Free English PANASONIC CU-E18HBEA (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.


CLICK HERE TO DOWNLOAD PANASONIC CU-E18HBEA (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.


How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.


What are the PANASONIC CU-E18HBEA safety precautions regarding electrical work?

Electrical work for the PANASONIC CU-E18HBEA must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed.


What is prohibited when servicing the PANASONIC CU-E18HBEA?

It is prohibited to modify the machine, part, or material during repairing service.


What should be done if the wiring unit for the PANASONIC CU-E18HBEA is supplied as a repairing part?

If the wiring unit is supplied as a repairing part, do not repair or connect the wire even if only a partial wire break exists. Exchange the whole wiring unit.


How should a fasten terminal be handled when servicing the PANASONIC CU-E18HBEA?

Do not wrench the fasten terminal. Pull it out or insert it straightly.


Who should install or service the PANASONIC CU-E18HBEA?

Engage a dealer or specialist for installation and servicing. If installation or servicing is done by the user and is defective, it will cause water leakage, electrical shock or fire.


What is required for the installation of the PANASONIC CU-E18HBEA?

Install according to the installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.


What accessories and parts should be used for the PANASONIC CU-E18HBEA installation and servicing?

Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.


Where should the PANASONIC CU-E18HBEA unit be installed regarding its strength and location?

Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.


What are the requirements for electrical work when installing the PANASONIC CU-E18HBEA?

For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.


Is an Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD) recommended for the PANASONIC CU-E18HBEA?

This equipment is strongly recommended to install with an Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.


What type of cable should be used for indoor/outdoor connection for the PANASONIC CU-E18HBEA?

Do not use a joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable. Connect the cable to the indoor unit tightly for indoor/outdoor connection. Clamp the cable so that no external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.


What is the required routing for wire connections in the PANASONIC CU-E18HBEA?

Wire routing must be properly arranged so that the control board cover is fixed properly. If the control board cover is not fixed perfectly, it will cause heat-up or fire at the connection point of the terminal, fire or electrical shock.


What must be avoided when installing or relocating the PANASONIC CU-E18HBEA?

When installing or relocating the air conditioner, do not let any substance other than the specified refrigerant, e.g., air, mix into the refrigeration cycle (piping). Mixing of air, etc., will cause abnormal high pressure in the refrigeration cycle and result in explosion, injury, etc.


Where should the PANASONIC CU-E18HBEA outdoor unit not be installed concerning verandas?

Do not install the outdoor unit near a handrail of a veranda. When installing the air-conditioner unit at a veranda of a high-rise building, a child may climb up to the outdoor unit and cross over the handrail, causing an accident.


What is the requirement for earthing the PANASONIC CU-E18HBEA equipment?

This equipment must be properly earthed. The earth line must not be connected to a gas pipe, water pipe, earth of lightning rod, and telephone. Otherwise, it may cause electric shock in case of equipment breakdown or insulation breakdown.


What should be done to prevent accidents involving small children and the PANASONIC CU-E18HBEA?

Keep away from small children, as the thin film may cling to the nose and mouth and prevent breathing.


What power supply cords should not be used for the PANASONIC CU-E18HBEA?

Do not use an unspecified cord, modified cord, joint cord, or extension cord for the power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation, or overcurrent will cause electrical shock or fire.


What is the correct procedure for tightening the flare nut on the PANASONIC CU-E18HBEA?

Tighten the flare nut with a torque wrench according to the specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage.


What should be done if using existing R22 pipes during installation of R410A models like the PANASONIC CU-E18HBEA?

In case of using existing R22 pipes during installation of R410A models, you must carry out pump down properly to collect back the refrigerant and oil before installing the new unit. The thickness of copper pipes used with R410A must be more than 0.6mm. Never use copper pipes thinner than 0.6mm. It is desirable that the amount of residual oil is less than 40 mg/10m.


When should the refrigerant piping be installed during the compressor run for the PANASONIC CU-E18HBEA?

During installation, install the refrigerant piping properly before running the compressor. Operation of the compressor without fixing refrigeration piping and valves in the opened condition will cause suck-in of air, abnormal high pressure in the refrigeration cycle, and result in explosion, injury, etc.


What should be done during pump down operation for the PANASONIC CU-E18HBEA?

