Free English PENTAIR MYERS CGL-43SW (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD PENTAIR MYERS CGL-43SW (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What are the indoor mounting instructions for the PENTAIR MYERS CGL-43SW?
Locate the control box in a convenient location, preferably close to the pump installation. The box may be secured to a wall or other stable vertical support by use of the four mounting holes located in the mounting feet on the top and bottom of the box.
The box should be mounted approximately 5 feet from the floor to the circuit breaker handle. Care should be taken to avoid mounting the control box under sweating pipes, faucets or other damp locations.
What are the outdoor mounting instructions for the PENTAIR MYERS CGL-43SW?
The control box may be mounted at the location of the pump and basin or may be mounted in a remote location. The box should be secured to a stable vertical support which in turn should be secured to a concrete basin or footer. The box could also be mounted to the side of the house or other stationary support if available within a reasonable distance. When selecting a location, you should consider the visibility of the alarm light.
The box may be secured by the use of four mounting holes located in the mounting feet on the top and bottom of the box. The box should be mounted approximately 5 feet from the ground to the circuit breaker handle.
What are the power supply wiring requirements for the PENTAIR MYERS CGL-43SW?
Run power supply lines to the control box and secure (knockouts are not supplied in this box). Select a convenient location on the bottom to enter the box with the power supply. Cut a hole with a chassis punch, caution should be taken not to get fiberglass chips in the components while cutting hole. After the hole is cut, any fiberglass particles must be removed from box. Failure to do so may result in premature component failure.
Connect incoming power to the circuit breaker top lugs and all necessary ground wires to the ground lug at the bottom of the box. The ground lug should be fastened to a good driven earth ground by one of the methods described in the National Electric Code.
NOTE: On single phase panels, the neutral terminal block (labeled “N” and located next to the circuit breaker) must be connected to the incoming power neutral line. If the incoming power does not have a neutral line, then the neutral terminal block should be jumpered to the ground lug.
How do I connect the pump cords to the PENTAIR MYERS CGL-43SW?
Run the wires from both pumps to the bottom of the control box by means of one of the methods described in your pump or basin installation instructions. A hole must be cut into the control box (use the same procedure as that described for incoming power supply lines).
Connect red, white and black wires to terminals marked M1, M2 and M3 (for 3 phase applications), or connect the red, white and black wires to terminals marked R, W and B (for 1 phase applications). Fasten green wire to ground lug.
WGL pumps may have an additional brown wire in the pump cord. This is for the seal leak probe and it should be connected to the terminal strip in the control box. See wiring diagram for the proper terminal connections.
How do I connect the float cords to the PENTAIR MYERS CGL-43SW?
See basin instructions for the proper depth at which to set the floats. Strip the float cord wires 3/8″, twist strands together, and connect black and white wires to terminal strip in the control box. See wiring diagram for the proper terminal connections.
What are the steps for operating the pumps on the PENTAIR MYERS CGL-43SW?
1. Make sure that all wires are inside the control box and not in a position to be pinched or shorted when the door is closed.
2. Turn on power to the control box.
3. Turn hand-off-auto switches to the “HAND” position. The pumps should start and the pump run lights should come on. (On duplex panels, this should be done for both pumps).
4. To put into service, put the hand-off-auto switch in the “AUTO” position. (On duplex panels, this should be done for both pumps). See basin instructions.
5. If unit does not operate as described, see troubleshooting chart.
How do I establish the correct rotation for three-phase pumps on the PENTAIR MYERS CGL-43SW?
Rotation of three phase pumps must be established by one of the two methods described below.
CAUTION: Keep hands and feet clear of impeller when checking rotation. Be sure to disconnect power to the control box while handling pumps. Make sure pump is wired and readied for rotation test before the control box is energized.
1. Before positioning pump in basin, run wires to control box. Lay the pump unit on its side and secure so that the starting torque of the motor will not cause the pump to roll. Energize the pump by turning the circuit breaker on and the hand-off-auto to “HAND”. The rotation should be counterclockwise as observed facing the bottom of the pump. If you do not get the proper rotation, disconnect the power to the control box and change the position of any two of the black motor leads in the terminal blocks.
2. Install the pump in the basin and run in some water so the pump can operate. Energize the pump by turning the circuit breaker on and the hand-of-auto switch to “HAND”. Let the pump pull the water down in the basin, and when the water reaches the bottom of the pump the rotation of the water can be observed. The water should rotate in a clockwise direction if the pump rotation is correct. If you do not get the proper rotation, disconnect the power to the control box and change the position of any two of the black motor leads in the terminal blocks.
How do I check the pump current draw for 3-phase pumps on the PENTAIR MYERS CGL-43SW?
