Free English TOSHIBA P3 435K (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.


CLICK HERE TO DOWNLOAD TOSHIBA P3 435K (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.


How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.


What are the standard ratings for a TOSHIBA P3 435K 460 Volt NEMA Type 1 Chassis?

The TOSHIBA P3 435K has the following standard ratings:

MODEL RATED KVA MOTOR HP(KW) OUTPUT CURRENT (AMPS) OUTPUT VOLTAGE 3-PHASE OVERLOAD CURRENT MAIN CIRCUIT INPUT POWER INPUT CONTROL POWER SOURCE
P3-435K 350 350/280 439 380-460V 120% FOR 60 SEC. 380V/50Hz or 400-460V/60Hz VOLTAGE +/-10% FREQ. +/- 2Hz NO EXTERNAL POWER SOURCE REQUIRED

What are the standard specifications for the control system of the TOSHIBA P3 435K?

The standard specifications for the control system are:

Control System: Sinusoidal PWM control

Output voltage regulation: Same as power line.

Output frequency: 0.01 to 400 Hz (0.1 to 80Hz default setting)*. 800 Hz operation possible.

Frequency setting: 0.1 Hz from operating panel input (60Hz base), 0.01 Hz from analog input (60Hz base, 12-bit) 0 to 10Vdc), 0.01 Hz from computer interface (60Hz base)

Frequency accuracy: Analog input: +/-0.2% of the maximum output frequency (25deg C +/-1 Odeg C), Digital input: +/-0.01% (25deg C +/-1 Odeg C)

Voltage/frequency characteristics: Constant V/f, variable torque, automatic torque boost, True Torque Control and automatic energy-saving control/maximum voltage frequency adjustment (25 to 400Hz), torque boost adjustment (0 to 30%), start-up frequency adjustment (0 to 10Hz).

PWM carrier frequency: Adjustable between 0.5 and 15kHz, self adjusting

Transistor type: Insulated gate bipolar (IGBT)

Output voltage regulation: Drive can be programmed to fix max. output volts, let max. float with input voltage or set max. to input voltage sensed at power-up.

Dynamic braking: Feature not available.

Frequency Input signals: 3k ohms potentiometer (1 k ohm to 10k ohm-rated potentiometer can be connected). 0 to 10Vdc (Zin=33k ohm), +/-10 Vdc (Zin=67k ohm), +/-5 Vdc (Zin=34k ohm), 4 to 20mAdc (Zin=500 ohm)

Set point control (PID): Proportional gain, integral gain, anti-hunting gain, lag time constant, and PID error limit adjustments.

Operating functions: Accel/decel time: 0.1 to 6000 secs, accel/decel time 1 or 2 selection, accel/decel pattern selection

Forward or reverse run: Forward run when F-CC closed (default); reverse run when R-CC closed (default); reverse run when both closed (default); coast-stop when ST-CC opened (default); emergency coast stop by a command from operating panel or terminal block; 3-wire control and motorized speed pot programmable functions.

Jogging run: Jog run from panel with JOG mode selection. Terminal block operation possible with parameter settings.

Multispeed run: Set frequency plus 15 preset speeds possible with combinations of CC, SS1, SS2, SS3, and SS4.

Retry: When a protective function is activated, the system checks main circuit devices, and attempts to restart. Settable to a maximum of 10 times; wait time adjustment (0 to 10 secs)

Soft stall: Automatic load reduction during overload (Default setting: OFF).

Automatic restart: A coasting motor can be smoothly restarted (Default setting: OFF).

Pattern Run: 4 groups of 8 patterns each can be set to the 15 preset speed values. A maximum of 32 different patterns can be run; terminal block control/repetitive run possible.

DC injection braking: Braking starting frequency adjustment (0 to 120Hz), braking current adjustment (0 to 100%), braking time adjustment (0 to 10secs), emergency stop braking function, motor shaft stationary control.

Upper/Lower limit: Limits the frequency between the set values (0 to max. frequency). Can be indicated via output contact closure.

Frequency jump: 3 jump frequency settings (each with unique band settings)

Edit function: Easy access user group containing all changed parameters

Blind function: Select to display needed parameter groups and parameters

User-defined defaults: User’s parameter values can be saved into a default library. User can then default drive to Toshiba’s values or to the user’s own.


How should I perform installation safety precautions for the TOSHIBA P3 435K?

The installation safety precautions for the TOSHIBA P3 435K are:

Always ground the unit to prevent electrical shock and to help reduce electrical noise. A separate ground cable should be run inside the conduit with the input, output, and control power cables (See Grounding page 4-7). THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.

Only qualified personnel should install this equipment (see General Safety Instructions on page iii).

Installation of drive systems should conform as a minimum, to the 1999 NEC National Electrical Code Article 110 “Requirements For Electrical Installations”, to all regulations of the Occupational Safety and Health Administration, and to any other applicable national, regional or industry codes and standards.

Install in a secure and upright position in a well ventilated location that is out of direct sunlight. The ambient temperature should be between -10 deg C and 40 deg C.

Allow clearance space to insure adequate ventilation. Do not obstruct any of the ventilation openings.

Avoid installation in areas where vibration, heat, humidity, dust, fibers, steel particles, explosive mists, gasses or sources of electrical noise are present.

Adequate working space and illumination must be provided for adjustment, inspection and maintenance of the drive (see 1999 NEC Article 110-16).

A noncombustible insulating floor or mat should be provided in the area immediately surrounding the electrical system where maintenance is required.

Use lockout/tagout procedures on branch circuit disconnect before drive installation.

Connect three phase power of the correct voltage to input terminals L 1, L2, L3 (R, S, T) and connect three phase power from output terminals T1, T2, T3 (U, V, W) to a motor of the correct voltage and type for the application. Size the branch circuit conductors in accordance with Selection of Main Circuit Wiring Equipment and Standard Cable Sizes Page 4-2.

If conductors of a smaller than recommended size are used in parallel to share current then the conductors should be kept together in sets i.e. U1, V1, W1 in one conduit and U2, V2, W2 in another (see 1999 NEC Article 300-20 and Article 310-4). National and local electrical codes should be checked for possible cable derating factors if more than three power conductors are run in the same conduit (see 1999 NEC Article 310 adjustment factors on page 70-196).

Install a molded case circuit breaker (MCCB) between the power source and the inverter. Size the MCCB to clear the available fault current of the power source (see 1999 NEC Article 430 Article 102 through Article 111).

Use separate metal conduits for routing the input power, output power, and control circuits.

If the factory provided door or NEMA 1 enclosure is removed from the drive, then it must be provided with an alternate enclosure before operating. The alternate enclosure should be a minimum of NEMA 1.

Do not connect control circuit terminal block return connections marked CC to inverter earth ground terminals marked GND(E). See Standard Connection Diagrams page 4-1 and Terminal Connections and Functions page 5-3.

If a secondary Magnetic Contactor (MC) is used between the inverter output and the load, it should be interlocked so the ST-CC terminals are disconnected before the output contactor is opened. If the output contactor is used for bypass operation, it must also be interlocked so that commercial power is never applied to the inverter output terminals (U,V,W).

Power factor improvement capacitors or surge absorbers must not be installed on the inverter’s output.


What are the operating safety precautions for the TOSHIBA P3 435K?

The operating safety precautions for the TOSHIBA P3 435K are:

Do not touch any internal part with power applied to the inverter; first remove the power supply from the drive and wait until charge LED (see page 5-1 for location) is no longer illuminated. Charged capacitors can present a hazard even if source power is removed.

DO NOT OPERATE THIS UNIT WITH ITS CABINET DOOR OPEN.

Only qualified personnel should have access to the adjustments and operation of this equipment. They should be familiar with the drive operating instructions and with the machinery being driven.

Only properly trained and qualified personnel should be allowed to service this equipment. See page iii.

Follow all warnings and precautions. Do not exceed equipment ratings.

Do not power up the inverter until this entire operation manual is reviewed.

The input voltage must be within +/-10% of the specified input Voltage. Voltages outside of this permissible tolerance range may cause internal protection devices to turn on or can cause damage to the unit. Also, the input frequency should be within +/-2 Hz of the specified input frequency.

Do not use this inverter with a motor whose rated input is greater than the rated inverter output.

This inverter is designed to operate NEMA B motors. Consult the factory before using the inverter for special applications such as an explosion proof motor or one with a repetitive type piston load.

Do not apply commercial power to the output terminals T1 (U), T2 (V), or T3 (W) even if the inverter source power is off. Disconnect the inverter from the motor before megging or applying bypass voltage to the motor.

Interface problems can occur when this drive is used in conjunction with some types of process controllers. Signal isolation may be required to prevent controller and/or drive malfunction (contact Toshiba or the process controller manufacturer for additional information about compatibility and signal isolation).

Do not open and then re-close a secondary magnetic contactor (MC) between the drive and the load unless the drive is OFF (output frequency has dropped to zero) and the motor is not rotating. Abrupt re-application of the load while drive is on or while motor is rotating can cause drive damage.

