What are the installation requirements for the PHILIPS DYNALITE DDLEDC605GL?
The PHILIPS DYNALITE DDLEDC605GL must be installed in an approved enclosure by a qualified electrician. The installation must be in accordance with all national and local electrical and construction codes and regulations.
How do I mount the PHILIPS DYNALITE DDLEDC605GL?
The PHILIPS DYNALITE DDLEDC605GL is designed to be mounted on a standard DIN rail within an approved enclosure.
What are the dimensions and required clearances for the PHILIPS DYNALITE DDLEDC605GL?
The dimensions and required clearances for the device are as follows:
Dimensions:
Height: 95 mm (3.74 in)
Width: 105 mm (4.13 in)
Depth: 75 mm (2.95 in)
Clearances:
A minimum clearance of 45 mm (1.77 in) is required above and below the device for ventilation.
What are the operating environment specifications for the PHILIPS DYNALITE DDLEDC605GL?
The PHILIPS DYNALITE DDLEDC605GL is rated for the following environmental conditions:
Operating Temperature: 0°C (32°F) to 40°C (104°F)
Humidity: ≤ 90%
Pollution Rating: IEC Pollution Degree II
Safety Rating: IEC Overvoltage Category III
What are the power supply requirements for the PHILIPS DYNALITE DDLEDC605GL?
The PHILIPS DYNALITE DDLEDC605GL requires a Class 1 or Class 2 (UL) / SELV (CE and RCM) power supply with the following specifications:
Voltage: 10-24 V DC
Voltage Ripple: ± 2% ≤ 1 Vpp
Maximum Current: ≤ 20 A
What are the output channel specifications for the PHILIPS DYNALITE DDLEDC605GL?
The PHILIPS DYNALITE DDLEDC605GL has 6 output channels, each with the following specifications:
Current Range per Channel: 10 mA – 5 A
Mode: Voltage Mode
How should I wire the LED outputs on the PHILIPS DYNALITE DDLEDC605GL?
Connect the positive terminal (A+) of your LED load to the corresponding channel’s ‘A’ terminal and the negative terminal (K-) to the ‘K’ terminal. The wiring classification depends on the power supply used:
• To be wired as Class 1 when powered by a Class 1 power supply.
• To be wired as Class 2 when powered by a Class 2 power supply.
Wire size: ≤ 2.5 mm² (12+ AWG)
Terminal torque: 0.4 Nm (3.5 Lb-in)
Maximum wire length:
• ≤ 20 m at 24 V
• ≤ 10 m at 12 V
How do I wire a single power supply to the PHILIPS DYNALITE DDLEDC605GL?
For a single power supply configuration, bridge the two positive inputs (+V1 and +V2) and connect the single positive wire from your power supply. Connect the negative wire to the -COM terminal. The total load must not exceed 20 A.
Power input wire size: ≤ 5 mm² (10+ AWG)
Power input terminal torque: 0.6 Nm (5.5 Lb-in)
Maximum wire length from power supply:
• ≤ 2 m at 24 V
• ≤ 1 m at 12 V
How do I wire two separate power supplies to the PHILIPS DYNALITE DDLEDC605GL?
For a dual power supply configuration, connect one power supply to the +V1 and -COM terminals (for channels 1-3) and the second power supply to the +V2 and -COM terminals (for channels 4-6). The negative -COM terminals must be common.
Important constraints:
• The load on each power supply input (+V1 or +V2) must not exceed 15 A.
• The total combined current for both inputs must not exceed 20 A (*V2 + *V1 ≤ 20 A).
Maximum wire length from power supply:
• ≤ 2 m at 24 V
• ≤ 1 m at 12 V
How do I connect the PHILIPS DYNALITE DDLEDC605GL to a DyNet or DMX control network?
You can connect to a control network using either the screw terminals or the RJ12 port.
Using Screw Terminals (RS-485 DyNet):
Connect the network cable to the green terminal block with the following connections: SHLD (Shield), GND (Ground), D+ (Data+), D- (Data-).
• Wire size: 0.3 – 2.5 mm² (22-12 AWG)
• Terminal torque: 0.4 Nm (3.5 Lb-in)
Using RJ12 Port (RS-485 DyNet / DMX RX):
Plug an RJ12 cable into the port. The pinout is as follows:
1: GND
2: GND
3: D+
4: D-
5: +12 V
6: +12 V
How do I set the DMX 512 address for the PHILIPS DYNALITE DDLEDC605GL?
To set the DMX 512 start address, use the 10-position DIP switch on the front of the device. Each switch corresponds to a value (1, 2, 4, 8, 16, 32, 64, 128, 256, and X for the 10th switch). Set the switches to the ON position to sum their values to the desired DMX start address. For example, to set address 3, turn switches 1 (value 1) and 2 (value 2) to ON.
What should I do if the PHILIPS DYNALITE DDLEDC605GL causes radio or television interference?
If the PHILIPS DYNALITE DDLEDC605GL causes harmful interference to radio or television reception, which can be determined by turning the equipment off and on, you are encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Any modifications not approved by the manufacturer of this device could void the user’s authority to operate this device.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD PHILIPS DYNALITE DDLEDC605GL (01) PDF DOCUMENT