1. Use an amprobe to check the amperage of any of the power leads going to the pump.
2. Turn the hand-off-auto switch to the “HAND” position and compare the amperage reading to the values shown on the chart.
3. If you get a reading of 0, make sure there is voltage to the motor leads. Push the overload reset button on the overload relay in the control panel. If you still do not get a reading either the motor has failed or there might be a wiring problem between the control panel and pump (improper connection in the junction box).
4. If you get high amperage readings on 2 wires and a zero reading on the third, you have a single phase condition which could be caused by one of the following:
A. One motor lead is not connected properly.
B. You have lost 1 phase of the 3 phase power coming into the panel.
C. One winding in the motor is open.
How do I check pump and float resistance on the PENTAIR MYERS CGL-43SW?
To check pump or float, disconnect incoming power and remove wires from the terminal block and with an ohmmeter check the measurements per chart.
| CORD MEASURED | ITEM MEASURED | CORRECT READING | OHMMETER SETTING | IF YOU GET ANY OTHER READING CHECK FOR THE FOLLOWING: |
|---|---|---|---|---|
| Power Cord | Motor Winding (1 Phase) | (See Chart) | R x 1 | Damaged winding or cord |
| Power Cord | Motor Winding (3 Phase) | (See Chart) | R x 1 | Damaged winding or cord |
| Power Cord | Ground to Motor Winding (Green to Red, Black or White) | Infinity to 200 | R x 100K | Damaged winding or cord moisture in motor |
| Power Cord | Ground to Seal Probe (Opt.) (Green to Brown) | Infinity to 200 | R x 100K | Water in seal chamber or damaged cord |
| Float Cord | Ground to Float Contacts (Green to Black or White) | Infinity to 200 | R x 100K | Water in float or damaged cord |
| Float Cord | Float Contacts (Black to White) | 0 – Float On Infinity-Float Off |
R x 1 | Switch has failed or damaged cord |
How do I test the contactor on the PENTAIR MYERS CGL-43SW?
1. Physically examine the contractor for badly burnt or sticking contacts. The contractor arm should move in and out freely.
2. Remove the wires on the coil to the contactor and measure the resistance. Zero the ohmmeter, and on the R x 1 scale you should read approximately 138 ohms.
3. Often a burnt coil can be spotted by merely looking to see if it is badly discolored or has a dark spot on it.
How do I test the 460 Volt transformer on the PENTAIR MYERS CGL-43SW?
1. Remove the wires from the primary side (H1-H4) and also from the secondary side (X2-XF-X1).
2. With an ohmmeter on the R x 1 scale touch terminals H1 and H4 (primary), you should get a reading of approximately 49.7 ohms for Simplex panels, and 21.5 ohms for Duplex panels.
3. With an ohmmeter on the R x 1 scale touch terminals X2 and X1 (secondary), you should get a reading of approximately 3.6 ohms for Simplex panels and 1.6 ohms for Duplex panels.
4. With an ohmmeter on the R x 1 scale touch terminals XF and X1, you should get a reading of 0. If you do not, replace the fuse.
How do I test the overload block on the PENTAIR MYERS CGL-43SW?
1. Remove the wires from the terminals on the side of the overload block.
2. With an ohmmeter on the R x 1 scale touch the two terminals, you should get a reading of 0. If you do not get this reading, push the large black reset button on the front of the overload block.
3. You may test the inner switching mechanism by pushing the small black button on the front of the overload block to trip the switch and pushing the large black button to reset it. If the inner switch does not work properly replace the overload block.
How do I check the overload heaters on the PENTAIR MYERS CGL-43SW?
Remove the heaters from the overload block and examine them for physical damage. A slight discoloration is normal, but if they are melted or warped they should be replaced.
How do I check the fuses on the PENTAIR MYERS CGL-43SW?
1. Pull the fuse out of the fuse block and check for continuity with an ohmmeter.
2. With an ohmmeter on the R x 1 scale, you should get a reading of 0. If you do not, replace it with the same type and rating that is shown on the decal located next to the fuse block.
