What are the key safety precautions for using the AEMC INSTRUMENTS SR193-BK and other compatible current probes?
The protection assured by the current probe can be compromised if it is used in a way that is not recommended by the manufacturer. Always follow these precautions:
• Comply with the rated maximum voltage and current, and the measurement category. Do not use the current probe on networks where the voltage or category exceeds those specified.
• Comply with the conditions of use (e.g. temperature, humidity, altitude, degree of pollution, location).
• Do not use the current probe if its housing is open, deteriorated, or incorrectly reassembled. Before each use, check the integrity of the insulation of the unit, jaws, clamps, housing, and leads.
• Do not subject the current probe to water or other liquids.
• Keep the jaw contacts of the clamp absolutely clean.
• Use suitable personal protective equipment when hazardous voltages may be accessible in the installation where the measurement is made.
• Any repairs must be carried out by accredited skilled personnel.
What do the safety and information symbols on the AEMC INSTRUMENTS SR193-BK mean?
| A (in triangle) | WARNING, risk of DANGER! The operator must refer to these instructions whenever this danger symbol appears. |
| Lightning bolt (in triangle) | CAUTION! Risk of electric shock. The voltage at the parts marked with this symbol may be dangerous. |
| Lightning bolt with hand (in triangle) | Application or withdrawal authorized on conductors carrying dangerous voltages. Type A current sensor as per IEC 61010-2-032. |
| Lightning bolt with hand crossed out (in triangle) | Must not be applied to or removed from conductors at dangerous voltages. Type B current sensor as per IEC 61010-2-032. |
| Square in a square | Equipment is protected by double insulation. |
| Battery symbol | Battery |
| Exclamation mark (in circle) | Important instructions to read and to fully understand. |
| i (in circle) | Useful information or tip to read. |
| CE | The CE marking guarantees conformity with European directives and with regulations covering EMC. |
| Crossed out trash can | The trash can with a line through it means that in the European Union, the product must undergo selective disposal for the recycling of electric and electronic material, in compliance with Directive WEEE 2002/96/EC. |
What are the definitions for the Measurement Categories (CAT) applicable to the AEMC INSTRUMENTS SR193-BK?
CAT IV: Measurement category IV corresponds to measurements taken at the source of low-voltage installations. Example: power feeders, counters and protection devices.
CAT III: Measurement category III corresponds to measurements on building installations. Example: distribution panel, circuit-breakers, machines or fixed industrial devices.
CAT II: Measurement category II corresponds to measurements taken on circuits directly connected to low-voltage installations. Example: power supply to domestic electrical appliances and portable tools.
What are the main features of the AEMC INSTRUMENTS SR193-BK current probe?
The AEMC INSTRUMENTS SR193-BK has the following features:
1. Jaws
2. Protective guard
3. Jaw opening lever
4. Shielded lead
5. Custom 4-pin input connector
How do I perform a measurement with the AEMC INSTRUMENTS SR193-BK and other current probes?
The current probes and flexible sensors are used to measure the current flowing in a conductor or bus bar without opening the circuit. The choice of probe depends on the amperage and the size of the conductor.
For three-phase measurements, use the color-coded ID markers to associate a color for each current input to match the phase identifiers on the measured system.
IMPORTANT NOTE: Always connect the probes or sensors with the indicating arrows pointing toward the load.
1. Connect the current probe or sensor to the current terminals of the instrument.
For Probes like the AEMC INSTRUMENTS SR193-BK:
• Press the jaw opening lever on the probe to open the jaws.
• Clamp the probe around the conductor to be tested. For best results, center the conductor in the jaws of the clamp.
For AmpFlex® and MiniFlex® Sensors:
• To open the sensor, press simultaneously on both sides of the opening connector (AmpFlex®) or press the opening device (MiniFlex®).
• Clamp the sensor around the conductor to be tested. For best results, center the conductor in the jaws of the clamp.
• Close the sensor by pushing the moving part into the connector until it clicks.