Use caution when setting output frequency. Overspeeding a motor can decrease its torque-developing ability and can result in damage to the motor and/or driven equipment.

Use caution when setting the acceleration and deceleration time. Unnecessarily short times can cause tripping of the drive and mechanical stress to loads.


What final checks should be made for the wiring confirmation on the TOSHIBA P3 435K before applying power?

The following final checks should be made before applying power to the TOSHIBA P3 435K unit:

Confirm that source power is connected to terminals L 1, L2, L3 (R, S, T). Connection of incoming source power to any other terminals will damage the drive.

The 3-phase source power should be within the correct voltage and frequency tolerances.

The motor leads must be connected to terminals T1, T2, T3 (U, V, W).

Make sure there are no short circuits or inadvertent grounds and tighten any loose connector terminal screws.


What is the procedure for a start-up and test for the TOSHIBA P3 435K after installation?

Prior to releasing an electrical drive system for regular operation after installation, the system should be given a start-up test by qualified personnel. This assures correct operation of the equipment for reasons of reliable and safe performance. It is important to make arrangements for such a check and that time is allowed for it.

When power is applied for the first time, the drive automatically starts up in the frequency monitor function of standard monitor mode with the ‘default’ parameters set as shown in the “FACTORY SETTING” column of the parameter tables starting on page 8-1. If these settings are not optimal for the application, program the desired settings before initiating a run. The drive can be operated with no motor connected. Operation with no motor connected or use with a small trial motor is recommended for initial adjustment or for learning to adjust and operate the drive.


What maintenance should be performed on the TOSHIBA P3 435K?

The following maintenance should be performed on the TOSHIBA P3 435K:

Use power lockout/tagout procedures on the disconnecting means in accordance with applicable electrical codes (see 1999 NEC Article 430-101) before performing any drive maintenance.

Periodically check the operating drive for cleanliness.

Do not use liquid cleaning agents.

Keep the heatsink free of dust and debris.

Periodically check electrical connections for tightness (with power off, locked out, and with charge LED extinguished (see page 5-1 for location)).


How is the operating mode switched for the TOSHIBA P3 435K?

Operating mode switching anytime (it is not necessary to stop the drive) is performed with the LOCAL/REMOTE and MANUAL/AUTO keys.

When power is applied to an inverter, if the command mode selection is not changed from its default setting, the drive will default to terminal (frequency and run/stop) control mode. To change from local frequency control to remote frequency control, or vice versa, press the UR key.

CAUTION: If the inverter is running at 0 Hz, and the Local/Remote key is pushed, the frequency command input will be switched to a source that may be set for a non-zero frequency command, and the motor may begin turning without any other key pressed.


What are the conditions for Run/Stop commands from the LED operation panel for the TOSHIBA P3 435K?

Run/stop commands from the LED operation panel are valid for the following settings of the CMOD parameter (O=permissible, X=not permissible):

CMOD = 0 X
CMOD = 1 X
CMOD = 2 O
CMOD = 3 X
CMOD = 4 O

Run/stop commands are entered with the RUN and STOP keys.


How is the Emergency Off command executed on the TOSHIBA P3 435K in auto mode?

In auto mode, the emergency off command is executed with the following procedure (assume starting in terminal control mode with the inverter running):

The first time STOP/RESET key is pressed, emergency off command prompt “ECIFF” will be displayed.

If within two seconds, the STOP/RESET key is pressed a second time, the emergency off command will be issued with “E” displayed.

If within two seconds, STOP/RESET is not pressed a second time, the emergency off command will be aborted and the display will return to the standard monitor mode.


How is the Emergency Off command executed on the TOSHIBA P3 435K in manual mode?

In manual mode, the emergency off command is similar with that of auto mode. The first time STOP/RESET key is pressed, it will be treated as a regular stop command. Therefore, there is no “ECIFF” display.

If STOP/RESET key is pressed a second time within one second, the press will be treated as emergency off command and E will be displayed and will be continuously flashing.

If STOP/RESET key is not pressed within one second, no emergency off command will be issued.


What is the procedure for a Trip Clear Command on the TOSHIBA P3 435K?

A trip clear can be performed after the cause of the trip has been removed by using the following procedure:

When STOP/RESET is pressed the trip is cleared and the display returns to standard monitor mode.

If any key other than the STOP/RESET key is pressed at the trip clear command prompt, the trip clear command is aborted and the display returns to standard monitor mode (where the trip title will be displayed flashing). The trip clear command does not clear the recorded past faults.


What are the options for Standard Setting Selections (TYP) on the TOSHIBA P3 435K?

The TYP parameter for Standard Setting Selections on the TOSHIBA P3 435K has the following options:

TYP = 0: No effect

TYP = 1: 50Hz standard operation, maximum output frequency, base frequencies, upper limit frequency, all terminal input reference point #2 frequencies, and commercial power/inverter switching frequency are set for 50Hz operation.

TYP = 2: 60Hz standard operation, maximum output frequency, base frequencies, upper limit frequency, all terminal input reference point #2 frequencies, and commercial power/inverter switching frequency are set for 60Hz operation.

TYP = 3: Standard factory-shipped conditions (sets all parameters except those in Gr.Rn to their factory-shipped values). THIS CLEARS ALL PAST TRIPS.

TYP = 4: Trip history clear (only past trips are cleared)

TYP = 5: Saves user-set parameters

TYP = 6: Standard user-set conditions (sets all parameters to the user saved settings)

TYP = 7: Initialize inverter typeform (Used to reset a ECLJP error.)


What is the effect of setting the Retry parameter on the TOSHIBA P3 435K?

When the ree parameter is set to a value not equal to zero on the TOSHIBA P3 435K, if an overcurrent, overvoltage, or overload trip occurs during operation, the inverter will trip, and the retry sequence will begin. The retry sequence will repeatedly attempt to restart the motor, and if normal operation can be achieved and last for one second, the inverter will switch to standard monitor mode, and operation will continue from there. However, if within the set number of retry attempts, the inverter cannot be restarted, it will remain tripped, and the standard trip message will be shown.


What is the Damper Function operation when using the TOSHIBA P3 435K?

The Damper function on the TOSHIBA P3 435K is selected by both assigning code 55 (damper status input 0:damper closes, 1:damper open) to an input terminal and assigning 64 or 65 (open damper 64/65: positive/negative logic) to an output terminal. Unless both are assigned, the damper function will not work.

If “damper status” is assigned to an input terminal and “open damper” is assigned to an output terminal, damper will work in the following way:

Whenever a run command is issued, “open damper” signal is sent out to the assigned output terminal. A wait occurs until “damper status” changes to 1 (means damper open full) and motor turns on. If a stop command is issued, “open damper” will be cleared (means to close damper) after the motor stops. During a deceleration, if another run command is issued, the motor should run immediately because the damper is still open. If “damper status” input becomes 0 (means the damper closes) while the motor is running, it drive trips and flashes “dRnp”. The damper trip is non-retriable. If any inverter trip occurs, after motor stops, the damper will be closed.


How does the Fire speed Function operate on the TOSHIBA P3 435K?

The Fire speed Function on the TOSHIBA P3 435K is used to automatically start a motor at the preset speed and forward direction in case of fire. If fire status input is assigned to an input terminal (default assignment to S1 input terminal) and the inverter is not in trip, then whenever fire is detected, a run command at forward direction and the speed set by Item 131 (F5or) will be issued. Fire speed run command has the highest priority besides drive trip. In a fire situation, the motor can not be stopped by STOP command from anywhere. Before the fire signal goes off, the motor can only be stopped by a drive trip. If the fire signal is not cleared, after trip is cleared, the motor automatically will start to run again at fire speed. If any trip occurs, the motor will stop. Remember that the fire speed run command is only a run command but with the highest priority. If the damper function is also working, after the fire speed run command is issued, the first thing to do is to open the damper. The motor will not run until a “damper open full” signal is received.

Fire speed is selected by default. The default setting for fire status input is input terminal S1. The fire status input can be assigned to any input terminal by setting input terminal function to code 56. Fire speed can be set by Item 131 (F5or). Fire speed is limited by setting the upper and lower limit frequency in Item 4 (LL) and Item 3 (UL.)


How can I program the Preset Speed (Sr.n) for the TOSHIBA P3 435K?

The following programming example is for Preset Speed on the TOSHIBA P3 435K:

Group Parameter Value
UTILITY PARAMETERS Gr.Ut BLIND FUNCTION SELECTION bLnd 1
UTILITY PARAMETERS Gr.Ut FREQ SETTING PARAMETERS BLIND bLSF 1
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED SELECTION Sr.n 3
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED MODE ACTIVATION Sr.n 0
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED #1 FREQUENCY FSor 11
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED #1 OPERATING MODE Sr.n I 0
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED #2 FREQUENCY Sr02 55
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED #2 OPERATING MODE Sr.n2 0
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED #3 FREQUENCY Sr03 33.7
FREQ SETTING PARAMETERS Gr.SF PRESET SPEED #3 OPERATING MODE Sr.n3 0

This example uses “S1” and “S2” terminals to access three preset speeds of 11.0 Hz (close “S1”-“CC”), 55.0 Hz (close “S2”-“CC”), and 33.7 Hz (close “S1” and “S2” to “CC”). “F”-“CC” and “ST”-“CC” must be made on the drive’s terminal strip. This example assumes Input terminal 1 II:: 1=1 and Input terminal 2 II::2 = 2 prior to performing the following programming.