During pump down operation, stop the compressor before removing the refrigerant piping. Removal of refrigeration piping while the compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in the refrigeration cycle, and result in explosion, injury, etc.


What should be confirmed after completing installation or service on the PANASONIC CU-E18HBEA?

After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts fire.


What should be done if there is refrigerant gas leakage during operation of the PANASONIC CU-E18HBEA?

Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts fire.


What caution should be observed regarding fingers or objects inside the PANASONIC CU-E18HBEA unit?

Do not insert your fingers or other objects into the unit; the high-speed rotating fan may cause injury.


Should parts other than original ones be used when servicing the PANASONIC CU-E18HBEA?

Must not use other parts except original parts described in the catalog and manual.


Where should the PANASONIC CU-E18HBEA unit not be installed regarding flammable gas leakage?

Do not install the unit at a place where leakage of flammable gas may occur. In case gas leaks and accumulates at the surrounding of the unit, it may cause fire.


What is the requirement for drainage piping installation for the PANASONIC CU-E18HBEA?

Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.


What is the instruction for tightening the flare nut on the PANASONIC CU-E18HBEA outdoor unit air inlet and aluminium fin?

Do not touch the outdoor unit air inlet and aluminium fin, it may cause injury.


What is the consideration for selecting the installation location for the PANASONIC CU-E18HBEA outdoor unit?

Select an installation location which is easy for maintenance.


What are the considerations for soldering with Pb free solder when servicing the PANASONIC CU-E18HBEA?

Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C). Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).


What are the methods for power supply connection to the PANASONIC CU-E18HBEA air conditioner?

Power supply connection to the air conditioner. Connect the power supply cord of the air conditioner to the mains using one of the following methods. The power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries, permanent connection of this room air conditioner to the power supply is prohibited.

i. Power supply connection to the receptacle using a power plug. Use an approved 15/16A (1.0 ~ 1.75HP) or 16A (2.0HP) or 20A (2.5HP) power plug with earth pin for the connection to the socket.

ii. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A (1.0 ~ 2.0HP) or 20A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap.


What precautions must be taken regarding refrigerant release during piping work for the PANASONIC CU-E18HBEA?

Do not release refrigerant during piping work for installation, servicing, reinstallation, and during repairing refrigerant parts. Take care of the liquid refrigerant, it may cause frostbite.


How many people may be required for installation or servicing work on the PANASONIC CU-E18HBEA?

It may need two people to carry out the installation or servicing work.


Where should the PANASONIC CU-E18HBEA appliance not be installed?

Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.


What is the caution regarding stepping on the PANASONIC CU-E18HBEA unit?

Do not sit or step on the unit; you may fall down accidentally.


What injury risk is associated with touching sharp parts of the PANASONIC CU-E18HBEA?

Do not touch the sharp aluminium fin; sharp parts may cause injury.


What is the PANASONIC CU-E18HBEA Indoor Unit Noise (H/L/QLo) in dB-A for 230V/240V?

The Indoor Noise (H / L / QLo) for the PANASONIC CU-E18HBEA is 41 / 30 / 27 dB-A for both 230V and 240V.


What is the PANASONIC CU-E18HBEA Outdoor Unit Noise (H/L) in dB-A for 230V/240V?

The Outdoor Noise (H / L) for the PANASONIC CU-E18HBEA is 47 / – / – dB-A for both 230V and 240V.


What is the standard piping length for the PANASONIC CU-E18HBEA?

The standard piping length for the PANASONIC CU-E18HBEA is 5.0 meters (16.4 ft).


What is the length range for piping for the PANASONIC CU-E18HBEA?

The length range for piping for the PANASONIC CU-E18HBEA is 3 (9.8 ft) to 30 (98.4 ft) meters.


What is the height difference allowed between the indoor and outdoor units for the PANASONIC CU-E18HBEA?

The I/D & O/D Height Different for the PANASONIC CU-E18HBEA is 20 meters (65.6 ft).


What is the recommended amount of additional refrigerant for the PANASONIC CU-E18HBEA based on piping length?

The additional gas amount is 20 g/m (0.2 oz/ft) for piping length beyond the rated length for the PANASONIC CU-E18HBEA.


What is the length for additional gas calculation for the PANASONIC CU-E18HBEA?

