Free English TOSHIBA MMD-AP0186BHP-TR (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD TOSHIBA MMD-AP0186BHP-TR (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the specifications for the TOSHIBA MMD-AP0186BHP-TR air conditioner?
The specifications for the TOSHIBA MMD-AP0186BHP-TR are as follows:
For 50Hz operation:
| Category | Specification | Value |
|---|---|---|
| Electrical characteristics | Power supply | 1phase 50Hz 230V (220V-240V) |
| Running current (A) | 0.52 | |
| Power consumption (kW) | 0.077 | |
| Starting current (A) | 0.90 | |
| Dimension | Height (mm) | 275 |
| Width (mm) | 700 | |
| Depth (mm) | 750 | |
| Total weight (kg) | 23 | |
| Fan unit | Fan type | Centrifugal fan |
| Standard air flow (m³/h) (Med./Low) | 800 (660/540) | |
| Motor output (W) | 150 | |
| External static pressure (Pa) (factory setting) | 30 | |
| Connecting pipe | Gas side (mm) | 12.7 |
| Liquid side (mm) | 6.4 | |
| Drain port (mm) | 25 (Polyvinyl chloride tube) | |
| Sound pressure level (dB(A)) (High/Med./Low) | 33/29/25 | |
For 60Hz operation:
| Category | Specification | Value |
|---|---|---|
| Electrical characteristics | Power supply | 1phase 60Hz 220V |
| Running current (A) | 0.55 | |
| Power consumption (kW) | 0.077 | |
| Starting current (A) | 0.95 | |
| Dimension | Height (mm) | 275 |
| Width (mm) | 700 | |
| Depth (mm) | 750 | |
| Total weight (kg) | 23 | |
| Fan unit | Fan type | Centrifugal fan |
| Standard air flow (m³/h) (Med./Low) | 800 (660/540) | |
| Motor output (W) | 150 | |
| External static pressure (Pa) (factory setting) | 30 | |
| Connecting pipe | Gas side (mm) | 12.7 |
| Liquid side (mm) | 6.4 | |
| Drain port (mm) | 25 (Polyvinyl chloride tube) | |
| Sound pressure level (dB(A)) (High/Med./Low) | 33/29/25 | |
What are the parts ratings for the TOSHIBA MMD-AP0186BHP-TR?
| Part | Rating |
|---|---|
| Fan motor | 340W150-2 |
| Drain pump motor | MDP-1401 |
| Float switch | FS-0218-102 |
| Pulse motor | EFM-MD12TF-1 |
| Pulse motor valve | EDM-B40YGTF-3 |
| TA sensor | Lead wire length: 328 mm |
| TC1 sensor | Ø4 size lead wire length: 1200 mm Vinyl tube (Blue) |
| TC2 sensor | Ø6 size lead wire length: 1200 mm Vinyl tube (Black) |
| TCJ sensor | Ø6 size lead wire length: 1200 mm Vinyl tube (Red) |
What are the functions of the main components in the refrigerant cycle of the TOSHIBA MMD-AP0186BHP-TR?
| Functional part name | Functional outline |
|---|---|
| Pulse Motor Valve (PMV) | 1) Controls super heat in cooling operation 2) Controls under cool in heating operation 3) Recovers refrigerant oil in cooling operation 4) Recovers refrigerant oil in heating operation |
| Temp. Sensor (TA) | 1) Detects indoor suction temperature |
| Temp. Sensor (TC1) | 1) Controls PMV super heat in cooling operation |
| Temp. Sensor (TC2) | 1) Controls PMV under cool in heating operation |
| Temp. Sensor (TCJ) | 1) Controls PMV super heat in cooling operation |
How does the TOSHIBA MMD-AP0186BHP-TR behave when power is reset?
When the power supply to the TOSHIBA MMD-AP0186BHP-TR is reset, the unit performs the following actions:
1. Identification of outdoor unit: The outdoor unit is identified, and control is redirected according to the identification result.
2. Indoor fan speed and air flow direction control availability settings: Settings such as indoor fan speed and air flow direction control availability are replaced on the basis of EEPROM data.
3. Fault code clearing: If the power supply reset is performed after a fault, the check code is cleared. If the abnormality persists after the Start/Stop button on the remote controller is pressed to resume operation, the check code is redisplayed on the remote controller.
How can I select an operation mode on the TOSHIBA MMD-AP0186BHP-TR?
The operation mode of your TOSHIBA MMD-AP0186BHP-TR changes in response to a command issued via the remote controller. The available commands and their functions are:
| Remote controller command | Control outline |
|---|---|
| STOP | Air conditioner shutdown |
| FAN | Fan operation |
| COOL | Cooling operation |
| DRY | Drying operation |
| HEAT | Heating operation |
How can I perform a test operation of the indoor unit for the TOSHIBA MMD-AP0186BHP-TR?