How can I program the Trim Pot Example using the “RX” terminal on the TOSHIBA P3 435K?

This example uses the “RX” terminal to trim a reference (i.e. a 4-20 mA input) +/-5 Hz on the TOSHIBA P3 435K:

Group Parameter Value
UTILITY PARAMETERS Gr.Ut BLIND FUNCTION SELECTION bLnd 1
UTILITY PARAMETERS Gr.Ut FEEDBACK CONTROL PARAMETERS BLIND bLFb 1
UTILITY PARAMETERS Gr.Ut FREQ SETTING PARAMETERS BLIND bLSF 1
FEEDBACK PARAMETERS Gr.Fb OVERRIDE CONTROL SELECT O,-d I 3
FREQ SETTING PARAMETERS Gr.SF RX TERMINAL STANDARD OR ADJUSTABLE In,-r 1
FREQ SETTING PARAMETERS Gr.SF RX INPUT REF SETTING POINT #1 , 0 %
FREQ SETTING PARAMETERS Gr.SF RX REF POINT #1 OUTPUT FREQUENCY F-PI 7 HZ
FREQ SETTING PARAMETERS Gr.SF RX INPUT REF SETTING POINT #2 O:::J ‘L 100 %
FREQ SETTING PARAMETERS Gr.SF RX REF POINT #2 OUTPUT FREQUENCY F-P2 -5 HZ

How can I program the Motor Operated Pot (MOP) or Floating Point Control for the TOSHIBA P3 435K?

The following programming allows a drive to emulate motor operated pot control. Momentarily shorting “S1”-“CC” increases frequency reference. Momentarily shorting “S2”-“CC” decreases frequency reference. Momentarily shorting “S3”-“CC” erases frequency reference. “F”-“CC” and “ST”-“CC” must be made on the drive’s terminal strip. This example assumes drive is defaulted to factory settings prior to the following programming is done:

Group Parameter Value
UTILITY PARAMETERS Gr.Ut BLIND FUNCTION SELECTION bLnd 1
UTILITY PARAMETERS Gr.Ut FREQ SETTING PARAMETERS BLIND bLSF 1
TERM SELECT PARAMETERS Gr.St INPUT TERMINAL SELECTION Ie:: 1
TERM SELECT PARAMETERS Gr.St “S1” INPUT TERMINAL FUNCTION Ie I 34
TERM SELECT PARAMETERS Gr.St “S2” INPUT TERMINAL FUNCTION Ie2 35
TERM SELECT PARAMETERS Gr.St “S3” INPUT TERMINAL FUNCTION Ie3 36
FREQ SETTING PARAMETERS Gr.SF FREQUENCY PRIORITY SELECTION #1 FC I 5

What are the necessary parameter adjustments to use True Torque Control (TTC) with a TOSHIBA/HOUSTON motor on the TOSHIBA P3 435K?

These parameters must be adjusted to use TTC with a TOSHIBA/HOUSTON motor on the TOSHIBA P3 435K:

Group Parameter Value
UTILITY PARAMETERS Gr.Ut BLIND FUNCTION SELECTION bLnd 1
UTILITY PARAMETERS Gr.Ut MOTOR PARAMETERS BLIND bLnl:: 1
FUNDAMENTAL PARAMETERS #1 Gr.F VOLTS PER FREQUENCY PATTERN PI:: 5
MOTOR PARAMETERS Gr.nl:: NUMBER OF MOTOR POLES nl::op *
MOTOR PARAMETERS Gr.nl:: MOTOR RATED CAPACITY nl::.[ *
MOTOR PARAMETERS Gr.nl:: MOTOR TYPE nl::ol:: **
MOTOR PARAMETERS Gr.nl:: LOAD MOMENT OF INERTIA nl::o iH ***

* Enter appropriate value from motor’s nameplate. KW = 0.746 X HP.

** Enter “0” for an EQPIII or “1” for a high efficiency motor.


What are the necessary parameter adjustments to use True Torque Control (TTC) with a GENERIC motor on the TOSHIBA P3 435K?

The following parameters must be adjusted to use TTC for a GENERIC motor on the TOSHIBA P3 435K:

Group Parameter Value
UTILITY PARAMETERS Gr.Ut BLIND FUNCTION SELECTION bLnd 1
UTILITY PARAMETERS Gr.Ut MOTOR PARAMETERS BLIND bLnl:: 1
FUNDAMENTAL PARAMETERS #1 Gr.F VOLTS PER FREQUENCY PATTERN PI:: 5
MOTOR PARAMETERS Gr.nl:: NUMBER OF MOTOR POLES nl::op *
MOTOR PARAMETERS Gr.nl:: MOTOR RATED CAPACITY nl::.[ *
MOTOR PARAMETERS Gr.nl:: MOTOR TYPE nl::ol:: **
MOTOR PARAMETERS Gr.nl:: MOTOR RATED VOLTAGE nl::ou 2
MOTOR PARAMETERS Gr.nl:: MOTOR RATED FREQUENCY nl::ol:: *
MOTOR PARAMETERS Gr.nl:: MOTOR RATED RPM nl::.r *
MOTOR PARAMETERS Gr.nl:: AUTO-TUNING ENABLE nl::.l::n 1****
MOTOR PARAMETERS Gr.nl:: LOAD MOMENT OF INERTIA nl::.iH ***

* Enter appropriate value from motor’s nameplate. KW = 0.746 X HP.

** Enter “0” for an EQPIII or “1” for a high efficiency motor.

**** The drive will auto tune the next time a run is initiated. This parameter is then reset to “0” by the drive’.


What is the status monitor display message when the TOSHIBA P3 435K is tripped?

When the TOSHIBA P3 435K drive is tripped, the first item displayed in status monitor mode is the output frequency at the time the drive tripped, indicated by the LED Message “50.0”.


What does the LED Message “pL n L IU” mean in the Status Monitor Messages for the TOSHIBA P3 435K?

The LED Message “pL n L IU” in the Status Monitor Messages for the TOSHIBA P3 435K indicates the currently active pattern group number and pattern speed. If the drive is not running, the group and speed numbers will appear as “PI:: -.-“.


What does the LED Message “n 1′-15” mean in the Status Monitor Messages for the TOSHIBA P3 435K?

The LED Message “n 1′-15” in the Status Monitor Messages for the TOSHIBA P3 435K indicates the Number of pattern group repetitions remaining. If the drive is not running, the number of cycles remaining will appear as “n- – -“.


What does the LED Message “S-n::J I UL” mean in the Status Monitor Messages for the TOSHIBA P3 435K?

The LED Message “S-n::J I UL” in the Status Monitor Messages for the TOSHIBA P3 435K indicates the Number of the preset speed being used. If the drive is not running, the preset speed number will appear as “5r.- -“.


What does the LED Message “2355” mean in the Status Monitor Messages for the TOSHIBA P3 435K?

The LED Message “2355” in the Status Monitor Messages for the TOSHIBA P3 435K indicates the Remaining pattern time (seconds or minutes). If the drive is not running, the remaining time will appear as “- – – -“.


What are the possible LED Messages indicating overload conditions in the Standard monitor mode for the TOSHIBA P3 435K?

The possible LED Messages indicating overload conditions in the Standard monitor mode for the TOSHIBA P3 435K are:

L: Indicates overload condition

LL: Indicates an overload and overcurrent condition

LLH: Indicates overload, overcurrent, and overheat conditions


What are the possible LED Messages indicating overvoltage conditions in the Standard monitor mode for the TOSHIBA P3 435K?

The possible LED Messages indicating overvoltage conditions in the Standard monitor mode for the TOSHIBA P3 435K are:

P: Indicates overvoltage condition


What are the possible LED Messages indicating overcurrent conditions in the Standard monitor mode for the TOSHIBA P3 435K?

The possible LED Messages indicating overcurrent conditions in the Standard monitor mode for the TOSHIBA P3 435K are:

r: Indicates overcurrent condition

LL: Indicates an overload and overcurrent condition

LLH: Indicates overload, overcurrent, and overheat conditions


What are the possible LED Messages indicating overheat conditions in the Standard monitor mode for the TOSHIBA P3 435K?

The possible LED Messages indicating overheat conditions in the Standard monitor mode for the TOSHIBA P3 435K are:

H: Indicates overheat condition


What are the possible LED Messages indicating communication timeout conditions in the Standard monitor mode for the TOSHIBA P3 435K?

The possible LED Messages indicating communication timeout conditions in the Standard monitor mode for the TOSHIBA P3 435K are:

e: Indicates communication timeout condition


What are the available Mode Selections in the Mode selection menu for the TOSHIBA P3 435K?