The length for additional gas calculation for the PANASONIC CU-E18HBEA is 10.0 meters (32.8 ft).


What is the indoor operation range (Dry Bulb and Wet Bulb temperatures in °C) for Cooling for the PANASONIC CU-E18HBEA?

The Indoor Operation Range for Cooling for the PANASONIC CU-E18HBEA is:

Maximum: Dry Bulb 32°C, Wet Bulb 23°C

Minimum: Dry Bulb 16°C, Wet Bulb 11°C


What is the indoor operation range (Dry Bulb temperature in °C) for Heating for the PANASONIC CU-E18HBEA?

The Indoor Operation Range for Heating for the PANASONIC CU-E18HBEA is:

Maximum: Dry Bulb 30°C

Minimum: Dry Bulb 16°C


What is the outdoor operation range (Dry Bulb and Wet Bulb temperatures in °C) for Cooling for the PANASONIC CU-E18HBEA?

The Outdoor Operation Range for Cooling for the PANASONIC CU-E18HBEA is:

Maximum: Dry Bulb 43°C, Wet Bulb 26°C

Minimum: Dry Bulb -10°C


What is the outdoor operation range (Dry Bulb and Wet Bulb temperatures in °C) for Heating for the PANASONIC CU-E18HBEA?

The Outdoor Operation Range for Heating for the PANASONIC CU-E18HBEA is:

Maximum: Dry Bulb 24°C, Wet Bulb 18°C

Minimum: Dry Bulb -10°C


What are the features of the PANASONIC CU-E18HBEA inverter technology?

The features of the PANASONIC CU-E18HBEA inverter technology include:

Wider output power range

Energy saving

Quick Cooling

Quick Heating

More precise temperature control


What is the refrigerant used for the PANASONIC CU-E18HBEA and what is its environmental benefit?

The PANASONIC CU-E18HBEA uses a Non-ozone depletion substances refrigerant (R410A).


What is the long installation piping capability for the PANASONIC CU-E18HBEA?

The PANASONIC CU-E18HBEA has long piping up to 30 meters.


What are some quality improvements in the PANASONIC CU-E18HBEA?

Quality improvements in the PANASONIC CU-E18HBEA include:

Random auto restart after power failure for safety restart operation

Gas leakage protection

Prevent compressor reverse cycle

Inner protector to protect compressor

Noise prevention during soft dry operation


What are some operation improvements in the PANASONIC CU-E18HBEA?

Operation improvements in the PANASONIC CU-E18HBEA include:

Quiet mode to reduce the indoor unit operating sound

Powerful mode to reach the desired room temperature quickly

24-hour timer setting


What serviceability improvement is included in the PANASONIC CU-E18HBEA?

The PANASONIC CU-E18HBEA includes a Breakdown Self Diagnosis function.


What are the dimensions for the PANASONIC CU-E18HBEA Indoor Unit and Remote Control?

The dimensions for the PANASONIC CU-E18HBEA Indoor Unit and Remote Control (in mm) are:

Height (I/D / O/D): 285 (11-1/4) / 750 (29-17/32)

Width (I/D / O/D): 750 (29-17/32) / 875 (34-15/32)

Depth (I/D / O/D): 370 (14-19/32) / 345 (13-19/32)

Remote Control: 118 (Width) x 136 (Height) x 19.5 (Depth) mm (approximate dimensions from diagram, not explicitly listed in table for indoor unit’s depth).


What are the weight specifications for the PANASONIC CU-E18HBEA Indoor Unit and Remote Control?

The weight specifications for the PANASONIC CU-E18HBEA Indoor Unit and Remote Control are:

Net (I/D / O/D): 18 (40) / 48 (106) kg (lb)


What are the pipe diameter specifications for the PANASONIC CU-E18HBEA?

The Pipe Diameter (Liquid / Gas) for the PANASONIC CU-E18HBEA is 6.35 (1/4) / 12.7 (1/2) mm (inch).


What is the maximum operating frequency of the PANASONIC CU-E18HBEA indoor fan motor in RPM for Cooling/Dry mode at SHi speed?

The maximum operating frequency of the PANASONIC CU-E18HBEA indoor fan motor in RPM for Cooling/Dry mode at SHi speed is 1700 rpm (Heat) and 1530 rpm (Cool).