The TOSHIBA MMD-AP0186BHP-TR has a check function to test the indoor unit’s operation singly, without communication with the remote controller or the outdoor unit. This should be used for short periods to avoid causing equipment trouble.
How to operate:
1. Short-circuit the CHK pin (CN71 on the indoor P.C. board). The operation mode will differ depending on the unit’s status at that time:
– Normal time: Both float switch (SW) and fan motor are normal.
– Abnormal time: Either the float SW or fan motor is abnormal.
2. During normal time only, if you also short-circuit the DISP pin (CN72 on the indoor P.C. board), you can set the indoor PMV to its minimum opening degree (30 pls). When the DISP pin is open, the maximum opening degree (1500 pls) can be obtained.
How to clear:
Open the CHK pin. The system will stop once but will automatically return to operation after several minutes.
| Normal time | Abnormal time | ||
|---|---|---|---|
| DISP pin open | DISP pin short circuit | ||
| Fan motor | (H) | (H) | Stop |
| Indoor PMV (*) | Max. opening degree (1500 pls) | Min. opening degree (30 pls) | Min. opening degree (30 pls) |
| Louver | Horizontal | Horizontal | Immediate stop |
| Drain pump | ON | ON | ON |
| Communication | All ignored | All ignored | All ignored |
| P.C. board LED | Lights | Lights | Flashes |
How do I set the indoor unit function DN code on my TOSHIBA MMD-AP0186BHP-TR?
To set the indoor unit function DN code on your TOSHIBA MMD-AP0186BHP-TR, you must use a wired remote controller and the system must be at rest. Follow these steps:
Step 1. Push the SET, TEMP up, and CL buttons simultaneously and hold for at least 4 seconds. The display will show the address of the header indoor unit, and the fan and louver of the selected unit will move.
Step 2. Each time you press the UNIT LOUVER button (left side), one of the indoor unit numbers under group control is displayed in turn. The fan and louver of the selected unit will move.
Step 3. Use the TEMP buttons to select the desired CODE No. (DN code) of the function you want to change.
Step 4. Use the TIME buttons to select the desired SET DATA associated with the selected function.
Step 5. Push the SET button. The display will change from flashing to steady.
– To change the selected indoor unit, go back to step 2.
– To change the selected function, go back to step 3.
Step 6. When the TEST button is pushed, the system returns to its normal off state.
How can I perform a frequency fixed operation (Test Run) on the TOSHIBA MMD-AP0186BHP-TR?
You can perform a test run on your TOSHIBA MMD-AP0186BHP-TR using either a wired or wireless remote controller.
In case of a wired remote controller:
1. Push the [CHK] button for 4 seconds or more. [TEST] will be displayed, and the unit will enter Test run mode.
2. Push the [ON/OFF] button.
3. Use the [MODE] button to set the mode to [COOL] or [HEAT]. Do not use any other mode.
4. The temperature cannot be adjusted during the test run. An error will be detected as usual. A frequency fixed operation is performed.
5. After the test run, push the [ON/OFF] button to stop the operation.
6. Push the [CHK] button to clear the test run mode. The [TEST] display will disappear, and the status will return to normal.
In case of a wireless remote controller:
1. Push the TEMPORARY button for 10 seconds or more. You will hear a “Pi!” sound, and the operation will change to test run. After approximately 3 minutes, a cooling operation will start forcibly. Check that cool air is blowing. If it doesn’t start, check the wiring.
2. To stop the test operation, push the TEMPORARY button once again (for about 1 second).
How can I read the error history on my TOSHIBA MMD-AP0186BHP-TR using the main remote controller (RBC-AMT32E)?
To access the error history (up to four errors are stored) on your TOSHIBA MMD-AP0186BHP-TR, follow this procedure while the system is at rest:
Step 1. Invoke the SERVICE CHECK mode by pressing the CHECK and SET buttons simultaneously and holding for at least 4 seconds.
Step 2. The letters “SERVICE CHECK” will light up, and the check code “01” will be displayed, indicating the most recent error. This will be accompanied by the indoor unit number to which the error is related and the specific check code.
Step 3. To view other error history items, press the TEMP up/down buttons to select another check code. The codes range from “01” (latest) to “04” (oldest).
Step 4. When you are finished, press the ON/OFF button to return to the normal display.
REQUIREMENT: Do not push the CL button, as this will erase the entire error history of the indoor unit.
How do I clear an error on my TOSHIBA MMD-AP0186BHP-TR using the wired remote controller?
Clearing an error of the outdoor unit:
This procedure clears the currently detected outdoor unit error for the refrigerant line connected to the indoor unit controlled by the remote. The indoor unit error is not cleared.
1. Push and hold the CL and TEST buttons for 4 seconds or longer to enter the service monitoring mode.
2. Push the TEMP button to set CODE No. to “FF”.
3. The display will count down from “0005” to “0000” at 5-second intervals. The error is cleared when “0000” appears.
4. Push the TEST button to return the display to normal.
Clearing an error of the indoor unit:
Push the ON/OFF button on the remote controller. Only the error of the indoor unit controlled by this remote controller will be cleared.