The available Mode selections in the Mode selection menu for the TOSHIBA P3 435K are:

Mode selections Explanation
SEeP Setup mode selection
PrOG Program mode selection
n on Status monitor mode selection

What is the procedure for accessing and editing a setup parameter starting from standard monitor mode on the TOSHIBA P3 435K?

The procedure for accessing and editing a setup parameter on the TOSHIBA P3 435K starting from standard monitor mode is:

LED Message nn LJ.LJ: Standard monitor mode (current output frequency displayed)

Key Operation S/P/M: Display changes to the first entry in the mode selection menu, SEeP (SETUP modeL

Key Operation RIW: Display changes to the first entry in the setup parameter list, RCC i (Acceleration time #1).

Key Operation ‘\7 dEC i: Assume we want to change upper limit frequency to 70.0 Hz. Pressing the U/D keys scrolls through the list of setup parameter titles until Ui is displayed.

Key Operation RIW: Pressing R/W selects the currently displayed parameter and displays its current setting value.

Key Operation XXX.x: Setting value increases.

Key Operation (press and hold) Release up key: Releasing the up key causes the setting value to stop increasing. The data will flash to indicate that the displayed value (RAM) has been changed from the non-volatile memory value.

Key Operation RIW: When the read/write key is pressed, the parameter name, UL, and the new setting value will be alternately displayed to indicate that the new setting value has been written to memory. After two alternating display cycles, the display will return to setup mode, with the parameter title UL displayed.


What are the P3 setup parameter titles for the TOSHIBA P3 435K?

The P3 setup parameter titles for the TOSHIBA P3 435K are:

P3 setup parameter titles Explanation
01 r I IILL I Acceleration time #1
dEC : Deceleration time #1
III UL Upper limit frequency
I I LL Lower limit frequency
SFl:l Local/Remote and Manual/Auto switch on the fly
:u :n IV input selection
P3 IV reference point #1
F-P3 IV reference point #1 frequency
PY IV reference point #2
F-PY IV reference point #2 frequency
I::H,- : Motor overload rating
51::[ : Stall selection
Sl::l : Stall level #1
nl n ULII Motor overload selection
Oll:: Motor 110% overload time limit
ROI IL Application parameters selection
I:::lP Standard setting mode
PRSS Pass number

What is the procedure to change parameter settings when in Program Mode on the TOSHIBA P3 435K?

The process to change parameter settings when in Program Mode on the TOSHIBA P3 435K is as follows:

Switch to program mode.

At the group title display, switch to the parameter’s group name by using the U/D keys. Press RIW key.

At the parameter title display, switch to the desired parameter by using the U/D keys. Press RIW key.

When the data is displayed, change it by using the U/D keys.

Press RIW key to write the data to the PPROM.


What is the example of changing the setting for acceleration time #1 to 20s (assuming power has just been applied to the inverter) when in Program Mode on the TOSHIBA P3 435K?

The example of changing the setting for acceleration time #1 to 20s when in Program Mode on the TOSHIBA P3 435K is:

Key Operation LED Message Explanation
nn u.u Standard monitor mode (current output frequency displayed)
S/P/M SEeP Switch to mode selection menu.
S/P/M o m 1 ruu Select program mode title with U/D keys.
RIW LJr.U Select program mode by pressing RIW key. First program group title is displayed.
u/u LJ I .1 :: select desired group title uSing the u/u Keys.
RIW FH Enter parameter group by pressing the R/W key. First parameter title in the group is displayed.
U/D 01 r 1 IILL I Select desired parameter using the U/D keys
RIW Inri IU.U Read parameter setting value by pressing the R/W key.
U/D ..,nn cu.u Adjust setting value to desired value.
RIW R[L :~20.0 Write new setting value to memory by pressing the R/W key. The parameter title and the new setting value will flash alternately for two cycles. Then the title Acc1 is displayed. 01 r I IILL I Display returns to program mode (parameter title display).

What are the P3 LED messages for Group contents in Program Mode for the TOSHIBA P3 435K?

The P3 LED messages for Group contents in Program Mode for the TOSHIBA P3 435K are:

P3 LED message Group contents Blind/Unblind default
r LI r.LI “ Parameters changed from factory default settings Unblinded
~,-.F Fundamental inverter operation parameters #1 Unblinded
[;,-.F 2 Fundamental inverter operation parameter #2. Blinded
Lw.Pn Panel control parameters Blinded
Lw.5f.: Terminal block selection parameters Unblinded
u,-.SL Special control parameters Unblinded
[;,-.5F Frequency setting parameters Blinded
Lw.Pr Protection function parameters Unblinded
Lw.Pf.: Pattern run control parameters Blinded
Lw.Fb Feedback control parameters Unblinded
[;,-.f.: r Communication parameters Unblinded
I _ n I UI.U I Pump application macro Unblinded
Lw.02 Fan application macro Unblinded
u,-.03 Cooling tower application macro Unblinded
r_on UI.IIII AM/FM output terminal adjustment parameters Unblinded
[;,-.Uf.: Utility parameters Unblinded
[;,-.nf.: Motor rating parameters Blinded

What is the explanation for the LED Message “E” in the Inverter Trip Codes for the TOSHIBA P3 435K?

The LED Message “E” in the Inverter Trip Codes for the TOSHIBA P3 435K means Emergency off trip message. It is displayed after the STOP/RESET key has been pressed once when in auto control mode, or press STOP/RESET key twice within one second in manual control mode.


What is the purpose of Item 313, PANEL OPERATION MODE SELECTION (pnOd), in the Utility Parameters for the TOSHIBA P3 435K?

Item 313, PANEL OPERATION MODE SELECTION (pnOd), in the Utility Parameters for the TOSHIBA P3 435K limits what can be done via the keypad. Panel “emergency stop” in remote mode is always valid.

The values entered here that are zero or are a power of two have one function assigned to them:

0: Keypad does nothing except switching between forward/reverse in manual mode

1: Reset drive fault only

2: Monitor only

4: “emergency stop” only

8: Run/Stop only

16: Read parameters only

32: Change parameters only

The rest of the possible parameter values are combinations of the above.

Note: to “change parameters only”, “read parameters only” should also be selected (See option 48)


What is the procedure to RESET AFTER OPTION “0” HAS BEEN PROGRAMMED IN ITEM 313 (pnOd) for the TOSHIBA P3 435K?

The procedure to RESET AFTER OPTION “0” HAS BEEN PROGRAMMED IN ITEM 313 (pnOd) for the TOSHIBA P3 435K is:

Press four keys simultaneously: LOCAUREMOTE, SPM, RIW, and up arrow

Drive will return to Item 314 and display: 0

If: 0 doesn’t appear after pressing the four keys, cycle power and try again.

Enter pass number between 00 – 99 with up/down arrows and press READIWRT. Pass number is programmed in Item 314 (PR55).

If pass number is entered correctly Item 313 (pnOd) will be reset to option 63, allowing all keypad operations; if entered incorrectly Err will be displayed.


What are the item descriptions for Fundamental Parameters #1 (Gr.F) in the Program Mode for the TOSHIBA P3 435K?

The item descriptions for Fundamental Parameters #1 (Gr.F) in the Program Mode for the TOSHIBA P3 435K are:

DISPLAY NO. ITEM NO. PARAMETER DESCRIPTION ADJUSTMENT RANGE DISPLAY RESOLUTION FACTORY SETTING PAGE NO.
FH 19 Maximum output frequency 30 – 400 Hz 0.01/0.1 Hz 80 Hz 9-3
uL I 20 Base frequency #1 25 – 400 Hz 0.01/0.1 Hz 60 Hz 9-3
uL5L 21 Base frequency voltage selection 0: Input voltage level, 1: Automatic setting, 2: Stationary setting 9-3
ulu I 22 Maximum voltage #1 for 460V 0 – 510V 1V 460V 9-3
d iSr 23 Reverse operation disable selection 0: Reverse allowed, 1: Reverse not allowed 0 9-3
UL 24 Upper limit frequency 0.0 Hz – FH 0.01/0.1 Hz 60.0 9-3
LL 25 Lower limit frequency 0.0 Hz -UL 0.01/0.1 Hz 0.0 9-3
Pc 26 V/F pattern 1: Constant torque *, 2: Variable torque, 3: Automatic torque boost, 4: Automatic torque boost with automatic energy saving, 5: Vector control, 6: Vector control with automatic energy saving 2 9-3
ub I 27 Voltage boost #1 for all drives 0 – 30% 0.1% 1% 9-3
RCC i 28 Acceleration time #1 0.1 – 6000s/0.01 – 600.0s 0.1s/0.01s 60.0 9-4
dEC i 29 Deceleration time #1 0.1 – 6000s/0.01 – 600.0s 0.1s/0.01s 60.0 9-4
S[LI i 30 Acc/Dec pattern #1 0: Linear, 1: Self-adjusting, 2: S-Pattern #1, 3: S-Pattern #2 0 9-4
SCL 31 Acc/Dec pattern adjustment amounts (low) 0 – 50 1% 25 9-4
SCH 32 Acc/Dec pattern adjustment amounts (high) 0 – 50 1% 25 9-4

What are the item descriptions for Fundamental Parameters #2 (Gr.F2) in the Program Mode for the TOSHIBA P3 435K?