What is the maximum airflow (m3/min) for the PANASONIC CU-E18HBEA outdoor unit in Cooling and Heating mode?

The maximum outdoor airflow for the PANASONIC CU-E18HBEA is 40.0 m3/min (1410 ft3/min) for both Cooling and Heating mode.


What is the refrigerant type and amount for the PANASONIC CU-E18HBEA?

The Refrigerant Type for the PANASONIC CU-E18HBEA is R410A, and the amount is 1.06 kg (37.4 oz).


What is the initial refrigerant oil amount for the PANASONIC CU-E18HBEA?

The initial refrigerant oil amount for the PANASONIC CU-E18HBEA is RB68A or Freol Alpha 68M (400 cm3).


How is the compressor frequency regulated by compressor discharge temperature for the PANASONIC CU-E18HBEA during operation protection?

The compressor frequency for the PANASONIC CU-E18HBEA is regulated as follows based on compressor discharge temperature:

If the compressor discharge temperature exceeds 112°C, the compressor will stop, occurring 4 times per 20 minutes, and the timer LED will be blinking (“F97” is to be confirmed).

The frequency is maintained between 90°C and 97°C.

The frequency is limited between 97°C and 110°C.

The compressor is OFF above 112°C.


What are the conditions for the compressor to stop when the Indoor Pipe Temperature Sensor indicates low temperature for the PANASONIC CU-E18HBEA during Heating Operation?

For Cold Draught Operation on the PANASONIC CU-E18HBEA, when indoor pipe temperature is low, cold draught operation starts where the indoor fan speed will be reduced.


What happens during Deice Operation for the PANASONIC CU-E18HBEA?

When outdoor pipe temperature and outdoor temperature is low for the PANASONIC CU-E18HBEA, deice operation starts where the indoor fan motor and outdoor fan motor stop and the operation LED blinks.


How is the compressor operating frequency regulated based on indoor heat exchanger temperature for the PANASONIC CU-E18HBEA during Overload Protection in Heating Operation?

The compressor operating frequency for the PANASONIC CU-E18HBEA during Overload Protection in Heating Operation is regulated according to the indoor heat exchanger temperature as shown below:

If the heat exchanger temperature exceeds 60°C, the compressor will stop.

Frequency is Limited between 55°C and 60°C.

Frequency is Free between 49°C and 55°C.

Operation is OFF below 49°C.


What causes the compressor to stop immediately due to Overheating Prevention Control on the PANASONIC CU-E18HBEA IPM?

When the IPM temperature rises to 110°C on the PANASONIC CU-E18HBEA, compressor operation will stop immediately. Compressor operation restarts after three minutes when the temperature decreases to 95°C.


What causes the compressor to stop due to DC Peak Current Control on the PANASONIC CU-E18HBEA IPM?

If the electric current to IPM exceeds the set value of 22.33 ± 5.0 A on the PANASONIC CU-E18HBEA, the compressor will stop operation. Then, operation will restart after three minutes. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two minutes. If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.


What are the X (A) and Y (A) current values for Cooling/Soft Dry (A) & (C) operation mode for the PANASONIC CU-E18HBEA?

For the PANASONIC CU-E18HBEA during Cooling/Soft Dry (A) & (C) operation mode, the current values are:

X (A): 8.83

Y (A): 15.06


What are the X (A) and Y (A) current values for Cooling/Soft Dry (B) operation mode for the PANASONIC CU-E18HBEA?

For the PANASONIC CU-E18HBEA during Cooling/Soft Dry (B) operation mode, the current values are:

X (A): 7.79

Y (A): 15.06


What are the X (A) and Y (A) current values for Heating operation mode for the PANASONIC CU-E18HBEA?

For the PANASONIC CU-E18HBEA during Heating operation mode, the current values are:

X (A): 10.08

Y (A): 15.06


What are the causes of H98 (Indoor High Pressure Protection) malfunction in the PANASONIC CU-E18HBEA?

The malfunction causes for H98 (Indoor High Pressure Protection) in the PANASONIC CU-E18HBEA include:

Air short circuit.

Clogged air filter of the indoor unit.

Dust accumulation on the indoor unit heat exchanger.

2/3 way valve closed.

Detection error due to faulty indoor fan motor.

Excessive refrigerant.

Clogged expansion valve or strainer.

Detection error due to faulty indoor pipe temperature sensor.

