SCHNEIDER ELECTRIC SMVS750I-CN (01) PDF SUMMARY:
What important instructions should be followed during installation and maintenance of the UPS and batteries?
Read the instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it.
What should I do if I see a “Danger” or “Warning” safety label?
Obey all safety messages that follow this symbol to avoid possible injury or death. The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
What does “DANGER” indicate?
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
What does “WARNING” indicate?
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
What does “CAUTION” indicate?
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
What does “NOTICE” indicate?
NOTICE is used to address practices not related to physical injury.
What are the general safety guidelines for this UPS?
- Adhere to all national and local electrical codes.
- This UPS is for indoor use only.
- To prevent the risk of fire or electric shock, install it in a temperature and humidity-controlled indoor area, free of conductive contaminants.
- The UPS must be installed indoors with a controlled environment free of excessive dust, corrosive air, or conductive dust.
- Keep it out of direct sunlight, water, and heat sources.
- Place the unit on a stable floor.
- Be sure that the mains socket outlet that supplies the UPS is installed near the UPS and easily accessible.
- Avoid using extension cords.
- The UPS must be connected to an earthed mains socket outlet.
- Connect the power cable directly to a wall outlet.
- Do not use surge protectors or extension cords.
- This UPS is designed to satisfy the requirement of PCs only.
- Do not connect printers, heaters, or copiers to the UPS.
What are the battery safety guidelines?
- Replace the battery at least every 5 years or at the end of its service life, whichever is earlier.
- Replace the battery immediately when the UPS indicates battery replacement is necessary.
- Replace batteries with the same number and type of batteries as originally installed in the equipment.
- Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when there is evidence of electrolyte leakage.
- Power off the UPS, unplug it from the AC input, and disconnect the batteries.
- Do not operate the UPS until the batteries have been replaced.
- Servicing of user-replaceable batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
- When replacing the battery, the UPS must be off, and its AC inlet unplugged.
- Do not dispose of batteries in a fire. The batteries may explode.
- Do not open or mutilate batteries. Released material is harmful to the skin and eyes and may be toxic.
- A battery can present a risk of electrical shock and burns by high short-circuit current.
- Contact with any part of a grounded battery can result in electrical shock.
- Remove watches, rings, or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect the charging source before connecting or disconnecting battery terminals.
- Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the source from ground.
- The UPS contains internal batteries and may present a shock hazard even when disconnected from AC power.
- The battery circuit is not isolated from the AC input, hazardous voltage may exist between battery terminals and ground. Test before touching.
- Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
- Do not remove the chassis cover. Servicing should be performed by a qualified engineer.
What is included in the package?
- User manual
- Software, User documentation CD
- USB cable
- China plug to IEC C13 plug (for models SMVS750I-CN, SMVS1000I-CN, SMVS1500I-CN, SMVS2000I-CN)
- China plug to IEC C19 plug (for model SMVS3000I-CN)
- RS232 cable
What are the rear panel features?
- USB Port
- Input Breaker
- AC Inlet
- Outlets
- Battery Connector
- RS-232 Serial Port
- Output Breaker (only for SMVS3000I-CN)
What are the front panel features?
- Front panel display, LCD
- POWER ON/OFF button
- Battery Mode
- Load Capacity
- Automatic Voltage Regulation (AVR)
- Battery Capacity
- On-line Mode
- UPS Status Information
What is the recommended rating for the input circuit breaker upstream of the UPS?
Before installing the UPS, be sure that the input circuit breaker on the UPS upstream is Type C rated at 16 A.
How do I connect the battery?
- Push the battery handle into the unit.
- Pull the battery handle and rotate.
How do I connect equipment and input power to the SMV UPS?
- Connect equipment to the battery backup outlets of the SMV UPS.
- Plug the SMV UPS power cord directly into a wall outlet, not into a surge protector or power strip.
- Press the POWER ON/OFF button to turn on the unit.
- NOTE: The SMV UPS should charge the battery for at least 8 hours to ensure sufficient runtime.
- Press the POWER ON/OFF button in 1~3 seconds. Confirm that the SMV UPS is on and is providing power to outlets.
How do I cold start the UPS?
Use the cold start feature to supply power to connected equipment from the UPS batteries when the UPS is off and there is no power utility.
- Press the POWER ON/OFF button. The display panel will illuminate.
- Press the POWER ON/OFF button again to supply battery power to the connected equipment.
When should the battery be connected and disconnected?
Connect the battery prior to operation. Disconnect the battery prior to transportation. Turn off the UPS and remove the input power cable before disconnecting the battery connector.
What management software is provided with the SMV UPS?
SMV UPS is provided with management software for unattended operating system shutdown, UPS monitoring, and UPS settings. Refer to http://www.se.com for more information.
What are the input voltage specifications?
The input voltage is 220/230(default)/240 VAC. The voltage range is 165-290 VAC ± 5 VAC for some models and 165-295 VAC ± 8 VAC for others.
What are the input breaker specifications?
The input breaker is 8 A for models SMVS750I-CN and SMVS1000I-CN, 12 A for SMVS1500I-CN, 20 A for SMVS2000I-CN, and 25 A for SMVS3000I-CN.
What is the input frequency range?
The input frequency range is 45-65 Hz (auto sensing) ±1 Hz.