The item descriptions for Fundamental Parameters #2 (Gr.F2) in the Program Mode for the TOSHIBA P3 435K are:

DISPLAY NO. ITEM NO. PARAMETER DESCRIPTION ADJUSTMENT RANGE DISPLAY RESOLUTION FACTORY SETTING PAGE NO.
uL2 33 Base frequency #2 25 – 400 Hz 0.01/0.1 Hz 60.0 9-5
uLu2 34 Maximum voltage #2 for 460V 0 – 510V 1V 460V 9-5
ub2 35 Voltage boost #2 for all sizes 0 – 30% 0.1% 1% 9-5
I::H,-2 36 Electronic thermal protection level #2 10 – 100%/A 1%/A 100 9-5
5I::C2 37 Stall protection enable #2 0: On, 1: Off 0 9-5
SEL2 38 Stall protection current limit adjustment #2 10 – 215%/A 1%/A 110.0 9-5
RCC2 39 Acceleration time #2 0.1 – 6000s/0.01 – 600.0s 0.1s/0.01s 60.0 9-5
dEC2 40 Deceleration time #2 0.1 – 6000s/0.01 – 600.0s 0.1s/0.01s 60.0 9-5
5[u2 41 Acc/Dec pattern #2 0: Linear, 1: Self-adjusting, 2: S-Pattern #1, 3: S-Pattern #2 0 9-5
Rd2F 42 Acc/Dec #1/#2 switching frequency 0 – FH (max. freq.) 0.1/0.01 Hz 0.0 9-5

What are the PANEL CONTROL PARAMETERS (Gr.Pn) for the TOSHIBA P3 435K?

DISPLAY NO. ITEM NO. PARAMETER DESCRIPTION ADJUSTMENT RANGE DISPLAY RESOLUTION FACTORY SETTING PAGE NO.
Fr 43 Forward/reverse 0: Reverse, 1 : Forward 1 9-6
ScPP 44 Stop pattern selection 0: Decelerated stop, 1 : Coast stop 0 9-6
PcP 45 Fundamental parameter #1 or #2 selection 1 : Fundamental parameter #1, 2: Fundamental parameter #2 1 9-6
Rd2 46 Acc/dec #1 or #2 selection 1 : Acc/dec #1, 2: Acc/dec #2 1 9-6
PrES 47 Panel reset selection 0: All possible, 1 : Only OL can be reset, 2: Only OL, OC1 , OC2, OC3 can be reset 0 9-6
PFbC 48 Panel feedback control (PID, speed feedback, drooping) 0: On (valid when panel operation is selected), 1 : Off (invalid when panel operation is selected) 0 9-6
SFL:l 49 Switch on fly 0: Off, 1 : On —- 0 9-6

What are the TERMINAL SELECTION PARAMETERS (Gr.St) for the TOSHIBA P3 435K?

The TERMINAL SELECTION PARAMETERS (Gr.St) for the TOSHIBA P3 435K include settings for Input terminal selection (Item 50), Input terminal response times (Items 63-66), Output terminal function selections (Items 67, 70, 73, 76), Output terminal delay times (Items 68, 71, 74, 77), Output terminal hold times (Items 69, 72, 75, 78), Low speed signal output frequency (Item 79), Acc/Dec complete detection bandwidth (Item 80), Speed reach HI frequency (Item 81), Speed reach LO frequency (Item 82), Commercial Power/Inverter Switching Output (Item 83), Commercial Power/Inverter Switching Frequency (Item 84), Output terminal pulse frequency selection (Item 85), and RR input special function selection (Item 86).


What is the function realized when Input terminal 4 (S4) is open to “CC” for the TOSHIBA P3 435K?

Different with respect to all of the other input terminals; sets the function realized when the “S4” terminal is open to “CC” for the TOSHIBA P3 435K. When S4 is open to “CC”, it is the emergency off command and motor will not run. Default setting is emergency off.


What is the default setting for Input terminal 56 (“F” INPUT TERMINAL FUNCTION) on the TOSHIBA P3 435K?

The default setting for Input terminal 56 (“F” INPUT TERMINAL FUNCTION) on the TOSHIBA P3 435K gives a forward run command when the “F” terminal is shorted to “CC”.


What are the function codes for Input Terminal Functions on the TOSHIBA P3 435K?

The function codes for Input Terminal Functions on the TOSHIBA P3 435K are:

0: Reverse direction command (default for “R” terminal function)

1: Binary coding for number of preset speed desired. Value: + 1

2: Binary coding for number of preset speed desired. Value: +2

3: Binary coding for number of preset speed desired. Value: +4 (default for “S3” terminal function)

4: Binary coding for number of preset speed desired. Value: +8

5: Forward direction command (default for “F” terminal function)

6: Reset faults (momentary falling-edge trigger) (default for “RES” terminal function)

7: Drive enable (default for “ST” terminal function)

8: Jog (also need direction command). See items 128 and 129.

9: Select ACC1/DEC1 (open) or ACC2/DEC2 (closed to “CC”)

10: Emergency stop. Also see Item 170, EMERGENCY STOP SELECTION (E5I:P).

11: DC injection. When outputting a frequency under DC INJECTION START FREQUENCY (dbF), short terminal to “CC” to inject. See Items 165, 166, and 167. Works in remote mode only.

12: Activate GROUP: FUNDAMENTAL PARAMETERS #1 (Gr.F )(open) or GROUP: FUNDAMENTAL PARAMETERS #2 (Gr.F2) (closed to “CC”)

13: PID off (closed to “CC”) or on (open)

14: Select Pattern Run #1

15: Select Pattern Run #2

16: Select Pattern Run #3

17: Select Pattern Run #4

18: Pattern Run continue signal

19: Pattern Run step signal

20: Jog forward (includes forward command). See items 127 and 128.

21: Jog reverse (includes reverse command). See items 127 and 128.

22: Bit #0 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/2048)

23: Bit #1 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/1024)

24: Bit #2 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/512)

25: Bit #3 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/256)

26: Bit #4 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/128)

27: Bit #5 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/64)

28: Bit #6 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/32)

29: Bit #7 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/16)

30: Bit #8 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/8)

31: Bit #9 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(FH)/4)

32: Bit #10 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY(F H)/2)

33: no function (use terminal to connect wires)

34: Motor operated pot: increase frequency reference

35: Motor operated pot: decrease frequency reference

36: Motor operated pot: clear frequency reference

37: Three wire control: NO momentary start push button

38: Three wire control: NO momentary stop push button. Contact factory for information on how to realize stop with a NC contact.

39: emulate local/remote mode selection

40: Forward (open) or reverse (closed to “CC”) command

41: Run (use in conjunction with code 40 above)

42: Binary data write (use with 22-32 above). If no input terminal’s function is set to “42”, the drive responds immediately to binary references commanded by changing data bits. If one of the input terminal’s function is set to “42”, the drive responds to binary reference only when terminal is closed to “CC”. Binary reference is lost when power is cycled.

43: emulate LOCAL/REMOTE key

44: emulate MANUAL/AUTO key

45: emulate SETUP/PROGRAM/MONITOR key

46: emulate UP key

47: emulate DOWN key

48: emulate READIWRITE key

49: emulate RUN key

50: emulate STOP key

51: Drive/bypass switching signal

52: Reserved for option

53: give “RR” priority over “IV” and “RX”

54: give “IV” priority over “RR” and “RX”

55: damper status input: 1: damper open, 0: damper closes

56: Firespeed ON/OFF

57: Inverter Overload (Olm:) ENABLE/DISABLE


What are the Output Contacts Functions available for the TOSHIBA P3 435K?

The Output Contacts Functions for the TOSHIBA P3 435K are:

0: Contact will close when drive is at or above Item 7, LOWER LIMIT FREQUENCY (LL)

1: Contact will close when drive is not at or above LL (see value 0 above)

2: Contacts will close when drive is at Item 6, UPPER LIMIT FREQUENCY (UL)

3: Contacts will close when drive is not at UL (see value 2 above)

4: Default for LOWAILOWC terminals. Contact will close when drive is at or above speed in Item 79, LOW SPEED SIGNAL OUTPUT FREQUENCY (LF)

5: Contact will close when drive is not at or above LF (see value 4 above)

6: Default for RCHAIRCHC terminals. Contact closes when any accel or decel is complete.

7: Contact closes when any acceleration or deceleration is not complete (see value 6 above).

8: Contact closes when drive is at or above Item 81, SPEED REACH MAXIMUM FREQUENCY (H,-CH) during accel or when drive is at or above Item 82, SPEED REACH MINIMUM FREQUENCY (L,-CH) during decel

9: Contact closes when drive is not at or above H,-CH during accel or when drive is not at or above LrCH during decel (see value 8 above).

10: Default for FLAlFLB/FLC terminals. Contact closes when drive is faulted (E OF F is not a fault)

11: Contact closes when drive is not faulted.