For MR193 and SL261 Probes:
• MR193: Set the switch to 1mV/A; the ON indicator will light up.
• SL261: Set the switch to 10mA or 100mA/A; the ON indicator will light up.
• Connect the probe to the instrument.
• Adjust the zero by turning the potentiometer with no conductor in the jaws of the clamp.
• When the measurement is finished, turn the probe switch to OFF.
What are the electrical specifications for the AEMC INSTRUMENTS SR193-BK and other compatible probes?
NOTE: The measurement ranges specified are for the probes and sensors. In some cases, they may differ from the ranges that can be measured by the instrument with which they are used. For complete specifications, refer to the product user manual supplied with each compatible instrument.
| Model | Measurement Range | Compatibility |
|---|---|---|
| AmpFlex® 193-24-BK (1) 24″ (610mm) | 200mA to 10kAAC (2) (12,000A) (3) | 8333, 8336 & PEL Series |
| AmpFlex® 193-36-BK (1) 36″ (910mm) | 200mA to 10kAAC (2) (12,000A) (3) | 8333, 8336 & PEL Series |
| AmpFlex® 196A-24-BK (1) 24″ (610mm) | 200mA to 10kAAC (2) (12,000A) (3) | 8435 |
| MiniFlex® MA193 (1) 10″ (250 mm) | 200mA to 3000A (10,000A peak) | 8333, 8336 & PEL Series |
| MiniFlex® MA193 (1) 14″ (355 mm) | 200mA to 3000A (10,000A peak) | 8333, 8336 & PEL Series |
| J93 | 50 to 3500; 50 to 5000 (DC only) | 8333, 8336, 8435 and PEL |
| MN93 | 2 to 240AAC (I >200A not permanent) | All PowerPads and PEL |
| MN193 | 5A: 0.005 to 6AAC 100A: 0.1 to 120AAC |
All PowerPads and PEL |
| MR193 | 10 to 1000AAC; 10 to 1300A PEAK AC+DC | All PowerPads and PEL |
| SL261 | 100mV/A: 100mA to 10A peak 10mV/A: 1 to 100A peak |
8333, 8336, 8435 and PEL |
| SR193 | 1 to 1200AAC (I > 1000A not continuously) | All PowerPads and PEL |
(1) 10 to 6500AAC for Model 8435
(2) 200mA to 10,000A measurement range for the PEL 100 Series.
(3) 12,000A is specified for the PEL 100 Series only.
Battery: 9V Alkaline NEDA 1604A, 6LR61
Battery Life:
• MR193 – 100H typical
• SL261 – 55H typical
• J93 – 70H typical
NOTE: Battery life is twice the typical value when using Lithium batteries.
What are the environmental and mechanical specifications for the AEMC INSTRUMENTS SR193-BK and other compatible probes?
Environmental
• Indoor use.
• Operating Temperature: 14° to 131°F (-10° to 55°C); 10% to 85% RH
• Storage Temperature: -40° to 158°F (-40° to 70°C); 10% to 90% RH
• Degree of pollution: 2
• Altitude: < 2000 m
Mechanical
| Model | Lead Length (nominal) | Clamping Diameter | Dimensions | Weight |
|---|---|---|---|---|
| AmpFlex® 193-24-BK 24″ (610mm) | 10 ft (3m) | 7.64″ (190mm) | 6.6 x 6.2 x .98″ (170 x 158 x 25mm) | 7.7 oz (270g) |
| AmpFlex® 193-36-BK 36″ (910mm) | 10 ft (3m) | 11.46″ (290mm) | 11 x 10.4 x .98″ (280 x 265 x 25mm) | 9.5 oz (220g) |
| AmpFlex® 196A-24-BK 24″ (610mm) | 10 ft (3m) | 7.64″ (190mm) | 6.6 x 6.2 x .98″ (170 x 158 x 25mm) | 7.7 oz (270g) |
| MiniFlex® MA193-10-BK 10″ (250mm) | 10 ft (3m) | 2.75″ (70mm) | 4.0 x 2.5 x 1.1″ (103 x 64 x 28mm) | 1.94 oz (55g) |
| MiniFlex® MA193-14-BK 14″ (350mm) | 10 ft (3m) | 3.94″ (100mm) | 4.0 x 2.5 x 1.1″ (103 x 64 x 28mm) | 2.11 oz (60g) |