What is the Simplex troubleshooting guide for the PENTAIR MYERS CGL-43SW?
| Problem | Position Hand-Auto Switch | Run Light | Check | CAUSE & REMEDY |
|---|---|---|---|---|
| Pump Does Not Turn Off | Auto | On | H-I | H. Float switch may have failed. Operate manually to see if basin pumps down and alarm goes off. Repair float if necessary. I. Pump or discharge line may be plugged. Pull pump and check discharge line and pump inlet. (CAUTION: Never put hands on grinder impeller unless power is turned off). |
| Pump Does Not Run | Hand | Off | A-C-B-D-F | A. Motor overload tripped. (1 PHASE ONLY) Reset by pushing Klixon overload reset button. If overload trips again, check power supply voltage. Check motor winding resistance, make sure pump shaft is not locked. (3 PHASE ONLY) Reset by pushing overload reset button. If overload does not trip again problem may be fixed. If overload trips again, check power supply voltage. Check motor winding resistance, make sure pump shaft is not locked. C. Tripped circuit breaker in control panel. Reset by pushing handle down to “OFF” position and resetting to “ON” position. Make sure that wires are not shorted and that the box is wired properly. B. Tripped circuit breaker or fuse at power supply panel. Reset breakers or replace fuses. If they continue to blow, check amp capacity of wire and breakers. Make sure it is wired properly and that you have the correct power supply system. D. Control circuit fuse blown. Check fuse per instructions. Replace fuse with same type and rating. F. May not be wired properly. Check wiring per wiring diagram. Make sure pump is connected to terminal block properly. |
| Pump Does Not Run | Auto | Off | A-F-C-B-E-D-H | (See remedies A, F, C, B, D above) E. Level in basin may not be high enough to turn switch on. Check basin. Run pump manually to see if pump operates properly. H. Float switch may have failed. Operate manually to see if basin pumps down and alarm goes off. Repair float if necessary. |
| Pump Does Not Run | Auto Or Hand | On | G-I | G. Too much water coming into basin. Reduce water flow. Pump may need servicing. I. Pump or discharge line may be plugged. Pull pump and check discharge line and pump inlet. (CAUTION: Never put hands on grinder impeller unless power is turned off). |
| Alarm Activates | Auto | Off | A-H-D-F | (See remedies A, H, D above) F. May not be wired properly. Check wiring per wiring diagram. Make sure pump is connected to terminal block properly. |
| Circuit Breaker Tripped | Auto-Off-Hand | Off | F-J | F. May not be wired properly. Check wiring per wiring diagram. Make sure pump is connected to terminal block properly. J. May be short circuit in wiring or pump power supply–Short in motor. Check wiring. (Short will not be located in control circuit unless control circuit fuse is blown). Check motor. (See chart for checking pump cables). |
| Fuse in Control Circuit Blown | Auto-Off-Hand | Off | G-H-K-I | G. Too much water coming into basin. Reduce water flow. Pump may need servicing. H. Float switch may have failed. Operate manually to see if basin pumps down and alarm goes off. Repair float if necessary. K. May be failed component operating coil. Check components per instructions. I. Pump or discharge line may be plugged. Pull pump and check discharge line and pump inlet. |
| Control Box Buzzes | Auto-Off-Hand | On Or Off | L | L. Wrong operating voltage or wrong voltage components. Check voltage and make sure relays and contactors are of proper voltage. |
What are the pump current draw and overload heater selection values for the PENTAIR MYERS CGL-43SW?
| MODEL | HP | VOLTAGE | PHASE | RPM | F.L.A. | L.R.A. | RESISTANCE BLK-WH | RESISTANCE BLK-RED | RESISTANCE WH-RED | HEATER | HEATER NO. |
|---|---|---|---|---|---|---|---|---|---|---|---|
| WGL20-01 | 2 | 208 | 1 | 3450 | 15.0 | 52.5 | 1.14-1.26 | 4.63-5.11 | 5.77-6.37 | — | — |
| WGL20-21 | 2 | 230 | 1 | 3450 | 12.5 | 44.0 | 1.46-1.62 | 7.20-8.00 | 8.66-9.62 | — | — |
| WGL20-03 | 2 | 208 | 3 | 3450 | 9.5 | 34.0 | 2.65-2.93 | 2.65-2.93 | 2.65-2.93 | K50 | 13621A091 |
| WGL20-23 | 2 | 230 | 3 | 3450 | 8.4 | 32.5 | 3.12-3.45 | 3.12-3.45 | 3.12-3.45 | K49 | 13621A062 |
| WGL20-43 | 2 | 460 | 3 | 3450 | 4.2 | 16.3 | 12.5-13.8 | 12.5-13.8 | 12.5-13.8 | K34 | 13621A104 |
WARNING: On 3 phase panels, overload heater elements are not factory installed in the overload relay. Elements must be purchased separately and correspond with the above chart. This must be done before the panel is put into service. Failure to install the elements before the panel is put into service, or failure to install the correct size elements, may result in pump failure. All pump and panel warranties will be void if the above guidelines are not followed.
CLICK HERE TO DOWNLOAD PENTAIR MYERS CGL-43SW (01) PDF DOCUMENT