Detection error due to faulty indoor unit PCB.


What should be done if an H98 error is indicated for the PANASONIC CU-E18HBEA?

If an H98 error is indicated for the PANASONIC CU-E18HBEA, follow these troubleshooting steps:

  1. Check the air passage.
  2. If there is no short circuit, provide sufficient air passage.
  3. Check the indoor unit air filter.
  4. If the air filter is dirty, clean the air filter.
  5. Check the dust accumulation on the indoor unit heat exchanger.
  6. If the indoor unit heat exchanger is dirty, clean the indoor unit heat exchanger.
  7. Check the 2/3 way valve.
  8. If the 2/3 way valve is closed, open the 2/3 way valve.
  9. Check the indoor unit fan motor operation.
  10. If the indoor unit fan motor does not operate normally, replace the indoor unit fan motor and/or indoor unit PCB.
  11. Check refrigerant amount.
  12. If the additional refrigerant amount is not filled correctly, reclaim and recharge with correct amount of refrigerant.
  13. Check for clogged expansion valve or strainer.
  14. If the expansion valve or strainer is clogged (ice formed), replace the expansion valve and/or strainer, and reclaim and recharge refrigerant.
  15. Check the indoor pipe temperature sensor.
  16. If it does not conform to the sensor characteristic chart, replace the indoor pipe temperature sensor.
  17. If it conforms to the sensor characteristic chart, replace the indoor unit PCB.

What are the causes of F91 (Refrigeration Cycle Abnormality) for the PANASONIC CU-E18HBEA?

The causes of F91 (Refrigeration Cycle Abnormality) for the PANASONIC CU-E18HBEA include:

Refrigerant shortage (refrigerant leakage).

Poor compression performance of compressor.

2/3 way valve closed.

Detection error due to faulty indoor intake air or indoor pipe temperature sensors.


How do I troubleshoot F91 (Refrigeration Cycle Abnormality) on the PANASONIC CU-E18HBEA?

To troubleshoot F91 on the PANASONIC CU-E18HBEA:

  1. Check the indoor air intake and pipe temperature sensors.
  2. If it does not conform to the sensor characteristic chart, replace the indoor intake air or pipe temperature sensor.
  3. Check if the 2/3-way valve is opened.
  4. If the 2/3-way valve is closed, open the 2/3 way valve.
  5. Check for gas leakage.
  6. If oil is oozing out from the 2/3 way valve, repair the pipe flare or union nuts, reclaim and recharge refrigerant.
  7. Check if capillary tube or dryer is clogged.
  8. If the capillary tube or dryer is clogged, replace the capillary tube or dryer.
  9. Charge for a specified amount of fresh refrigerant.
  10. If the Refrigerant cycle abnormality error occurs again, replace the outdoor unit PCB and compressor.
  11. If the error does not occur again, the procedure is complete.

What conditions cause F93 (Compressor Rotation Failure) on the PANASONIC CU-E18HBEA?

The malfunction decision conditions for F93 (Compressor Rotation Failure) on the PANASONIC CU-E18HBEA is when a compressor rotation failure is detected by checking the compressor running condition through the position detection circuit.


What are the causes for F93 (Compressor Rotation Failure) on the PANASONIC CU-E18HBEA?

The malfunction causes for F93 (Compressor Rotation Failure) on the PANASONIC CU-E18HBEA include:

Compressor terminal disconnect.

Outdoor PCB malfunction.

Compressor malfunction.


How do I troubleshoot F93 (Compressor Rotation Failure) on the PANASONIC CU-E18HBEA?

To troubleshoot F93 on the PANASONIC CU-E18HBEA:

  1. Check the U, V, and W connector connection. Turn OFF the power, check the U, V, and W connection at the outdoor unit PCB and compressor terminal.
  2. If the connector connection is not normal, correct the connection.
  3. If the connector connection is normal, disconnect the harnesses U, V, and W from the compressor terminal.
  4. Turn ON the power and operate the inverter checker B LEDs blinking.
  5. If the 6 LEDs are blinking in the same sequence/condition, replace the compressor.
  6. If the 6 LEDs are not blinking in the same sequence/condition, replace the outdoor unit PCB.

What causes F95 (Cooling High Pressure Abnormality) on the PANASONIC CU-E18HBEA?