What is the output voltage specification?
The rated output voltage is 220/230(default)/240 VAC.
What is the typical transfer time?
The typical transfer time is 2-6 ms, 12 ms max.
What is the output waveform?
The output waveform is a Pure Sinewave.
What is the typical charging time?
The typical charging time is 4-6 hours to recover to 90% capacity.
What are the operating temperature and humidity conditions?
The operating temperature and humidity are 0-90% RH @ 0-40 °C (non-condensing) for some models and 0-95% RH @ 0-40 °C (non-condensing) for others.
What is the noise level?
The noise level is < 45 dB.
What does it mean when the UPS beeps every 2 seconds?
The SMV UPS is running on battery.
What does it mean when the UPS is beeping continuously?
The SMV UPS has a low battery condition, and the battery run-time is very low.
What does it mean when the UPS is beeping continuously and the Load Capacity LED is illuminated?
The battery backup outputs are overloaded.
What does it mean when the UPS is beeping continuously and the fan error indicator is illuminated?
A fan error is detected.
What does it mean when the UPS is beeping every 4 seconds and the battery icon is illuminated?
The battery is near the end of its useful life or is damaged and needs to be replaced.
What should I do if the SMV UPS will not turn on?
- Press the POWER ON/OFF button to turn on the UPS.
- Be sure that the power cord is securely connected to the utility power outlet and AC power is available at the utility power outlet. Where applicable, check that the wall outlet is switched on or input breaker works properly.
What should I do if the connected equipment loses power?
- Connect the battery.
- Connect the SMV series UPS to AC power and recharge for 10 hours.
- Disconnect non-essential equipment one at a time to reduce the load on the UPS.
- Contact Schneider Electric Customer Support.
What should I do if the SMV series UPS is operating on battery power while connected to AC power?
- Be sure that the input plug of the UPS is securely connected to the utility power socket.
- Be sure that AC power is available at the utility power socket by connecting another device to the utility power socket.
- Reset the circuit breaker.
- Turn the SMV series UPS off. If the error message persists, contact Schneider Electric Customer Support.
What should I do if the Err message illuminates on the display interface?
- Turn the SMV series UPS off.
- Disconnect non-essential equipment from the outlets and turn the SMV series UPS on.
- If the error message persists, contact Schneider Electric Customer Support.
- Contact APC by Schneider Electric Customer Support.
What should I do if the SMV series UPS is beeping every 4 seconds?
- Be sure that the battery connector in the rear panel is connected.
- Contact Schneider Electric Customer Support if the SMV series UPS remains beeping with the battery connector securely connected.
What should I do if the SMV series UPS has an inadequate battery runtime?
- Leave the SMV series UPS connected to AC power for 10 hours while the battery charges to full capacity.
- As the battery ages, the runtime capability decreases.
- The battery is near the end of its useful life and should be replaced.
What is the warranty period for this product?
Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of two (2) years from the date of purchase.
What does the warranty cover?
Schneider Electric’s obligation under this warranty is limited to repairing or replacing, at its sole discretion, any such defective products.
What does the warranty not cover?
This warranty does not apply to equipment that has been damaged by accident, negligence, or misapplication, or has been altered or modified in any way.
What should I do if my unit needs to be repaired or replaced?
- Review the Troubleshooting section of the manual to eliminate common problems.
- If the problem persists, view the documents in the Schneider UPS Knowledge Base through the Schneider Electric Information Technology website, http://www.se.com.cn, and submit customer support requests, please contact Schneider Electric Customer Support. Tel: (+86) 400 810 1315.
- Note the model number, serial number, and date of purchase.
- Call Schneider Electric Customer Support and a technician will attempt to solve the problem over the phone.
- If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
- If the unit is under warranty, the replacement is free.
What are the limitations of the service provided by Schneider Electric?
The services are limited to UPS models sold and used in mainland China. The original warranty service will not be available if the user uses a UPS model sold in a non-Mainland China region, or the place of use is not in the Mainland China region. If Schneider Electric tests and inspections show that the failure does not exist or was caused by misuse, negligence, or incorrect transportation, storage, installation, debugging, or use by the end user or any third party, Schneider Electric will not take responsibility.
In what cases is no warranty service provided?
- Unauthorized repair or modification.
- Any act of replacing internal parts or missing internal parts.
- The appearance of the machine is damaged during transportation, storage, installation, debugging, or use.
- Wrong connection or use under improper voltage conditions.
- Improper on-site operation or other operations beyond the scope of use.
- Repair by personnel not designated by Schneider Electric.
- Use in corrosive environments.
- Use in exposure to the natural environment.
- Any liquid soaking or immersion.
- Irresistible natural factors (earthquakes, floods, mudslides, etc.).
- Fire, theft.
- Any change, damage, or removal of the Schneider Electric serial number.
What do the “O” and “X” symbols in the Hazardous Substances table indicate?
- O indicates that said hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
- X indicates that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
What are the limit values of the hazardous substances?
- Lead (Pb), Mercury (Hg), Hexavalent Chromium (Cr(VI)), Polybrominated Biphenyls (PBB), and Polybrominated Diphenyl Ethers (PBDE) limit is 1,000 PPM.
- Cadmium (Cd) limit is 100 PPM.