12: Contact closes when drive is faulted on anything except EARTH FAULT (EF I, EF2) or LOAD END OVERCURRENT (DCL) (“emergency stop” EDFF is not a fault)

13: Contact closes when drive is faulted on EF I, EF2 or DCL (see value 12 above)

14: Contact closes when overcurrent stall is active (use as overcurrent pre-alarm). The stall current level is adjustable via Item 182 (SEL I) or Item 38 (SEL2).

15: Contact closes when overcurrent stall is not active. The stall current level is adjustable via Item 182 (SEL I) or Item 38 (SEL2) (see value 14 above).

16: Contact closes to signify inverter overload pre-alarm. Example of inverter overload: E3 is rated for 110% of rated current for 2 minutes. If drive is operated at 110% of rated current for 60 secs, the inverter overload is at 50%, or half of its overload current-time capability. The drive trips on overload at 100%.

17: Contact closes to signify drive is not in an overload pre-alarm. See explanation for value 16 above.

18: Contact closes to signify motor overload pre-alarm. See explanation for value 16 above.

19: Contact closes to signify motor is not in an overload pre-alarm. See explanation for value 16 above.

20: Contact closes when heatsink reaches 84deg C. Contact opens at 80deg C after it has closed

21: Contact closes when heatsink is under 84 deg C. Contact closes at 80deg C after it has opened

22: Contact closes when drive is displaying “overvoltage” P. See page 11-7.

23: Contact closes when drive is not displaying “overvoltage” P. See page 11-7.

24: Contact closes when drive is displaying “undervoltage” nDF F. See page 11-7.

25: Contact closes when is not displaying “undervoltage” nDFF. See page 11-7.

26: Contact closes when output current is at or greater than the current programmed into Item 186, LOW CURRENT DETECTION LEVEL (LLPC) for longer than the time programmed in Item 187, LOW CURRENT DETECTION TIME (LLPc)

27: Contact closes when output current is not at or greater than the current programmed into LLPC for longer than the time programmed in LLPc (see value 27 above).

28: Contact closes when torque current equals or exceeds the setting programmed into Item 190, OVERTORQUE TRIP LEVEL (DEL).

29: Contact closes when torque current does not equal or exceed the setting programmed into DEL (see value 28 above).

30: Contact closes when dynamic braking resistor is half way or more into its overload ascalculated by the drive based upon the setting in Item 162, BRAKING RESISTOR VALUE (Pbr) and Item 163, BRAKING RESISTOR POWER RATING (PbCP). See explanation of overload for Value 16.

31: Contact closes when dynamic braking resistor is less than half way into its overload as calculated by the drive based upon the settings in Pbr and Pb[P (see value 30 on previous page).

32: Contact closes when drive is executing an “emergency stop”

33: Contact closes when drive is not executing an “emergency stop”

34: Contact closes when drive is executing a retry

35: Contact closes when the drive is not executing a retry

36: Contact closes when drive is running a Pattern Run

37: Contact closes when drive is not running a Pattern Run

38: Contact closes when the error signal calculated by the drive’s PID equals or exceeds the value programmed into Item 273, PID DEVIATION UPPER LIMIT (PLlUL) or Item 274, PID DEVIATION LOWER LIMIT (PULL).

39: Contact closes when the error signal calculated by the drive’s PID does not equal or exceed the value programmed into PLiUL or PULL (see value 38 above).

40: Contact closes when drive is running at or above 0.01 Hz.

41: Contact closes when drive is not running at or above 0.01 Hz.

42: Contact closes when drive is faulted on a “severe” fault (not retryable) *

43: Contact closes when drive is not faulted on a “severe” fault (not retryable) *

44: Contact closes when drive is tripped on a retryable fault *

45: Contact closes when drive is not tripped on a retryable fault *

46: Auto-bypass control. Contact closes to energize coil of output contactor.

47: Opposite logic state (see value 46 above)

48: Auto-bypass control. Contact closes to energize coil of bypass contactor.

49: Opposite logic state (see value 48 above)

50: Contact closes when drive’s cooling fan(s) is on.

51: Contact closes when drive’s cooling fan(s) is not on.

52: Contact closes when drive is jogging

53: Contact closes when drive is not jogging

54: Contact closes when drive is getting RUN/STOP command from the keypad

55: Contact closes when drive is not getting RUN/STOP command from the keypad

56: Contact closes when drive run time is greater than or equal to time programmed into Item 193, CUMULATIVE RUN TIMER ALARM SETTING (IJLlc).

57: Contact closes when drive run time is not greater than or equal to time programmed into IJ& (see value 56 above)

58: Contact closes when drive trips on a “communication error” ErrS

59: Contact closes when drive does not have a ErrS (see value 58 above)

60: Contact changes state when drive goes through 0.0 Hz to change direction. Contact is closed/open during forward/reverse run. Contact maintains current condition at 0.0 Hz when decel is complete after a stop command.

61: Contact changes state when drive goes through 0.0 Hz to change direction. Contact is open/closed during forward/reverse run. Contact maintains current condition at 0.0 Hz when decel is complete after a stop command.

62: Contact closes when drive has a run command and ST-CC is made

63: Contact closes when drive does not have a run command

64: Open/Close damper. Contact close: open damper.

65: Opposite logic state (see value 64 above)

66: IV analog input loss warning. ON: IV lost. Valid when Item 194 (LR IS) adjustment range option: 0 is not selected.

67: Opposite logic state (see value 66 above)

* Retryable faults include: OVERCURRENT(ACCEL) IJ[ I, OVERCURRENT(DECEL) IJ[2, OVERCURRENT(RUN) IJ[3, DC OVERCURENT(ACC) IJ[ IP, DC OVERCURRENT (DEC) IJ[2P, DC OVERCURRENT(RUN) IJ[3P, OVERVOLTAGE(ACCEL) IJP I, OVERVOLTAGE(DECEL) IJP2, OVERVOLTAGE(RUN) IJP3, OVERHEAT IJH, MOTOR OVERLOAD IJLilc, INVERTER OVERLOAD IJL In, DBR OVERLOAD TRIP IJLr


What are the Drive Fault Displays and Explanations for OVERCURRENT (ACCEL) D[ i or DC OVERCURRENT (ACC) D[ iP on the TOSHIBA P3 435K?

For OVERCURRENT (ACCEL) D[ i or DC OVERCURRENT (ACC) D[ iP on the TOSHIBA P3 435K:

Cause: Drive current exceeded 145% of its rated FLA (190% above 100 HP).

Comments: Check for phase-phase short. ACCELERATION TIME R[[ i or R[[2 may be too small. VOLTAGE BOOST Lib i or Llb2 may be too high. Is motor/machine jammed? Is mechanical brake engaged while drive is running? If drive is starting into a rotating motor, see Item 176, AUTO-RESTART RrSc . If there is a contactor between motor and drive, wire so that contactor changes state only when drive is outputting 0.0 Hz. Drive will automatically adjust accel time with Item 30, ACC/DEC PATTERN #1 S[LI i set to option “1”.


What are the Drive Fault Displays and Explanations for OVERCURRENT (DECEL) D[2 or DC OVERCURRENT (DEC) D[2P on the TOSHIBA P3 435K?

For OVERCURRENT (DECEL) D[2 or DC OVERCURRENT (DEC) D[2P on the TOSHIBA P3 435K:

Cause: Drive current exceeded 145% of its rated FLA.

Comments: Check for phase-phase short. DECELERATION TIME dEC i or dE[2 may be too small. Is motor/machine jammed? Is mechanical brake engaged while drive is running? Adding appropriate braking resistor across “PA” and “PB” terminals may solve problem (see page 9-20). Drive will automatically adjust decel time with Item 30, ACC/DEC PATTERN #1 S[LI i option set to “1”.


What are the Drive Fault Displays and Explanations for OVERCURRENT (RUN) D[3 or DC OVERCURRENT (RUN) D[3P on the TOSHIBA P3 435K?

For OVERCURRENT (RUN) D[3 or DC OVERCURRENT (RUN) D[3P on the TOSHIBA P3 435K:

Cause: Drive current exceeded 145% of its rated FLA.

Comments: Check for phase-phase short. Is motor/machine jammed? Is mechanical brake engaged while drive is running? Adding appropriate dynamic braking resistor across “PA” and “PB” terminals may solve problem (see page 9-20). If there are severe load fluctuations, adding mechanical dampening or an output line reactor may help to electrically dampen.


What are the Drive Fault Displays and Explanations for U-PHASE SHORT-CIRCUIT OCR I or V PHASE SHORT-CIRCUIT O[R2 or W PHASE SHORT-CIRCUIT O[R3 on the TOSHIBA P3 435K?

For U-PHASE SHORT-CIRCUIT OCR I or V PHASE SHORT-CIRCUIT O[R2 or W PHASE SHORT-CIRCUIT O[R3 on the TOSHIBA P3 435K:

Cause: Drive detected short-circuit in transistor.

Comments: Replace transistor. Contact your Toshiba distributor for authorized repair.