The malfunction decision condition for F95 (Cooling High Pressure Abnormality) on the PANASONIC CU-E18HBEA is when the outdoor unit heat exchanger high temperature data (61°C) is detected by the outdoor pipe temperature sensor during operation of cooling.


What are the malfunction causes for F95 (Cooling High Pressure Abnormality) on the PANASONIC CU-E18HBEA?

The malfunction causes for F95 (Cooling High Pressure Abnormality) on the PANASONIC CU-E18HBEA include:

Air short circuit at the outdoor unit.

Dust accumulation on the outdoor unit heat exchanger.

2/3 way valve closed.

Faulty outdoor unit fan motor.

Excessive refrigerant.

Clogged expansion valve or strainer.

Faulty outdoor pipe temperature sensor.

Faulty outdoor unit PCB.


How do I troubleshoot F95 (Cooling High Pressure Abnormality) on the PANASONIC CU-E18HBEA?

To troubleshoot F95 on the PANASONIC CU-E18HBEA:

  1. Check the outdoor air passage.
  2. If there is any short circuit, provide sufficient air passage.
  3. Check the dust accumulation on the outdoor unit heat exchanger.
  4. If the outdoor unit heat exchanger is dirty, clean the outdoor heat exchanger.
  5. Check the 2/3 way valve.
  6. If the 2/3 way valve is closed, open the 2/3 way valve.
  7. Check the outdoor unit fan motor operation.
  8. If the fan motor does not operate normally, replace the outdoor unit fan motor and/or outdoor PCB.
  9. Check refrigerant amount.
  10. If the additional refrigerant amount is not filled correctly, reclaim and recharge with correct amount of refrigerant.
  11. Check for clogged expansion valve or strainer.
  12. If the expansion valve or strainer is clogged (ice formed), replace the outdoor fan motor.
  13. Check the outdoor pipe temperature sensor.
  14. If it does not conform to the sensor characteristic charts, replace the outdoor pipe temperature sensor.
  15. If it conforms to the sensor characteristic charts, replace the outdoor unit PCB.

What causes F96 (IPM Overheating) on the PANASONIC CU-E18HBEA?

The malfunction decision conditions for F96 (IPM Overheating) on the PANASONIC CU-E18HBEA are:

During operation of cooling and heating, when IPM temperature data (100°C) is detected by the IPM temperature sensor.

Multi Models Only:

Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated.

Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.


What are the malfunction causes for F96 (IPM Overheating) on the PANASONIC CU-E18HBEA?

The malfunction causes for F96 (IPM Overheating) on the PANASONIC CU-E18HBEA include:

IPM overheats due to short circuit of hot discharge air flow.

IPM overheats due to defective of outdoor fan motor.

IPM overheats due to defective of internal circuitry of IPM.

IPM overheats due to defective IPM temperature sensor.

Multi Models Only:

Compressor OL connector poor contact.

Compressor OL faulty.


How do I troubleshoot F96 (IPM Overheating) on the PANASONIC CU-E18HBEA?

To troubleshoot F96 on the PANASONIC CU-E18HBEA:

  1. Check the outdoor unit installation condition during cooling or soft dry operation.
  2. If there is any improper heat radiation, reinstall the outdoor unit, remove the obstacle(s), and clean the outdoor heat exchanger.
  3. If there is no improper heat radiation, check if the outdoor fan motor is operating.
  4. If the outdoor fan motor is operating, the issue is a defect in IPM or the outdoor unit PCB needs replacing.
  5. If the outdoor fan motor is not operating, replace the outdoor fan motor.

What causes F97 (Compressor Overheating) on the PANASONIC CU-E18HBEA?

The malfunction decision condition for F97 (Compressor Overheating) on the PANASONIC CU-E18HBEA is when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor during operation of cooling and heating.


What are the malfunction causes for F97 (Compressor Overheating) on the PANASONIC CU-E18HBEA?

The malfunction causes for F97 (Compressor Overheating) on the PANASONIC CU-E18HBEA include:

Refrigerant shortage (refrigerant leakage).

2/3 way valve closed.

Detection error due to faulty compressor tank temperature sensor.


How do I troubleshoot F97 (Compressor Overheating) on the PANASONIC CU-E18HBEA?