| J93 | 10 ft (3m) | 2.84″ (72mm) | 13.23 x 5.00 x 1.65″ (336 x 127 x 42mm) | 3.75 lbs (1.7kg) |
| MN93 | 10 ft (3m) | 0.8″ (20mm) | 5.47 x 2.00 x 1.18″ (135 x 51 x 30mm) | 24 oz (690g) |
| MN193 | 10 ft (3m) | 0.8″ (20mm) | 5.47 x 2.00 x 1.18″ (135 x 51 x 30mm) | 24 oz (690g) |
| MR193 | 10 ft (3m) | One 1.6″ (42mm) or two 0.98″ (25mm) or two bus bars 1.96 x 0.19″ (50 x 5mm) | 8.8 x 3.82 x 1.73″ (224 x 97 x 44mm) | 19 oz (540g) |
| SL261 | 6.5 ft (1.9m) | 0.46″ (11.8mm) | 9.09 x 1.42 x 2.64″ (231 x 36 x 67mm) | 11.6 oz (330g) |
| SR193 | 10 ft (3m) | 2″ (52mm) | 8.5 x 4.4 x 1.8″ (216 x 111 x 45mm) | 24 oz (690g) |
What are the safety ratings of the AEMC INSTRUMENTS SR193-BK and other compatible probes?
• Protection index IP 40 for the probes and IP 30 jaws open, according to IEC 60 529
• IP 65 for the AmpFlex® according to IEC 60 529
• IK 04 according to IEC 50102
• Drop test: According to IEC 61010-1
• Electrical safety according to IEC 61010-2-032.
Maximum applicable voltage:
• AmpFlex®: 1000V CAT III; 600V CAT IV
• MiniFlex®: 1000V CAT III; 600V CAT IV
• J93: 600V CAT III; 300V CAT IV
• MN93/MN193: 600V CAT III; 300V CAT IV
• MR193: 600V CAT III; 300V CAT IV
• SL261: 600V CAT III
• SR193: 1000V CAT III; 600V CAT IV
Specifications are subject to change without notice.
How do I clean my AEMC INSTRUMENTS SR193-BK current probe?
CAUTION: Risk of electric shock. Disconnect the instrument from any source of electricity before cleaning.
• Use a soft cloth, dampened with soapy water. Rinse with a damp cloth and dry rapidly with a dry cloth.
• Do not use alcohol, solvents, or hydrocarbons.
• Do not splash water directly on the instrument.
How do I replace the battery on compatible probe models for the AEMC INSTRUMENTS SR193-BK?
Use only factory specified replacement parts.
Model MR193
1. Disconnect the MR193 completely and turn the rotary switch to OFF.
2. Use a screwdriver to unscrew the screws and remove the battery compartment cover on the backside of the unit.
3. Withdraw the battery from its compartment.
4. Disconnect the old battery without pulling on the wires and replace with a new one, observing the polarity.
5. Put the battery into its compartment.
6. Put the cover back in place and screw the screws back in.
Model SL261
1. Disconnect the SL261 completely and turn the rotary switch to OFF.
2. Unscrew the battery compartment screw and pull off the battery compartment cover.
3. Replace the battery with a new one, observing the polarity.
4. Put the cover back in place and screw the screw back in.
Model J93
1. Insert a tool, not more than 3mm in diameter, in the hole in the battery compartment cover.
2. Push to unlock the battery compartment cover, then slide it off.
3. Remove it completely by hand.
4. Remove the battery and the shim from the compartment.
5. Place the new battery in the compartment with the polarity as indicated on the label. Then replace the shim.
6. Put the battery compartment cover back in the slide and push it in until you hear a click.
Used batteries must not be treated as ordinary household waste. Recycle them appropriately.