What are the Drive Fault Displays and Explanations for LOAD-END OVERCURRENT O[l on the TOSHIBA P3 435K?

For LOAD-END OVERCURRENT O[l on the TOSHIBA P3 435K:

Cause: Drive detected short-circuit on output.

Comments: Check for phase-phase short. Meg motor/leads with leads disconnected from drive. Remove any power factor correction caps on motor. See Item 169, OUTPUT SHORT CIRCUIT DETECTION SELECT.


What are the Drive Fault Displays and Explanations for OVERVOLTAGE (ACCEL) OP I or OVERVOLTAGE (RUN) O[P3 on the TOSHIBA P3 435K?

For OVERVOLTAGE (ACCEL) OP I or OVERVOLTAGE (RUN) O[P3 on the TOSHIBA P3 435K:

Cause: Bus exceeded 787 VDC (460 volt drive).

Comments: Incoming AC may have gone high or spiked (verify with Item 319,320, 321, or 322 set to option “16”); a line reactor or a lower tap on transformer may help. Motor may be mechanically forced to run faster than drive is commanding; install appropriate dynamic braking resistor (see page 9-20). On eccentric cyclic loads like presses or pump jacks, contact your Toshiba distributor for special programming instructions that may make a DBR unnecessary.


What are the Drive Fault Displays and Explanations for OVERVOLTAGE (DEC) O[P2 on the TOSHIBA P3 435K?

For OVERVOLTAGE (DEC) O[P2 on the TOSHIBA P3 435K:

Cause: Bus exceeded 787 VDC (460 volt drive).

Comments: Incoming AC may have gone high or spiked (verify with Item 319 set to option “16”); a line reactor or a lower tap on transformer may help. Item 2, DECELERATION TIME #1 O[P2 may be too short. Drive will automatically change decel time with Item 31, ACC/DEC PATTERN ADJUST LOW 5[l option set to “1 “. Make sure Item 164, OVERVOLTAGE STALL PROTECTION OP55 is set to option “0”. Motor may be mechanically forced to run faster than drive is commanding (due to large load inertias mechanical couplings); install appropriate dynamic braking resistor (see page 9-20). On eccentric cyclic loads like presses or pump jacks, contact your Toshiba distributor for special programming instructions that may make a DBR unnecessary.


What are the Drive Fault Displays and Explanations for INVERTER OVERLOAD Ol In on the TOSHIBA P3 435K?

For INVERTER OVERLOAD Ol In on the TOSHIBA P3 435K:

Cause: Drive exceeded 100% of its rated current for too long of a time.

Comments: This trip indicates that the drive output exceeded its rated current for specific amounts of time. For example, drives can output 110% of their rated current for 60 seconds, and 150% for 0.5 seconds. If using DC Injection, Item 166, DC INJECTION CURRENT db[ or Item 167 DC INJECTION TIME dbe they may be too large. If Item 98, PWM CARRIER FREQUENCY [F is greater than 8 KHz, try carrier frequencies less than 8 KHz. Programming Item 14, OVER LOAD SELECTION Oln to option”1″ or “3” (soft stall on) makes the drive reduce output frequency/voltage to shed load (works best on variable torque applications). Motor or load bearings may have seized. Enabling True Torque Control (see page 1 0-7) may reduce drive’s current output and solve the problem. Make sure that drive is seeing voltage on all three input phases. Drive may be undersized.


What are the Drive Fault Displays and Explanations for MOTOR OVERLOAD Olile on the TOSHIBA P3 435K?

For MOTOR OVERLOAD Olile on the TOSHIBA P3 435K:

Cause: Motor is in danger of overheating because it drew too much current for too long of a time, as determined by the drive.

Comments: See page 8-14. Check Items 178, 179, 180, and 181. If trip occurred at a low frequency, the setting of Item 179, OVERLOAD REDUCTION START FREQUENCY OlF is probably critical. Motor overload protection can be turned off by placing a “2” or “3” in Item 181. Check value in Item 180, MOTOR 110% OVERLOAD TIME LIMIT Ole.


What are the Drive Fault Displays and Explanations for DBR OVERCURRENT 0[,- on the TOSHIBA P3 435K?

For DBR OVERCURRENT 0[,- on the TOSHIBA P3 435K:

Cause: IGBT7 (dynamic braking transistor) is damaged

Comments: Check ohm value connected to “PA” and “PB” terminals (see page 9-20 for minimum ohm values). If using multiple resistors, make sure parallel-series combination is wired correctly. Check IGBT7. Check DC bus fuse for continuity; if open, check output transistors. Consult your Toshiba distributor for authorized service.


What are the Drive Fault Displays and Explanations for DBR OVERLOAD OL,- on the TOSHIBA P3 435K?

For DBR OVERLOAD OL,- on the TOSHIBA P3 435K:

Cause: Dynamic braking resistor is in danger of overheating (as determined by drive).

Comments: Check that the values entered into Item 162, BRAKING RESISTOR VALUE Pbr and Item 163, BRAKING RESISTOR CAPACITY Pb[P are correct.


What are the Drive Fault Displays and Explanations for OVERHEAT OH on the TOSHIBA P3 435K?

For OVERHEAT OH on the TOSHIBA P3 435K:

Cause: Drive’s heatsink exceeded 90deg C.

Comments: Check drive’s muffin fans (if any). Clear heatsinks of anything blocking airflow. The enclosure that the drive is installed in may be too small or there may be to many heat sources in the same enclosure. Drive may not have been properly sized for operating altitude. Thermistor on heatsink may be bad.


What are the causes for EMERGENCY OFF E on the TOSHIBA P3 435K?

The causes for EMERGENCY OFF E on the TOSHIBA P3 435K are:

Drive received one of the following ESTOP commands:

1. Drive was receiving STOP/RUN command via terminal strip when STOP button on keypad was pressed.

2. One of the drive’s input terminal’s function is set to “10” (see Item codes 0-56 and page 9-11), and terminal is being opened/closed to command ESTOP.


What are the EEPROM related faults (EEPROM WRITE FAILURE or EEPROM READ FAILURE) on the TOSHIBA P3 435K?

For EEPROM WRITE FAILURE or EEPROM READ FAILURE (EEP:, EEP2) on the TOSHIBA P3 435K:

Cause: EEPROM was unable to read/write to peripherals.

Comments: Check for miswiring that may be causing noise (such as “CC” connected to ground, an external 10 volt source connected to “PP” etc.) Control board may need to be replaced. See picture of board on page 5-2.


What are the RAM ERROR or ROM ERROR faults (Err3, Err4) on the TOSHIBA P3 435K?

For RAM ERROR or ROM ERROR (Err3, Err4) on the TOSHIBA P3 435K:

Comments: Check for miswiring that may be causing noise (such as “CC” connected to ground, an external 10 volt source connected to “PP” etc.). Replace control board. See picture of board on page 5-2.


What is the cause for OPTION ROM ERROR Err5 on the TOSHIBA P3 435K?

For OPTION ROM ERROR Err5 on the TOSHIBA P3 435K:

Comments: Check for miswiring that may be causing noise (such as “CC” connected to ground, an external 10 volt source connected to “PP” etc.). If drive is energized with option ROM installed and is later energized without option ROM installed, this fault will appear. Reset in normal fashion.


What are the causes and comments for CPU ERROR ErrY on the TOSHIBA P3 435K?

For CPU ERROR ErrY on the TOSHIBA P3 435K:

Comments: If option ROM or option board is installed or removed when drive is powered, this fault will appear. Reset like any fault. Check for miswiring that may be causing noise (such as “CC” connected to ground, an external 10 volt source connected to “PP” etc.). If the CPU is truly damaged, the fault will not reset and replacement of the control board is necessary. See picture of control board on page 5-2.


What are the causes and comments for COMMUNICATION ERROR ErrS on the TOSHIBA P3 435K?

For COMMUNICATION ERROR ErrS on the TOSHIBA P3 435K:

Cause: RS232 or RS485 timer did not respond

Comments: Check wiring to RS232 or RS485 ports. Check setting of Item 286, COMMUNICATION SELECTION OPt (should be option “1” for RS485). Check jumpers J1, J2, and J3 on RS485 option board (see RS485 Communications Option Manual). Cable may be broken.


What are the causes and comments for OPTION PCB ERROR Err8 on the TOSHIBA P3 435K?

For OPTION PCB ERROR Err8 on the TOSHIBA P3 435K:

Comments: If drive is energized with an option board installed and is later energized without the board installed, this fault will appear. Check connectors between control board and option board. Check settings of Item 99, FREQUENCY PRIORITY SELECTION #1 F[ I, Item 100, FREQUENCY PRIORITY SELECTION #2 F[2, and Item 286, COMMUNICATION SELECTION DPe. Use stand-ofts to secure board.


What are the causes and comments for LOW CURRENT TRIP LI[ on the TOSHIBA P3 435K?

For LOW CURRENT TRIP LI[ on the TOSHIBA P3 435K:

Cause: The drive’s output current went below the current value entered in Item 186, LOW CURRENT DETECT LEVEL LLP[ for at least the amount of time entered in Item 187, LOW CURRENT DETECTION TIME LLPe.