To troubleshoot F97 on the PANASONIC CU-E18HBEA:

  1. Check the compressor tank temperature sensor.
  2. If it does not conform to the sensor characteristic chart, replace the compressor tank temperature sensor.
  3. If it conforms to the sensor characteristic chart, check if the 2/3 way valve is closed.
  4. If the 2/3 way valve is closed, open the 2/3 way valve.
  5. Check for gas leakage.
  6. If oil is oozing out from the 2/3 way valve, repair the pipe flare or union nuts, reclaim and recharge refrigerant.
  7. Check if the capillary tube or dryer is clogged.
  8. If the capillary tube or dryer is clogged, replace the capillary tube or dryer.
  9. Charge for a specified amount of fresh refrigerant.
  10. If the Refrigerant cycle abnormality error occurs again, replace the outdoor unit PCB and outdoor unit compressor.
  11. If the error does not occur again, the procedure is complete.

What causes F98 (Input Over Current Detection) on the PANASONIC CU-E18HBEA?

The malfunction decision condition for F98 (Input Over Current Detection) on the PANASONIC CU-E18HBEA is when an input over-current (15.06A) is detected by checking the input current value being detected by the current transformer (CT) with the compressor running during operation of cooling and heating.


What are the malfunction causes for F98 (Input Over Current Detection) on the PANASONIC CU-E18HBEA?

The malfunction causes for F98 (Input Over Current Detection) on the PANASONIC CU-E18HBEA include:

Over-current due to compressor failure.

Over-current due to defective outdoor unit PCB.

Over-current due to defective inverter main circuit electrolytic capacitor.

Over-current due to excessive refrigerant.


How do I troubleshoot F98 (Input Over Current Detection) on the PANASONIC CU-E18HBEA?

To troubleshoot F98 on the PANASONIC CU-E18HBEA:

  1. Get restarted and measure the input current.
  2. If the input current is greater than 15.06A, replace the outdoor unit PCB.
  3. If the input current is not greater than 15.06A, turn off the power supply. Check the main circuit electrolytic capacitor.
  4. If the main circuit electrolytic capacitor is normal, check the refrigerant amount.
  5. If there is excess refrigerant, repair the pipe flare or union nuts, and reclaim and recharge refrigerant.
  6. If there is no excess refrigerant, replace the outdoor unit PCB or replace the outdoor unit compressor.

What causes F99 (Output Over Current Detection) on the PANASONIC CU-E18HBEA?

The malfunction decision condition for F99 (Output Over Current Detection) on the PANASONIC CU-E18HBEA is when an output over-current (20.2A) is detected by checking the current that flows in the inverter DC peak sensing circuitry during operation of cooling and heating.


What are the malfunction causes for F99 (Output Over Current Detection) on the PANASONIC CU-E18HBEA?

The malfunction causes for F99 (Output Over Current Detection) on the PANASONIC CU-E18HBEA include:

DC peak due to compressor failure.

DC peak due to defective power transistor(s).

DC peak due to defective outdoor unit PCB.


How do I troubleshoot F99 (Output Over Current Detection) on the PANASONIC CU-E18HBEA?

To troubleshoot F99 on the PANASONIC CU-E18HBEA:

  1. Get restarted and measure the input current.
  2. If the input current is greater than 20.2A, replace the outdoor unit PCB.
  3. If the input current is not greater than 20.2A, check the compressor winding resistance (U-V, V-W, W-U) after turning off the power and disconnecting the harness U, V, and W from the terminal.
  4. If the compressor’s winding resistance (U-V, V-W, W-U) are not uniform, replace the compressor.
  5. If the compressor’s winding resistance (U-V, V-W, W-U) are uniform, replace the outdoor unit PCB.

When checking the power transistor, never touch any live parts for at least 10 minutes after turning off the circuit breaker. If unavoidable necessary to touch a live part, make sure the power transistor’s supply voltage is below 50V using the tester. For the UVW, make measurement at the Faston terminal on the board of the relay connector. The resistance measurement guide is:

Tester’s negative terminal Power transistor (+) UVW Power transistor (-) UVW
Tester’s positive terminal UVW Power transistor (+) UVW Power transistor (-)
Normal resistance Several kΩ to several MΩ 0 Ω or ∞

CLICK HERE TO DOWNLOAD PANASONIC CU-E18HBEA (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.