between indoor unit and wired control
08 8 Fault of indoor unit float switch
09 9 Fault of duplicate indoor unit address
12 12 Fault of indoor unit 50Hz Zero-crossing
13 13 DC motor match (AD*MQERA)
14 14 fault of indoor unit DC motor
16 16 DC motor communication (AD*MQERA)
18 18 BS valve box or 4WV switch failure
20 20 Corresponding faults of outdoor units

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD CARRIER 40VD028H-7S-QEE (01) PDF DOCUMENT