How do I use the monitoring function on the wired remote controller (RBC-ATM32E) for my TOSHIBA MMD-AP0186BHP-TR?
You can use the service monitoring mode to check sensor temperatures or the operation status of the remote controller, indoor unit, and outdoor unit.
Step 1. Push and hold the TEST and CL buttons for 4 seconds or longer to enter the service monitoring mode. The service monitor will light up, and the temperature for CODE No. 00 will appear first.
Step 2. Push the TEMP button to change to the CODE No. of the item you wish to monitor.
Step 3. Push the left part of the UNIT LOUVER button to change the item to monitor. This allows you to view the sensor temperature or operation status of the indoor and outdoor units in the refrigerant line.
Step 4. Push the TEST button to return the display to normal.
How do I read setting data from the EEPROM on my TOSHIBA MMD-AP0186BHP-TR?
To read the setting data from the EEPROM, including factory settings and any modifications, follow these steps:
1. Push the SET, TEMP up, and CL buttons simultaneously and hold for at least 4 seconds. In group control, the first unit number displayed is the header unit’s. The CODE No. (DN code) 10 will also be displayed, and the selected unit’s fan will turn on.
2. Each time the UNIT LOUVER button (left side) is pushed, the next indoor unit number in the group is displayed. The selected unit’s fan will operate.
3. Use the TEMP buttons to move the CODE No. up or down.
4. Change the CODE No. from 10 to 01 (for filter sign lighting time) and jot down the setting data displayed.
5. Change the CODE No. using the TEMP button and jot down the setting data for that code.
6. Repeat step 5 until all necessary setting data has been recorded. The DN codes range from 01 to FF.
7. When finished, push the TEST button to return the system to its normal off state. It may take about a minute for the system to become responsive.
CODE No. (DN code) necessary at minimum:
| DN | Contents |
|---|---|
| 10 | Type |
| 11 | Indoor unit capacity |
| 12 | Line address |
| 13 | Indoor address |
| 14 | Group address |
How do I write setting data to the EEPROM on my TOSHIBA MMD-AP0186BHP-TR after replacing a P.C. board?
After replacing a service P.C. board, the EEPROM is set to factory default values. Follow these steps to write the correct settings:
1. Push the SET, TEMP up, and CL buttons simultaneously and hold for at least 4 seconds. “ALL” will be displayed under UNIT No., and CODE No. 10 will be shown.
2. Push the left part of the UNIT LOUVER button to select the specific indoor unit number whose service board was replaced.
3. Use the TEMP buttons to move the CODE No. up or down.
4. First, set the type and capacity codes. This overwrites the factory defaults.
(1) Set CODE No. to 10.
(2) Use the TIME button to select the unit type.
(3) Push the SET button. The display should become steady.
(4) Use the TEMP button to set CODE No. to 11.
(5) Use the TIME button to set the capacity code.
(6) Push the SET button. The display should become steady.
(7) Push the TEST button to return the system to its normal off state.
5. Next, write any on-site setting changes (like addresses) by performing the tasks in step 1 again.
6. Use the TEMP button to set the CODE No. to 01 (filter sign lighting time).
7. Check the displayed value against the information you recorded or received from the customer. If there is a discrepancy, change the setting and push the SET button.
8. Use the TEMP button to change to the next CODE No. Check and change the setting if necessary.
9. Repeat steps 6 and 7 until all settings are checked.
10. When finished, push the TEST button to return the system to normal. For group operations, reconnect any disconnected group control wiring.
How do I remove and attach the air filter on my TOSHIBA MMD-AP0186BHP-TR?
1. Detachment
1) Slide the filter toward the opposite side of the arrow mark and then pull it out. If two filters are provided, pull out the first filter, and the second filter will be pulled out connected to it.
2. Attachment
1) Insert the filter into the filter rail toward the arrow mark, slide it until it stops, and then fix it. If two filters are provided, insert the second filter in the same direction after inserting the first one.
How do I remove and attach the drain pan on my TOSHIBA MMD-AP0186BHP-TR?
1. Detachment
1) Remove the drain cap and extract any accumulated water. Be sure to use a bucket to collect the water.
2) Loosen the screws that fix the bottom base (3 positions). For some models, you may need to remove 2 screws at the center.
3) As shown in the diagram, slide the bottom base in the arrow’s direction. The electric parts cover the bottom base, which will open using the hinge part as a shaft.
4) Hold the handle of the drain pan and pull it off slowly. CAUTION: Do not hold the drain socket, as this may cause water leakage.
2. Attachment
1) First, hook the thin side of the drain pan to the discharge panel and then push in the thick side.
2) Close the bottom base and fix it with screws.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD TOSHIBA MMD-AP0186BHP-TR (01) PDF DOCUMENT