What are the causes and comments for UNDERVOLTAGE TRIP LIP I on the TOSHIBA P3 435K?

For UNDERVOLTAGE TRIP LIP I on the TOSHIBA P3 435K:

Cause: The drive’s DC bus voltage went below 413 VDC (460 V P3), for at least the time entered in Item 185, UNDERVOLTAGE DETECT TIME LlPe.

Comments: Item 184, UNDERVOLTAGE TRIP SELECTION LlP5L turns the ability to undervoltage trip on/off. On some models, turning on Item 174, REGENERATION POWER RIDE-THROUGH LlLI[ and adjusting Item 175, REGENERATION RIDE-THROUGH TIME LILIa may keep bus up during brown out if there is sufficient regen energy from the load.


What are the causes and comments for OVERTORQUE TRIP Dc on the TOSHIBA P3 435K?

For OVERTORQUE TRIP Dc on the TOSHIBA P3 435K:

Cause: The drive’s torque current went above the current value programmed in Item 190, OVERTORQUE TRIP LEVEL DeL. The drive can be programmed to torque current limit; contact your Toshiba distributor and request the torque limit application guideline.


What are the causes and comments for EARTH FAULT (SOFT) EF I, EARTH FAULT (HARD) EF2 on the TOSHIBA P3 435K?

For EARTH FAULT (SOFT) EF I, EARTH FAULT (HARD) EF2 on the TOSHIBA P3 435K:

Cause: Drive detected some current to ground. Depending on rating, drive senses ground fault via ZCT (hard fault) or HCT (soft fault).

Comments: With leads disconnected from drive, meg motor and leads. Look for any moisture that may provide current path to ground. Make sure that control wiring is separated from power wiring. Adding noise supressors on coils of starters on same line as drive may snub noise picked up by ZCT. RF/EMI filter may help remove noise generated by SCR rectifiers in the vicinity. Make sure drive chassis and motor are grounded.


What are the causes and comments for AUTO-TUNING ERROR Een on the TOSHIBA P3 435K?

For AUTO-TUNING ERROR Een on the TOSHIBA P3 435K:

Cause: Motor’s physical characteristics are not within the window of allowable values for modeling.

Comments: Try a different inertia setting in Item 353, LOAD MOMENT OF INERTIA ile.IH. Motor must be at rest to perform auto-tuning. Motor must be one HP size within the drive’s HP size. Auto-tuning is best done with motor at full-load temperature (if temperature is very cold, auto-tune error may appear).


What is the cause for GATE ARRAY FAULT Err5 on the TOSHIBA P3 435K?

For GATE ARRAY FAULT Err5 on the TOSHIBA P3 435K:

Comments: Replace control board.


What are the causes and comments for CURRENT DETECT ERROR Errl on the TOSHIBA P3 435K?

For CURRENT DETECT ERROR Errl on the TOSHIBA P3 435K:

Comments: Occurs when drive is stopped but CPU detects current flowing. This fault could be caused by plugging in RS232 cable with drive powered (resulting in damage to control board). Adding a RF/EMI filter may remove noise spikes from nearby SCR rectifiers. If the control board is damaged, the drive must be serviced.


What is the cause and comment for INV TYPEFORM ERROR Ee~P on the TOSHIBA P3 435K?

For INV TYPEFORM ERROR Ee~P on the TOSHIBA P3 435K:

Cause: Control board is not configured to drive’s rating.

Comments: Enter option “7” into Item 310, STANDARD SETTING MODE SELECTION e~P.


What is the Drive Warning Display and Explanation for DAMPER TRIP dRnp on the TOSHIBA P3 435K?

For DAMPER TRIP dRnp on the TOSHIBA P3 435K:

Cause: Damper function is selected (one input terminal is assigned to 56 and one output terminal is assigned to 64). Every time a run command is issued, the output terminal will output a signal to open damper. Then waiting for the damper open full signal from the input terminal. After getting the damper open full signal from the input terminal, the motor will start to run. If the damper is closed while the motor is running, go damper trip.

Comments: Check the input damper status signal.


What is the Drive Warning Display and Explanation for IV ANALOG INPUT LOSS TRIP L055 on the TOSHIBA P3 435K?

For IV ANALOG INPUT LOSS TRIP L055 on the TOSHIBA P3 435K:

Cause: L R :5 = 3 and IV input voltage is less than 1 volt.

Comments: Check IV input voltage.


What are the Drive Warning Displays and Explanations for DC BUS UNDERVOLTAGE nOFF on the TOSHIBA P3 435K?

For DC BUS UNDERVOLTAGE nOFF on the TOSHIBA P3 435K:

Cause: The drive’s DC bus voltage went below approximately 413 VDC (460 volt drive), for at least the time entered in Item 184, UNDERVOLTAGE DETECT TIME UPc.

Comments: Item 164, UNDERVOLTAGE TRIP SELECTION turns the ability to undervoltage trip on/off.


What is the Drive Warning Display and Explanation for CONTROL POWER LOW POFF on the TOSHIBA P3 435K?

For CONTROL POWER LOW POFF on the TOSHIBA P3 435K:

Control Power low warning voltage levels are sensed on DC bus and are set slightly less than DC BUS UNDERVOLTAGE nOFF levels.


What is the Drive Warning Display and Explanation for OVERLOAD L on the TOSHIBA P3 435K?

For OVERLOAD L on the TOSHIBA P3 435K:

A flashing overcurrent display means that the drive is outputting more than 110% of its rated current. If Item 14, OVERLOAD SELECTION OLn is set to “1” or “3” (soft stall on), the drive’s output frequency will automatically decrease in an effort to reduce current. See suggestions for remedying an inverter overload trip on page 11-4. Setting one of the monitor’s functions (Items 319-322) to “10” will give an indication of how close a drive is to tripping.


What is the Drive Warning Display and Explanation for OVERCURRENT [ on the TOSHIBA P3 435K?

For OVERCURRENT [ on the TOSHIBA P3 435K:

A flashing overcurrent display means that the drive is stalling. (Stall level is set by Item 13, STALL PROTECTION CURRENT LEVEL 5EL:). The drive’s output frequency will automatically decrease.


What is the Drive Warning Display and Explanation for OVERVOLTAGE P on the TOSHIBA P3 435K?

For OVERVOLTAGE P on the TOSHIBA P3 435K:

A flashing overvoltage display means that the drive’s DC bus has exceeded 720 VDC (460 volt drive).


What is the Drive Warning Display and Explanation for OVERHEAT H on the TOSHIBA P3 435K?

For OVERHEAT H on the TOSHIBA P3 435K:

A flashing overheat display means that the drive’s heat sink temperature has exceeded 84deg C. Display dissappears when heatsink temperature reaches 80deg C.


What is the Drive Warning Display and Explanation for COMM c on the TOSHIBA P3 435K?

For COMM c on the TOSHIBA P3 435K:

A flashing comm display means that the drive has momentarily lost communications. Display will clear when follower receives valid reference. Cycling power or reinitializing drive will clear warning.


How is the input terminal information decoded for the TOSHIBA P3 435K?

The eleven input terminals for the TOSHIBA P3 435K correspond to the following bits in the ‘A’ group (input terminals 1 to 5) and ‘B’ group (input terminals 6 to 11):

‘A’ group (input terminals 1 to 5) bits correspond to (from right to left): Input terminal 1 (R), Input terminal 2 (S1), Input terminal 3 (S2), Input terminal 4 (S3), Input terminal 5 (S4).

‘B’ group (input terminals 6 to 11) bits correspond to (from right to left): Input terminal 6 (F), Input terminal 7 (RES), Input terminal 8 (ST), Input terminal 9 (S5), Input terminal 10 (S6), Input terminal 10 (S7).

Input terminal 5 (S4) indicates “when ON” or “when OFF” (upper half blank).


How is the output terminal information decoded for the TOSHIBA P3 435K?

The four output terminals for the TOSHIBA P3 435K correspond to the following bits (from left to right): Output terminal 1 (RCH), Output terminal 2 (LOW), Output terminal 3 (FL), Output terminal 4 (OUT): Option PCB. The operating status of the cooling fan and main contactor for the initial charging circuit are also displayed.

The bits correspond to: Cooling fan ON/OFF status, Main contactor for initial charging circuit status, Output terminal 4 (OUT) (when ON or when OFF (upper half blank)), Output terminal 3 (FL), Output terminal 2 (LOW), and Output terminal 1 (RCH).


What are the causes for the DBR OVERLOAD OL,- fault on the TOSHIBA P3 435K?

For DBR OVERLOAD OL,- on the TOSHIBA P3 435K:

Cause: Dynamic braking resistor is in danger of overheating (as determined by drive).

Comments: Check that the values entered into Item 162, BRAKING RESISTOR VALUE Pbr and Item 163, BRAKING RESISTOR CAPACITY Pb[P are correct.


CLICK HERE TO DOWNLOAD TOSHIBA P3 435K (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.